ECGSOLAX 10.2KW Hybrid Solar Inverter User Manual

Model: MAX-10.2K

1. About This Manual

1.1 Purpose

This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.

1.2 Scope

This manual provides safety and installation guidelines as well as information on tools and wiring.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
  2. CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit, take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wiring before attempting any maintenance or cleaning. turning off the unit will not reduce this risk.
  5. CAUTION - Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
  12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

3. Introduction

This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

3.1 Features

  • Pure sine wave inverter
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible to mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/Over temperature/ short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function

3.2 Basic System Architecture

The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system:

  • Generator or Utility.
  • PV modules

Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.

Diagram showing the basic system architecture of the ECGSOLAX Hybrid Solar Inverter connecting solar panels, generator/utility, external battery packs, and home appliances.
Figure: Basic System Architecture. This diagram illustrates how the inverter integrates solar power, a generator or utility grid, and external battery packs to supply power to home appliances.

3.3 Product Overview

Detailed product overview of the ECGSOLAX Hybrid Solar Inverter, showing the front panel LCD display and touch buttons, and the rear panel with various input/output ports.
Figure: Product Overview. This image highlights the LCD display, status, charging, and fault indicators, touch function buttons, power on/off switch, AC input, main output, second output, PV1 and PV2 input, RS-232/WIFI/Remote LCD communication port, battery input, and anti-dust kit.

RGB Lighting for Different Working Mode

The inverter features RGB lighting that automatically switches to indicate the current working mode:

  • Red: Battery mode
  • Blue: Utility mode
  • Purple: PV mode
Three inverters showing different RGB light colors: Red for Battery mode, Blue for Utility mode, and Purple for PV mode.
Figure: RGB Lighting Modes. The inverter's RGB light changes color to indicate its current operational mode (Battery, Utility, or PV).

PV1 & PV2 Input Explanation

The MAX-10.2KW inverter has dual PV1 & PV2 input lines, structured in a parallel design internally.

  • PV1: The maximum PV panel input must not exceed 5100W. Max. PV input voltage is 500V, and the max. PV input current is 23A.
  • PV2: The maximum PV panel input must not exceed 5100W. Max. PV input voltage is 500V, and the max. PV input current is 23A.
  • The PV panel specifications for each PV input line, the PV panel connection methods for each PV input line, and the orientations of the PV panels for PV1 and PV2, all need to be consistent.
  • The total sum of PV1 & PV2 should not exceed 10200W.

4. Setup (Installation)

4.1 Unpacking and Inspection

Before installation, please inspect the inverter. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:

  • The inverter x1
  • User manual x 1
  • DC Fuse x 1
  • Ring terminal x1
  • Mc4 terminal head x2

4.2 Preparation

Before connecting all wiring, please take off bottom cover by removing two screws as shown below.

4.3 Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install at a height suitable for the eyes, making it convenient to read data at any time.
  • For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
Diagram showing recommended clearances for inverter installation: 20cm on sides, 50cm top and bottom.
Figure: Recommended Mounting Clearances. Ensure adequate space around the inverter for proper ventilation and heat dissipation.

!! SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the inverter by screwing two screws. It's recommended to use M4 or M5 screws.

4.4 Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.

ModelWire SizeCable (mm)Torque value (max)
MAX-10.2K1 x 2AWG252 Nm

Please follow below steps to implement battery connection:

  1. Remove insulation sleeve 18 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as below chart.
Diagram showing how to connect multiple 12V battery packs in series to the 10.2KW inverter.
Figure: Battery Connection Diagram. Illustrates connecting four 12V battery packs in series to the inverter.
  1. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.

WARNING: Shock Hazard

Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure.

4.5 AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended specification of AC breaker is 63A for 0.2KW inverter.

CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for AC wires:

ModelGaugeCable(mm2)Torque value
MAX-10.2K10AWG61.2 Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (Ground (yellow-green)) first.
Diagram showing AC input and output wiring connections for the inverter, indicating L-LINE (brown or black) and N-Neutral (blue) terminals.
Figure: AC Input/Output Wiring. This diagram shows the correct polarity for AC input and output connections (L-LINE, N-Neutral).

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

  1. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
  2. Make sure the wires are securely connected.

CAUTION: Appliances such as air conditioner are required at least 23 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still cause internal damage to the air conditioner.

4.6 PV Connection

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for PV wires:

ModelWire SizeCable (mm2)Torque value (max)
MAX-10.2K1x10AWG61.2 Nm

PV Module Selection:

When selecting proper PV modules, please be sure to consider below parameters:

  1. Open circuit Voltage (Voc) of PV panels do not exceeds the max. PV array open circuit voltage of the inverter.
  2. Open circuit voltage of PV panels should be higher than the min. battery voltage.
INVERTER MODELMAX-10.2K
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range90Vdc~450Vdc

Take 250Wp PV panel as an example. After considering above two parameters, the recommended panel configurations are listed in the table below.

PV Specification -250WPV panel Input (Min in serial: 6pcs, max. in serial: 13pcs)Quantity of PV panelsTotal Input power
-Vmp:30.1Vdc6pcs in serial6pcs1500W
-Imp:8.3A8pcs in serial8pcs2000W
-Voc:37.7Vdc12pcs in serial12pcs3000W
-Isc:8.4A13pcs in serial13pcs3250W
-Cells:6012pcs in serial and 3 sets in parallel36pcs8200W
10pcs in serial and 4 sets in parallel40pcs10200W

PV Module Wire Connection

Step 1: Check the input voltage of PV array panels. The acceptable input voltage of the inverter is 120VDC~500VDC. Please make sure that the maximum current load of each PV input connector is 10A.

CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the system before wire connection.

Step 2: Disconnect the DC circuit breaker.

Step 3: Assemble provided PV connectors with PV panels / modules by the following below steps.

Components for PV connectors and Tools:
Female connector housingFemale connector housingMale terminal
Female terminalCrimping tool and spanner
Male connector housing

Cable preparation and connector assembly process: Strip one cable 8mm on both end sides and be careful NOT to nick conductors.

Step 4: Check correct polarity of connection cable from PV panels and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.

4.7 Final Assembly

After connecting all wirings, please put bottom cover back by screwing two screws as shown below.

4.8 Communication Connection

1). Wi-Fi cloud communication (option): Please use supplied communication cable to connect to inverter and Wi-Fi module. Download APP and installed from APP store, and Refer to "Wi-Fi Plug Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.

2). GPRS cloud communication (option): Please use supplied communication cable to connect to inverter and GPRS module, and then applied external power to GPRS module. Download APP and installed from APP store, and Refer to "GPRS RTU Quick installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.

5. Operating

5.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the bottom of the case) to turn on the unit.

5.2 Operation and Display Panel

The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.

LED Indicator

LED IndicatorMessages
INV/ACGreenSolid OnOutput is powered by utility in Line mode
FlashingOutput is powered by battery or PV in battery mode
CHGGreenSolid onBattery is fully charged.
FlashingBattery is charging.
FAULTRedSolid OnFault occurs in the inverter.
FlashingWarning condition occurs in the inverter.

Function Keys

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

5.3 LCD Display Icons

The LCD display provides various icons and information:

IconFunction description
Input Source information
Indicates the AC input
Indicates the PV input
8.8.8 KW V A HzIndicate input voltage, input frequency, PV voltage, charger current (if PV charging for 8.2KW models), charger power, battery voltage.
Configuration Program and Fault Information
8.8.8Indicates the setting programs
8.8.8Indicates the warning and fault codes. Warning: Icon is flashing with warning. Fault: Icon is lighting with fault code.
Output Information
8.8.8 KW VA %Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current.
Battery Information
Load Information
OVER LOADIndicates overload
Mode Operation Information
Indicates unit connects to the mains/Utility.
Indicates unit connects to the PV panel.
AC BYPASSIndicates load is supplied by utility power.
Indicates the utility charger circuit is working.
Indicates the DC/AC inverter circuit is working
Mute Operation

5.4 LCD Setting

After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press "Up" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit.

Setting Programs:

ProgramDescriptionSelectable option
00Exit setting modeEscape(default) 00 GOEOne-button restore setting options
00 GOH
01Output source priority: To configure load power source priorityUtility first 01 USbUtility will provide power to the loads as first priority. Solar and battery energy will provide power to the loads only when utility power is not available.
Solar first (default) 01 S06Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, utility will supply power to the loads at the same time. Battery provides power to the loads only when any one condition happens: Solar energy and utility is not available. - Solar energy is not sufficient and utility is not available.
SBU priority 01 S60Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12.
02Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current)10A 02 1020A 02 20
30A 02 3040A 02 40
50A 02 5060A (default) 02 60
70A 02 7080A 02 80
90A 02 90100A 02 100
110A 02 110120A 02 120
130A 02 130140A 02 140
150A 02 150160A 02 160
170A (for 10.2kw) 02 170180A (for 10.2kw) 02 180
03AC input voltage rangeAppliances(default) 03 APLIf selected, acceptable AC input voltage range will be within 90-280VAC.
UPS 03 UPSIf selected, acceptable AC input voltage range will be within 170-280VAC.
05Battery typeAGM(default) 05 AGnFlooded 05 FLd
User-defined 05 USEIf "User-defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26,27 and 29.
User-defined 05 LIbWhen the solar energy exists, set this item to LIB and the lithium battery will be activated for 3 second.
06Auto restart when overload occursRestart disable(default) 06 LEdRestart enable 06 LHE
07Auto restart when over temperature occursRestart disable(default)Restart enable
09Output frequency50Hz (default) 09 50.60Hz 09 60.
10Output voltage220V 10 220230V (default) 10 230
240V 10 240
11Maximum utility charging current2A 11 2A10A 11 10A
20A 11 20A30A (default) 11 30A
40A 11 40A50A 11 50A
60A 11 60A70A 11 70A
Note: If setting value in program 02 is smaller than that in program in 11, the inverter will apply charging current from program 02 for utility charger.80A 11 80A90A 11 90A
100A 11 100A110A 11 110A
120A 11 120A130A 11 130A
140A 11 140A150A (for 10.2kw) 11 150A
160A (for 10.2kw) 11 160A170A (for 10.2kw) 02 170
180A (for 10.2kw) 02 180
12Setting voltage point back to utility source when selecting "SBU priority" or "solar first" in program 01.Available options in 7.2kw / 8.2kw / 10.2kw 42V 12 4243V 12 43
44V 12 4445V 12 45
46V (default) 12 4647V 12 47
48V 12 4849V 12 49
50V 12 5051V 12 51
13Setting voltage point back to battery mode when selecting "SBU priority" or "solar first" in program 01.Available options in 7.2kw / 8.2kw / 10.2kw Battery full charged 13 48049V 13 490
50V 13 50051V 13 510
52V 13 52053V 13 530
54V (default) 13 54055V 13 550
56V 13 56057V 13 570
58V 13 580
16Charger source priority: to configure charger source prioritySolar first 16 C50If this inverter/charger is working in line, standby or fault mode, charger source can be programed as below: Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available.
Solar and Utility(default) 16 SNUSolar energy and utility will charge battery at the same time.
Only solar 16 050Solar energy will be the only charger source no matter the utility is available or not.
If this inverter/charger is working in battery mode or power saving mode, only solar energy can charge battery. Solar energy will charge battery if it's available and sufficient.
18Alarm controlAlarm on(default) 18 b0nAlarm off 18 b0F
19Auto return to default display screenReturn to default display screen(default) 19 ESPIf selected, no matter how users switch display screen, it will automatically return to default display screen (input voltage/output voltage) after no button is pressed for 1 minute.
Stay at latest screen 19 HEPIf selected, the display screen will stay at latest screen user finally switches.
20Backlight controlBacklight On(default) 20 L0nBacklight off 20 L0F
22Beeps while primary source is interruptedAlarm on(default) 22 A0nAlarm off 22 A0F
23Overload bypass: when enabled, the unit will transfer to line mode if overload occurs in battery mode.Bypass disable(default) 23 b9dBypass enable 23 b9E
25Record Fault codeRecord enable(default) 25 FEnRecord disable 25 EdS
26Bulk charging voltage (C.V voltage)7.2KW/8.2KW/10.2KW default setting: 56.4V C 26 56.4If self-defined is selected in program 5, this program can be setup. Setting range is from 48.0V to 61.0V for 7.2KW/8.2KW/10.2KW model. Increment of each click is 0.1V.
27Floating charging voltage7.2KW/8.2KW/10.2KW default setting: 54.0V FLY 27 54.0If self-defined is selected in program 5, this program can be set up. Setting range is from 48.0V to 61.0V for 7.2KW/8.2KW/10.2KW model. Increment of each click is 0.1V.
29Low DC cut-off voltage7.2KW/8.2KW/10.2KW default setting: 40.0V C 29 40.0If self-defined is selected in program 5, this program can be setup. Setting range is from 40.0V to 48.0V for7.2kW/8.2kW/10.2kWmodel. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected.
30Battery equalizationBattery equalization 30 EEnBattery equalization disable(default) 30 EdS
If"Flooded" or "user-defined" is selected in program 05, this program can be set up.
31Battery equalization voltage7.2KW/8.2KW/10.2KW default setting: 58.4V C 31 58.4Setting range is from 48.0V to 61.0V for 7.2kW/8.2kW/10.2KWmodel. Increment of each click is 0.1V.
33Battery equalized time60min(default) 33 60Setting range is from 5min to 900min. Increment of each click is 5min.
34Battery equalized timeout120min (default) 34 120Setting range is from 5min to 900min. Increment of each click is 5min.
35Equalization interval30 days(default) 35 30dSetting range is from 0 to 90 days. Increment of each click is 1 day.
36Equalization activated immediatelyEnable 36 AEnDisable(default) 36 AdS
If equalization function is enabled in program 30, this program can be set up. If "Enable" is selected in this program, it's to activate battery equalization immediately and LCD main page will shows "E9". If "Disable" is selected, it will cancel equalization function until next activated equalization time arrives based on program 35setting. At this time, "E9" will not be shown in LCD main page.
37Grid-tie operationOff-grid(default) 37 OFFInverter operates only in off-grid mode. Solar energy provides power to the loads as first priority and charging second.
Hybrid 37 HYdInverter operates hybrid mode. Solar energy provides power to the loads as first priority and charging second. Excess energy feed to grid.
38Grid-tie current10A 38 10Increment of each click is 2A.
39Led pattern lightLed pattern off 39 L0FLed pattern on(default) 39 L0n
41Dual outputDisable(default) 41 L2FUse 41 L20
42Enter the dual output functional voltage point7.2KW/8.2KW/10.2KW default setting: 44.0V 42 44.0Setting range is from 40.0V to 46.0 V for 48VDC model. Increment of each click is 0.1V.

5.5 Display Setting

The LCD display information will be switched in turns by pressing "Up" or "DOWN" key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, main CPU Version.

5.6 Operation Mode Description

The inverter supports various operation modes, including Standby, Line, and Grid-Tie. The LCD display will show relevant information for each mode.

Operation modeSelectable informationLCD display
Standby modeInput voltage=222V, PV voltage=210V, Battery voltage=25V, Output voltage=0V, Load in Watt=0W, Chg(Flashing),Inv/ac(bright)Shows input voltage, PV voltage, battery voltage, output voltage, load in Watt, and charging/inverter status.
Input voltage=223V, PV voltage=0V, Battery voltage=25V, Output voltage=0V, Load in Watt=0W, Chg(Flashing),Inv/ac(bright)Shows input voltage, PV voltage, battery voltage, output voltage, load in Watt, and charging/inverter status.
Input voltage=0V, PV voltage=210V, Battery voltage=25V, Output voltage=0V, Load in Watt=0W, Chg(Flashing)Shows input voltage, PV voltage, battery voltage, output voltage, load in Watt, and charging/inverter status.
Line modeInput voltage=224V, PV current=8.6A, Battery current=12.5A, Output voltage=222V, Load in VA=1.88KVA, Chg(Flashing),Inv/ac(bright)Shows input voltage, PV current, battery current, output voltage, load in VA, and charging/inverter status.
Input voltage=224V.PV voltage=0V, Battery voltage=25V, Output voltage=222V, Load in Watt=188W, Chg(Flashing),Inv/ac(bright)Shows input voltage, PV voltage, battery voltage, output voltage, load in Watt, and charging/inverter status.
Grid-Tie OperationInput voltage=224V, PV current=8.6A, Battery current=12.5A, Output voltage=222V, Load in VA=1.88KVA, Chg(Flashing),Inv/ac(bright)Shows input voltage, PV current, battery current, output voltage, load in VA, and charging/inverter status. When working in Grid-Tie mode, the icon will flash 3S/times.

5.7 Battery Equalization Description

Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.

* How to Apply Equalization Function

You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in device by either one of following methods:

  1. Setting equalization interval in program 35.
  2. Active equalization immediately in program 36.

* When to Equalize

In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.

* Equalize charging time and timeout

In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.

However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.

6. Maintenance

6.1 Overview

Every inverter is already installed with anti-dust kit from factory. Inverter will automatically detect this kit and activate internal thermal sensor to adjust internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environment.

6.2 Clearance and Maintenance

Step 1: Please loosen the screw in counterclockwise direction on the top of the inverter.

Step 2: Then, dustproof case can be removed and take out air filter foam as shown in below chart.

Step 3: Clean air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

7. Troubleshooting

5.8 Fault Reference Code

Fault CodeFault EventIcon on
01Fan is locked when inverter is off.01 ERROR
02Over temperature02 ERROR
03Battery voltage is too high03 ERROR
04Battery voltage is too low04 ERROR
05Output short circuited or over temperature is detected by internal converter components.05 ERROR
06Output voltage is too high.06 ERROR
07Overload time out07 ERROR
08BUS voltage is too high08 ERROR
09BUS soft start failed09 ERROR
51Over current or surge51 ERROR
52BUS voltage is too low52 ERROR
53Inverter soft start failed53 ERROR
55Over DC voltage in AC output55 ERROR
57Current sensor failed57 ERROR
58Output voltage is too low58 ERROR
59PV voltage is over limitation59 ERROR

5.9 Warning Indicator

WarningCodeWarning EventAudible AlarmIcon flashing
01Fan is locked when inverter on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
15PV energy is low.Beep twice every 3 seconds15
E9Battery equalizationNoneE9
bPBattery is not connectedNonebP

8. Troubleshooting Table

ProblemLCD/LED/BuzzerExplanation / Possible causeWhat to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer will be active for 3 seconds and then complete off.The battery voltage is too low(< 1.91V/Cell)1.Re-charge battery. 2.Replace battery.
No response after power on.No indication1.the battery voltage is far too low(<1.4V/Cell) 2. Internel fuse tripped1.Contact repair center for replacing the fuse. 2.re-charge battery. 3.replace battery.
Mains exist but the unit works in battery mode.Input voltage is displayed as 0 on the LCD and green LED is flashing.Input protector is trippedCheck if AC breaker is tripped and AC wiring is connected well.
Green LED is flashingInsufficient quality of AC power.(shore or generator)1.Check if AC wires are too thin and/or too long 2.Check if generator(if applied) is working well or if input voltage range setting is correct(UPS Appliance)
Green LED is flashingSet "solar first" as the priority of output source.Change output source priority to Utility first.
When the inverter is turned on, internal relay is switched on and off repeatedly.LCD display and LEDs are flashing.Battery is disconnected.Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on.Fault code 07Overload error. The inverter is overload 110% and time is up.Reduce the connected load by switching off some equipment.
Fault code 05Output short circuited.Check if wiring is connected well and remove abnormal load.
Temperature of internal converter component is over 120°CCheck whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 02Internal temperature of inverter component is over 100°CReturn to repair center.
Fault code 03Battery is over-charged.Check if specification and quantity of batteries meet the requirements.
The battery voltage is too high.
Fault code 01Fan fault.Replace the fan.
Fault code 06/58Output abnormal(inverter voltage below than 190Vac or is higher than 260Vac)1.Reduce the connected load. 2.Return to repair center.

8. Specifications

Table 1 Line Mode Specifications

INVERTER MODELMAX-10.2K
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac+7V(UPS); 90Vac+7V(Appliances)
Low Loss Return Voltage180Vac+7V(UPS); 100Vac+7V(Appliances)
High Loss Voltage280Vac+7V
High Loss Return Voltage270Vac+7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return frequency42 ± 1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)
Output power derating: When AC input voltage drops to 170V, the output power will be derated.

Table 2 Inverter Mode Specifications

INVERTER MODELMAX-10.2K
Rated Output Power10.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac+5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@>150% load;5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage48Vdc
Cold Start Voltage46.0Vdc
Low DC Warning Voltage @ load < 50%44.0Vdc
@ load > 50%42.0Vdc
Low DC Warning Return Voltage @ load < 50%45.0Vdc
@ load > 50%44.0Vdc
Low DC Cut-off Voltage @ load < 50%41.0Vdc
@ load > 50%40.0Vdc
High DC Recovery Voltage62Vdc
High DC Cut-off Voltage63Vdc
No Load Power Consumption70W

NOTE:

For this inverter, if the startup voltage doesn't reach 120V, it can initiate but won't operate properly. If the voltage remains below 120V from the start, the inverter will continue to be unable to function correctly. However, if the voltage reaches 120V after a certain period following startup, the inverter can operate normally. In such a scenario, if weather changes lead to reduced sunlight and the voltage drops below 120V again, the inverter can still operate normally as long as the voltage is above 90V but below 120V.

Table 3 Two Load Output Power

INVERTER MODELMAX-10.2K
Full Load10200W
Maximum Main Load10200W
Maximum Second Load(battery model)3400W
Main Load Cut Off Voltage44VDC
Main Load Return Voltage48VDC

NOTE:

The second output is an output that gives priority to ensuring the load still can run when the battery is out of power. When the second output is not connected, the main output can offer a full amount 10200w. If you want to use the second output and connect a load to it, the maximum rated power of the second output can not be more than3400W. it will occupy the main output load power if you use the second output and connect load to it. If the second output is connected to a 200W load, then the main output maximum will be only 10000w, which is 10200w-200w.

The biggest advantage of this is that when the battery and inverter are running out of power, it gives priority to disconnecting the main output load, to ensure the second output load can still work.

When the battery voltage is lower than the battery disconnection voltage, the second output will also stop output, and the entire reverse control integrated machine will stop Working.

Table 4 Charge Mode Specifications

Utility Charging Mode
INVERTER MODELMAX-10.2K
Charging Algorithm3-Step
AC Charging Current (Max)160Amp
Bulk Charging Voltage Flooded Battery58.4
AGM / Gel Battery56.4
Floating Charging Voltage54Vdc
Charging Curve

MPPT Solar Charging Mode

INVERTER MODELMAX-10.2K
Max. PV Array Power10200W
Nominal PV Voltage360Vdc
PV Array MPPT Voltage Range90Vdc~500Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)180Amp

Table 5 Grid-Tie Operation

INVERTER MODELMAX-10.2K
Nominal Output Voltage220/230/240VAC
Feed-in Grid Voltage Range195~253VAC
Feed-in Grid Frequency Range49~51 ± 1Hz/59~61±1Hz
Nominal Output Current44.3A
Power Factor Range>0.99
Maximum Conversion Efficiency(DC/AC)98%

Table 6 General Specifications

INVERTER MODELMAX-10.2K
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension(D*W*H),mm537*390*130
Net Weight, kg14.5

9. Appendix: Approximate Back-up Time Table

ModelLoad(w)Backup Time @48Vdc 100Ah(min)Backup Time @48Vdc 200Ah(min)
5006131288
1000268613
1500158402
2000111271
max-10.2K250090215
320076182
350065141
400050112
450044100
50004090
62003680
72003270
82002860
92002450
102002040

Note:

  1. Backup time depends on the quality of the battery, age of battery and type of battery.
  2. Specifications of batteries may vary depending on different manufacturers.
  3. The final interpretation right of this product belongs to the company.

9. User Tips

  • For optimal performance, especially when used as a compensator, ensure that batteries are connected. The inverter may not function properly without them.
  • If you encounter issues with the monitoring software, check online resources or contact support for assistance, as some users have reported difficulties.
  • The unit is generally sturdy and of good quality, but proper installation and adherence to wiring guidelines are crucial for reliable operation.
  • When setting up for autonomous (off-grid) use, carefully configure the inverter settings to match your specific needs.

10. Warranty & Support

For technical support, please contact ECGSOLAX New Energy Co., Ltd.

A detailed user manual in PDF format is available for download: User Manual (PDF)

Product Video

Video: ECGSOLAX 10.2KW Hybrid Solar Inverter Product Showcase. This video provides a visual overview of the inverter's design and features.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.