1. Introduction
1.1. Overview
The USR-DR13X series (including USR-DR134) is an ultra-small DIN rail mounting industrial-grade serial device server launched by PUSR. It facilitates two-way fast data transmission between RS232/RS485 and RJ45 Ethernet ports. This device integrates a TCP/IP protocol stack and Modbus gateway function, allowing direct integration into industrial scenarios, accelerating business framework construction, and reducing human resource investment.
These products support a wide voltage power supply via terminal block connectors, feature an RS232/RS485 serial port, and support baud rates from 600 to 230400bps. Designed for stability, they can operate reliably for 7x24 hours in harsh environments. The series has been rigorously tested and widely adopted across various industries, including finance, transportation, large company networks, and manufacturing, for diverse project solutions.1.2. Features
- Equipped with a deeply optimized TCP/IP protocol stack, offering low latency, strong scalability, stability, and reliability.
- 1.5KV built-in network Magnetic Isolation.
- Supports standard MQTT protocol for accessing MQTT platforms.
- Supports light edge computing, up to 25 points, with data reporting/writing in JSON mode.
- Supports user-defined web pages, allowing UI style customization.
- Wide baud rate: 600~230.4 Kbps, with multiple parity bit options: NONE, Odd, Even.
- Supports Modbus RTU to Modbus TCP protocol conversion and multi-host polling.
- Includes a keepalive mechanism for quick detection and reconnection of dead connections.
- Features hardware and software watchdog, ensuring automatic restarts if the device malfunctions.
- 10/100Mbps Ethernet port with Auto MDI/MDIX support.
- Operates across a wide industrial temperature range: -25°C to 75°C.
- Versatile operation modes: TCP Server, TCP Client, UDP, HTTP client.
- Supports virtual COM, COM Port Redirector USR-VCOM (windows).
- Easy configuration via built-in webpage and AT commands.
2. Setup and Installation
2.1. Hardware Interface Introduction
2.1.1. Dimensions
The USR-DR13X series features an ultra-small design, measuring 74mm (L) x 24mm (W) x 22mm (H), not including the terminal block. This compact size allows for installation in various scenarios, including small enclosures.

2.1.2. Serial Port
The USR-DR13X series utilizes a push-type terminal connector for convenient and quick wiring. The terminal wiring definitions are as follows:
| No. | Pin | Type | Description |
|---|---|---|---|
| 1 | DC 5-24V + | P | Positive input of the power supply |
| 2 | DC 5-24V - | P | Negative input of the power supply |
| 3 | RX/A | I/O | Serial signal |
| 4 | TX/B | I/O | Serial signal |
| 5 | GND | P | The digital ground |

2.1.3. Ethernet Port
The USR-DR13X series adopts a 10Base-T/100Base-TX adaptive Ethernet RJ45 interface, supporting automatic MDI/MDIX connection.
| Pin Number | Signal Name |
|---|---|
| 1 | Send data+ (TD+) |
| 2 | Send data- (TD-) |
| 3 | Receive data+ (RD+) |
| 6 | Receive data- (RD-) |
| 4, 5, 7, 8 | Unused |
2.1.4. LED Indicators
There are four indicators on the device: POW, WORK, COM, and LINK. Their descriptions are as follows:
| LED Name | Status | Description |
|---|---|---|
| Power (Red) | ON | Power supply is normal |
| OFF | No power supply or abnormal power supply | |
| Work (Green) | Blinking (Slow) | System is booted up and running |
| COM (Green) | Blinking (Fast) | The device is upgrading the firmware |
| OFF | The serial port does not send or receive data | |
| LINK (Green) | ON | 1. The TCP socket connection has been established 2. In UDP mode, it's always on |
| OFF | The TCP socket connection has not been established |
2.1.5. Reset to Factory Setting
- **Reload button**: Press and hold the Reload button for 3-15 seconds when powered on to restore factory settings.
- **AT command**: Use the `AT+CLEAR` command to reset the device to factory settings.
- **Software**: Perform a factory reset via the setup software or network configuration protocol.
2.2. Quick Test & Hardware Connection
To quickly set up your USR-DR13X serial server, you will need a PC, a router, the serial server, a network cable, a serial cable, and a DC5V/1A power supply. All devices must be connected to the same network (locally or via gateway) to establish a TCP/IP network.

3. Configuration and Parameter Details
3.1. Web Interface Configuration
Every USR-DR13X Industrial Serial Device Server has a built-in web server for convenient configuration. Access it by entering the device's IP address in your web browser (e.g., Edge, Firefox, or Google Chrome). You will be prompted for authentication; the default username and password are both "admin".
3.1.1. Status
After successful login, you will see the main page of the Web interface, which displays specific device information such as module name, IP address, and MAC address.
3.1.2. IP Settings
A valid and unique IP address must be assigned to the USR-DR13X within your network. If the device needs to access internet services like an NTP server, you must configure the DNS server to resolve hostnames.
3.1.3. Serial Port Settings
The serial device server's primary function is transparent data transmission between standard serial bus data (RS-232, RS-485) and standard Ethernet data (TCP/IP protocol). The Port configuration page allows you to set serial port and socket parameters.
3.1.4. System Parameters
This tab includes system-level settings such as device name, system log, username, and password. Most of these settings are optional.
3.2. Configuration Software
Parameters can also be configured using the dedicated configuration software. If the USR-DR13X is connected to the same gateway as your PC, the device can be accessed via broadcast packets. The software allows you to search for devices, modify parameters, and open the web server.
3.2.1. Download Software
Download the configuration software from the PUSR website:
- **Old version (for transparent transmission)**: Setup-Software-USR-MO-V2-2-6-1-exe.html
- **New version (for edge computing)**: Setup-Software-EthernetTool-V1-4-Edge-computing.html
- **Test software**: usr-tcp232-test-V13.html
It is recommended to set Network Parameters first using the configuration tool, then perform other device-specific configurations via the web interface.
4. Operation Modes
4.1. TCP Server
In TCP Server mode, the TCP connection is initiated by the host (TCP client) to the USR-DR13X. This mode supports up to 16 simultaneous connections. Once a connection is established, data can be transmitted bidirectionally. The work mode can be set in the "serial port" tab of the configuration interface.
4.2. TCP Client
When operating as a TCP client, the remote device must function as a TCP server. The USR-DR13X will initiate the TCP connection, and the remote server's IP and port must be configured accordingly.
4.3. UDP Server
UDP is a faster, more efficient, and connectionless transport protocol. When the USR-DR134 operates as a UDP server, it does not verify the source address. Upon receiving a UDP data packet, the destination IP and port are changed to match the sender of the UDP data.
4.4. UDP Client
In UDP client mode, the DR13X will only communicate with the configured target IP/Port. Data not originating from the target IP/Port will not be received by the DR13X.
4.5. HTTP Client
In HTTPD Client mode, the device can achieve data transmission between a serial port device and an HTTP server. Configure the HTTPD header and HTTP URL, along with other related parameters, to enable data transmission. The HTTP connection is a short connection; if the device does not receive data from the serial port within a preset time, it will actively disconnect (default is 3 seconds).
5. Modbus Gateway
The Modbus gateway function is available in firmware version V4304 and above, located in the edge gateway page. Enabling this function allows for Modbus TCP/RTU conversion, Modbus polling, and other related features.

5.1. Modbus RTU/TCP Conversion
This function enables the conversion between Modbus RTU and Modbus TCP protocols. The USR-DR13X supports serial master Ethernet slave mode, where the serial device acts as the Modbus master and the Ethernet device as the Modbus slave.
5.2. Modbus Multi-Host Poll
When enabled, the USR-DR13X supports multiple hosts sending query commands simultaneously without causing data conflicts.
5.3. Modbus Custom Polling
Users can configure the USR-DR13X to send custom Modbus-RTU query commands to serial devices. After each command, the device waits for a reply based on the polling timeout. If no reply is received, it sends the next query command after the polling interval. Up to 5 acquisition commands, each with a maximum of 16 bytes, can be set via AT commands.
5.4. Abnormal Response
If the DR13X fails to receive Modbus response data from the serial device within the set time limit or if the response data is incorrect, it will report an abnormal response to the network-end device.
6. Additional Features
6.1. Heartbeat Packet
The device can send heartbeat packets to the serial device at preset intervals. The content can be hex or string. This helps reduce communication pressure on the server. In TCP client and UDP client modes, the DR13X sends heartbeat data to inform the server it is online, and reconnects if data is not received from the serial device within a set time. The heartbeat function is closed by default.
6.2. Registration Packet
Available in TCP client and UDP client modes, registration packets allow servers to identify different clients. The content can be the MAC address of the DR13X, or user-defined. This is also used for registering to the PUSR cloud.

6.3. Index Function
The Index function addresses the challenge in TCP Server mode where multiple clients connect to the device and send/receive data simultaneously. It helps distinguish data sources and ensures data is sent to specific clients. When a TCP connection is established, the serial output includes the connection order. When clients send data, the DR13X prefixes it with a serial number (e.g., 11, 12). To send data to a specific client, prefix the data with its corresponding serial number (e.g., "01" for the first client).
6.4. User-Defined Webpage
The USR-DR13X supports user-defined webpages, allowing customization of the LOGO/NAME and UI style. You can download the original webpage from the PUSR website and upgrade it via the Ethernet Tool. The webpage file size should not exceed 172KB.
7. Specifications

| Category | Parameters | Value |
|---|---|---|
| Power Supply | Power Input | 5-24V DC |
| Working Current | 97mA@5V | |
| Power Interface | Push-type Connector | |
| Hardware Interface | Ethernet Port | 1*RJ45, 10/100Mbps, auto MDI/MDIX |
| Serial Ports | USR-DR132: 1*RS232 USR-DR134: 1*RS485 | |
| Baud Rate | 600~230.4K | |
| Data bits | 7, 8 | |
| Parity bit | Odd, Even, Mark, Space supported when data bits are 7; None, Odd, Even supported when data bits are 8 | |
| Stop bits | 1, 2 | |
| Reload Button | Reset to factory settings | |
| Indicators | POW, WORK, COM, LINK | |
| Physical Parameters | EMC Protection | IEC 61000-4-2 (ESD): Level 2 IEC 61000-4-4 (EFT): Level 2 IEC 61000-4-5 (Surge): Level 2 |
| Dimension | 74*24*22 mm | |
| Installation | 35mm DIN-Rail, Mounting Hole | |
| Operating Temperature | -40~85℃ | |
| Storage Temperature | -40~105℃ | |
| Operating Humidity | 5%~95% RH (non-condensing) | |
| Network Protocols | Network Protocols | TCP/UDP/HTTP/IPv4/ICMP/DHCP/ARP |
| IP Address | DHCP, Static | |
| DNS | DNS | Configurable DNS |
| Configuration | Configuration | AT Command, Built-in webpage, Config Utility |
| Work Mode | Work Mode | TCP Client, TCP Server, UDP Client, UDP Server, HTTP Client |
| Modbus Gateway | Modbus Gateway | Modbus RTU/TCP protocol conversion, Modbus Polling, Modbus RTU to Json |
| TCP Server | Up to 16 clients | |
| Packaging mechanism | Packaging Time: 4-byte data transmission time Packaging Length: 400 Bytes |
8. Maintenance
8.1. Firmware Upgrade
USR IoT continuously upgrades its firmware to add new features and optimize performance. Contact sales for the latest firmware version. To upgrade, right-click the device in the Ethernet Tool and select "Firmware upgrade." Ensure the device is on the same LAN network as your PC, and close any firewalls or other network adapters to prevent upgrade failure.8.2. Restart Device
To reset the serial device server, right-click the device in the configuration software and select "Restart." This action disconnects both Ethernet and serial connections and saves new configuration settings to flash memory.8.3. Restore to Factory Default Settings
The configuration utility provides a function to restore the serial device server to factory default settings. If you wish to do so, click the "Reset" button in the software.
9. Troubleshooting
- **Connection Issues**: Ensure all devices (PC, router, serial server) are connected to the same local network. Verify network cables are properly connected.
- **IP Address Conflicts**: Ensure the USR-DR13X has a unique IP address within your network. If connecting directly to a PC, ensure the PC's IP address is in the same subnet as the device.
- **Parameter Mismatch**: Double-check that serial port parameters (baud rate, data bits, parity, stop bits) match between the USR-DR13X and the connected serial device.
- **Abnormal Modbus Response**: If the device fails to receive a Modbus response or receives an incorrect one within the timeout period, it will report an abnormal response to the network-end device. Review Modbus polling settings and device communication.
- **Firmware Upgrade Failure**: Ensure firewalls and other network adapters are disabled during firmware upgrades. The device must be on the same LAN as the PC.
- **Data Transmission Issues**: If data is not transmitting successfully, verify the configured operation mode (TCP Server/Client, UDP Server/Client, HTTP Client) and ensure remote IP/Port settings are correct. For UDP Client mode, ensure data is from the target IP/Port.
10. User Tips
- **Initial Setup**: Always start by configuring network parameters (IP type, IP address, subnet mask, gateway, DNS) using the configuration software for a smooth initial setup.
- **Web Interface vs. Software**: For detailed and user-friendly configuration, the built-in web interface is generally recommended. The software is useful for initial device discovery and basic settings.
- **Modbus Polling**: When using Modbus custom polling, ensure your AT commands for query are correctly formatted and the device is restarted after sending them.
- **Data Filtering**: Utilize UDP data filtering in UDP Client mode to prevent unwanted data from non-target sources, improving data integrity and reducing processing load.
- **Keepalive & Watchdog**: Leverage the heartbeat packet and watchdog features for enhanced reliability, ensuring the device remains connected and automatically recovers from unexpected issues.
11. Warranty and Support
11.1. Warranty
The information provided in this document is in connection with Jinan USR IoT Technology Ltd. and/or its affiliates' products. No license, express or implied, is granted for any intellectual property rights. USR IoT and/or its affiliates assume no liability and disclaim any express, implied, or statutory warranty relating to its products, including, but not limited to, the implied warranty of merchantability, fitness for a particular purpose, or non-infringement. In no event shall USR IoT and/or its affiliates be liable for any direct, indirect, consequential, punitive, special, or incidental damages.
11.2. Contact Us
Jinan USR IoT Technology Limited
- Address: Floor 12 and 13, CEIBS Alumni Industrial Building, No. 3 Road of Maolingshan, Lixia District, Jinan, Shandong, China
- Official Website: https://www.pusr.com
- Official Shop: https://shop.usriot.com
- Technical Support: http://h.usriot.com/
- Inquiry Email: inquiry@usriot.com
- Skype & WhatsApp: +86 13405313834
- Tel: +86-531-88826739
- Fax: +86-531-88826739-808
12. Revision History
| Version | Date | Author | Description |
|---|---|---|---|
| V1.0.3.01 | 2017-09-20 | Established | |
| V1.0.4 | 2023-07-03 | May Liu | 1. Add description of Modbus Gateway 2. Add description of Multicast |
| V1.0.5 | 2024-01-24 | May Liu | 1. Add description of MQTT gateway, edge computing, user-defined webpage and firmware upgrading. 2. Modify the description of Modbus gateway |