Introduction
This manual provides detailed instructions for the LCTC Advanced Digital Temperature Controller. Please read it carefully before installation and operation to ensure proper use and optimal performance.
The LCTC PID Temperature Controller offers precise temperature control with a variety of input and output options, including SSR, Relay, 4-20mA, and 0-10V. It features a three-color LCD VA display, bar graphic, and advanced PID control algorithms with auto-tuning. RS485 Modbus communication is also supported for integration into larger systems.

Key Features
- Display: LCD three-color VA display, bar graphic, output percentage MV1/MV2 or feedback MVFb display.
- Accuracy: 0.2% measuring accuracy, maximum resolution 0.1 for TC and RTD input.
- Output Types: Relay, SSR drive, analog (4-20mA, 0-10V), triac, re-transmission.
- Alarms: AL1/AL2 relay output, excitation, non-excitation, delay output, alarm lock function. Alarm modes include PV, deviation, absolute, band, alarm standby, PV deviation alarm ramp start-up, ramp end alarm, Loop break alarm, heater break alarm. Up to 2 alarms.
- Control Modes: PID with auto-tuning, on/off, heating or cooling, heating+cooling, 3-wires proportional valve control, valve control with feedback signal, output restrain.
- Program Versions: PID mode, ramp up mode, temp constant mode, soft-start.
- Add-on Features: Auto/manual control, run/stop function, even SV input.
- Communication: RS-485, Modbus-RTU, pattern 8-(N,O,E)-(1,2).
- Ambient Conditions: Temperature 0-50°C, Humidity 0-80%RH.
Specifications
Model Information
| Model | Panel Size (width x height) |
|---|---|
| LCD108 | 48x48mm |
| LCD408 | 48x96mm |
| LCD708 | 72x72mm |
| LCD908 | 96x96mm |
General Specifications
- Brand Name: LCTC
- Origin: Mainland China
- Use: Industrial
- Certification: CE
- Display Size: 1.9 Inches & Under
- Battery Included: No
- High-concerned chemical: None
Input Sensor Types and Ranges

Note: The accuracy is not guaranteed for type S thermocouple in the range of 0-100. Analog input types (except 0-50mA, 10-50mV) need to be specified when ordering.
Setup
Mounting Dimensions

Wiring Diagram
The following diagrams illustrate general wiring connections. Always refer to the connection stickers on the side of your specific controller for detailed application wiring.


Power Source
- A: 85-265Vac 50/60Hz
- B: 24Vac/24Vdc
Auxiliary Power Source (AUX)
- N: No aux power
- B: 24Vdc grounded
- D: 12Vdc grounded
- A: 24Vdc isolated
- C: 12Vdc isolated
Operating Instructions
Panel Description

- PV window: Displays Process Value (PV) and parameter notation.
- SV window: Displays Set Value (SV) and parameter value.
- Bar graphic: Indicates output%, feedback value, or re-transmission value.
- OP1/OP2: Indicate output status.
- ATU: Indicate auto-tuning status.
- AL1/AL2: Indicate alarm status.
- COM: Communication indication.
- PRG: Temp constant mode indication.
- MAN: Manual control/soft-start indication.
- SET: Main function key.
- A/M: Auto/manual switch key and enter key.
- F3 (Shift key): Used for shifting digits or fast ATU initiation.
- F2 (Numeric decrease): Decreases numeric values.
- F1 (Numeric increase/Run/Stop): Increases numeric values or activates Run/Stop.
Power-on Initialization
Upon power-on, the display will show the software version and edition, input type, and setting value range before entering normal PV/SV display mode.
Changing SV (Set Value)
To change the SV, use the shortcut key:
- From the PV/SV display mode, press the SET key once to enter SV configuration parameter.
- The upper display shows SV, and the lower display shows the current SV value with the unit's digits flashing. Use F1/F2 to change the value and F3 to shift the flashing digit.
- After modifying, press SET to save the configuration or A/M to save changes and exit. If left idle for 3 seconds, the controller will return to PV/SV display mode without saving.
Parameter Menu Navigation (F Menu)
The controller features a comprehensive parameter menu for advanced configuration. To access the F menu:
- From the PV/SV display mode, press SET and F3 keys simultaneously to enter the password interface.
- Enter password '0033' using F1/F2 and F3 keys, then press SET to enter the F menu.
- Use F1 or F2 to shift between F00-F08 menu groups.
Quick Start Menu Level 1 (6.1.1)
Press SET once from PV/SV mode to enter this menu. It displays monitoring parameters like MV1 and MV2, auto-tuning status, and alarm values.
Quick Start Menu Level 2 (6.1.2)
Press SET for 3 seconds from PV/SV mode to enter this menu. It allows setting input offset, proportional band (P), and integral time (I).
Quick Start Menu Level 3 (Custom Menu)
This is a customizable menu accessible with password '0808'. It allows users to group frequently used parameters to prevent unauthorized access.
Auto-Tuning (7. Auto-Tuning)
Auto-tuning helps the controller automatically determine optimal PID parameters for stable temperature control.
- Enter the F02 menu group and locate 'AT'.
- Change the 'AT' value from 'NO' to 'YES' to activate auto-tuning.
- During auto-tuning, the AT light will flash. It will turn off when auto-tuning is complete, and PID values will be calculated automatically.
Note: Auto-tuning is an ON/OFF control mode. It is recommended to start auto-tuning at ambient temperature for best results. Auto-tuning will terminate if manual mode or STOP mode is entered, or if power is interrupted.
Auto/Manual Control Switch (8. Auto manual control switch)
The controller supports both automatic and manual control modes.
- Via Parameter Menu: Locate 'AM.RS' under F02 group. Set it to 'MAN' for manual control or 'Auto' for automatic control.
- Via Front Panel: If 'KA/M=1' under PASS-0303 menu, the A/M shortcut key on the front panel is enabled. Press A/M for 2 seconds to switch between auto and manual modes.
RUN/STOP Function (9. RUN/STOP function)
The controller can be set to RUN or STOP mode.
- Via Parameter Menu: Go to F02 menu and locate 'AM.RS'. Set it to 'Stop' for STOP mode or 'Auto' for RUN mode.
- Via Front Panel: If 'KR/S=1' under PASS-0303 menu, the F1 shortcut key is enabled. Press F1 for 2 seconds to switch between RUN/STOP.
Temperature Constant Mode and Ramp/Soak Mode (13. Temp constant mode and ramp/soak mode)
This feature is applicable for programmable versions of the controller. It allows for controlled temperature changes over time.
Maintenance
Regular maintenance is crucial for the longevity and optimal performance of your LCTC PID Temperature Controller. While specific maintenance schedules are not detailed in this manual, general best practices include:
- Keep the device clean and free from dust and debris. Use a soft, dry cloth for cleaning.
- Ensure proper ventilation around the controller to prevent overheating.
- Periodically check all wiring connections for tightness and signs of wear or corrosion.
- Avoid exposing the controller to excessive moisture, extreme temperatures, or corrosive environments.
Troubleshooting
This section provides general guidance for common issues. For complex problems, refer to the detailed parameter settings in the full user manual (PDF) or contact technical support.
Common Issues and Solutions:
- No Display/Power: Check power connections (AC85-265V or 24Vac/24Vdc) and ensure they are secure. Verify the power source is active.
- Incorrect Temperature Reading (PV): Ensure the correct input sensor type is selected in the parameters (INP1). Check sensor wiring for proper polarity and connection. Calibrate the input offset (PVOS) if necessary.
- Output Not Activating: Verify the Set Value (SV) is correctly configured and the Process Value (PV) is within the desired control range. Check output wiring (Relay, SSR, Analog) and ensure the load is correctly connected. Confirm the control mode (PID, ON/OFF) is appropriate for the application.
- Unstable Temperature Control: Perform auto-tuning (refer to section 7) to optimize PID parameters. Check for external disturbances affecting the sensor or heating/cooling element.
- Alarm Not Triggering: Verify alarm settings (AL1, AL2 values, alarm mode ALd1/ALd2) are correctly configured. Check alarm output wiring.
- Communication Issues (RS485): Check RS485 wiring (A+, B-). Verify communication parameters (baud rate, data format, device address) are correctly set in the controller and the master device.
User Tips
- PID Tuning: For optimal and stable temperature control, always perform auto-tuning after initial setup or if the process characteristics change. This helps the controller adapt to your specific system.
- Output Type Selection: Choose your output type (SSR, Relay, 4-20mA, 0-10V) based on your application needs. SSR (Solid State Relay) offers faster switching and is ideal for precise control, while mechanical relays are suitable for slower processes.
- Manual Clarity: While the device is generally easy to set up, some users find the manual's parameter descriptions challenging. Take your time to understand each parameter's function, especially when navigating the F-menu.
- Special Functions: If your application requires specific functions like Fuzzy logic, Autotuning, Transmission, Remote control, LED BAR display, Motor valve control, Heat & Cool, or Programmable ramp/soak, ensure these are specified during purchase. The standard product may not include all special features.
Warranty and Support
For detailed technical information, advanced parameter settings, or troubleshooting not covered in this manual, please refer to the official user manual PDF:
For further assistance, please contact the LeiChuangTEC Store customer service.