1. Introduction
This manual provides detailed instructions for the installation, operation, and maintenance of the Erilles Load Cell Signal Conditioner Transmitter Module. This versatile module is designed to convert signals from Wheatstone bridge type load cells into standard industrial outputs: 0-5V, 0-10V, or 4-20mA. It features high precision, good stability, and is suitable for various weighing and pressure sensing applications.
2. Specifications
| Parameter | Value |
|---|---|
| Power Supply | DC 12-24V |
| Output Signal (Version A) | 4-20mA current output |
| Output Signal (Version B) | 0-5V / 0-10V voltage output |
| Input Signal | Wheatstone bridge type load cell |
| Excitation Voltage | 5VDC |
| Working Temperature | -20°C ~ +70°C |
| PCB Size | Round board, diameter approx. 38mm |
| Theory | Resistance Sensor |
| Material | Polymer |
| Type | Optical-Electronics Sensor |
| Output Type | Digital Sensor |
| Use | Pressure Sensor |
| Customizable | Yes |
| Package Dimensions (L x W x H) | 20cm x 20cm x 10cm |
| Package Weight | 0.2 kg |
3. Setup and Wiring
Ensure the module is powered off before making any connections. Connect your Wheatstone bridge type load cell to the module according to the diagrams below. The module supports 4-wire load cells.
3.1. Wiring for 0-5V / 0-10V Module
- Sensor Signal - (S-)
- Sensor Signal + (S+)
- Sensor Excitation - (E-)
- Sensor Excitation + (E+)
- Power Supply V+ (12-24V)
- GND (Ground)
- Signal Out - (O-)
- Signal Out + (O+)
3.2. Wiring for 4-20mA Module
- Sensor Signal - (S-)
- Sensor Signal + (S+)
- Sensor Excitation - (E-)
- Sensor Excitation + (E+)
- Power Supply V0 (Ground)
- Power Supply V+ (12-24V)
- Output Current: 4-20mA
4. Operation and Calibration
The module requires calibration to ensure accurate readings from the connected load cell. Use the "Zero Adj" and "Span Adj" potentiometers for this process.
4.1. Zero Adjustment (ZERO ADJ)
This potentiometer is used to set the module's zero output when the load cell is unloaded. For voltage output, adjust until the output is 0V. For current output, adjust until the output is 4mA.
4.2. Span Adjustment (SPAN ADJ)
This potentiometer is used to set the output value when a standard weight (rated load) is applied to the load cell. For voltage output, adjust until the output matches the target voltage (e.g., 5V or 10V). For current output, adjust until the output is 20mA.
4.3. Calibration Steps
- Power the module and ensure the load cell is connected correctly.
- With no load applied to the load cell, adjust the Zero potentiometer until the output is at 0 (for voltage output) or 4mA (for current output).
- Apply the rated load to the load cell.
- Adjust the Span potentiometer until the output matches the target value (e.g., 10V or 20mA).
- Repeat the zero and span adjustment steps several times until the readings are stable and accurate. This iterative process helps compensate for any interaction between the two adjustments.
5. Maintenance and Precautions
- During soldering, always use standard rosin flux. Avoid using corrosive flux, as it can damage the PCB.
- Do not wash the PCB after soldering, as cleaning agents may cause potential issues or damage components.
- Zero and span adjustments may interact. It is crucial to repeat the calibration process several times to achieve optimal accuracy and stability.
- If using the module with other sensors, carefully refer to the pin definitions to ensure correct connections. Do not connect randomly.
- Do not swap the positions of the zero and span adjustment potentiometers.
- The module is designed for durability and has good protection/sealing, making it suitable for environments with dust.
6. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| No output or incorrect output | Incorrect wiring; insufficient power supply; faulty load cell; module damage. | Verify all wiring connections against the diagrams. Ensure power supply is within DC 12-24V. Test the load cell independently. Inspect module for visible damage. |
| Unstable or drifting readings | Improper calibration; environmental interference (temperature, vibration); faulty load cell. | Perform calibration steps carefully, repeating zero and span adjustments. Ensure stable operating environment. Check load cell for damage or instability. |
| Output does not match expected range | Incorrect span adjustment; wrong module version (e.g., 0-5V instead of 0-10V). | Re-calibrate the span with the rated load. Confirm the correct module version is being used for the desired output range. |
7. User Tips
- This module is highly accurate and provides stable, precise data, making it suitable for demanding industrial applications and weighing systems.
- Users have reported seamless integration with existing equipment and consistent accuracy over time.
- The module is generally easy to calibrate and set up, contributing to smoother production processes.
- It is compatible with 4-wire load cells.
- The module exhibits stable performance even under heavy use and maintains accuracy after continuous operation.
- The terminal blocks are noted for their high quality.
- The module's design offers good protection and sealing, allowing it to function effectively in dusty environments.
8. Warranty and Support
For specific warranty information and technical support, please refer to the official seller or manufacturer. A detailed user manual in PDF format is available for download: User Manual (PDF).