SUMRY MPS-VIII ECO Series 3.6KW/6.2KW

Contents

Sumry MPS-VIII ECO Series Hybrid Solar Inverter User Manual

Model: MPS-VIII ECO Series 3.6KW/6.2KW

Brand: SUMRY

1. Introduction

1.1 Purpose and Scope

This manual provides detailed instructions for the assembly, installation, operation, and troubleshooting of the Sumry MPS-VIII ECO Series Hybrid Solar Inverter. It is essential to read this manual thoroughly before proceeding with any installation or operation to ensure safe and efficient use. Keep this manual for future reference.

1.2 Product Features

  • Pure sine wave inverter for clean and stable power output.
  • Configurable input voltage range for various appliances (home appliances, personal computers) via LCD settings.
  • Adjustable battery charging current to suit different applications.
  • Configurable AC/Solar Charger priority for optimized energy management.
  • Compatible with both mains voltage and generator power.
  • Automatic restart function upon AC recovery.
  • Comprehensive protection against overload, over-temperature, and short circuits.
  • Smart battery charger design for enhanced battery performance and longevity.
  • Cold start function for reliable operation in various conditions.

1.3 Basic System Architecture

The hybrid solar inverter integrates inverter, solar charger, and battery charger functions to provide uninterrupted power. A complete system typically includes the inverter/charger, a generator or utility connection, PV modules, and external battery packs. Consult with your system integrator for specific configurations based on your energy requirements. This inverter is capable of powering a wide range of home and office appliances, including motor-type loads like refrigerators and air conditioners.

Basic System Architecture Diagram
Figure 1: Basic System Architecture. This diagram illustrates how solar panels, a generator/utility grid, and a lithium battery connect to the Sumry On/Off Grid Solar Inverter to power AC loads and on-grid home loads, with monitoring via an APP or computer.
Inverter with Multi-functional Safety Protection
Figure 2: Multi-functional Safety Protection. The image highlights various protection features including Overload Protection, Short Circuit Protection, Battery Protection, Overheating Protection, Overcurrent Protection, and High Low Voltage Protection.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION: Only qualified personnel can install this device with a battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable sizes. It is very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool, causing sparks or short circuits in batteries or other electrical parts, which could lead to an explosion.
  9. Please strictly follow the installation procedure when disconnecting AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.

3. Setup

3.1 Unpacking and Inspection

Before installation, carefully inspect the unit for any damage. The package should contain:

3.2 Mounting the Unit

Consider the following points when selecting an installation location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level to easily read the LCD display.
  • For proper air circulation and heat dissipation, allow a clearance of approximately 20 cm to the sides and 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C for optimal operation.
  • The recommended installation position is vertically adhered to the wall.
  • Ensure sufficient space for heat dissipation and wire removal.

WARNING: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit using two M6 screws.

Inverter Mounting Dimensions and Clearances
Figure 3: Recommended mounting clearances for the inverter, showing 20cm side clearance and 50cm top/bottom clearance.

3.3 Battery Connection

CAUTION: For safety and regulatory compliance, it is recommended to install a separate DC over-current protector or disconnect device between the battery and inverter. Refer to the table below for recommended fuse or breaker sizes.

WARNING! All wiring must be performed by qualified personnel. It is crucial to use appropriate cables for battery connection to reduce the risk of injury.

Follow these steps for battery connection:

  1. Remove 18 mm of insulation sleeve from positive and negative conductors.
  2. Apply bootlace ferrules to the ends of positive and negative wires using a proper crimping tool.
  3. Connect all battery packs as shown in the diagram below.
  4. Insert the battery wires firmly into the inverter's battery connectors. Ensure bolts are tightened to a torque of 2 Nm in a clockwise direction. Verify correct polarity at both the battery and inverter/charger terminals.

Recommended tool: #2 Pozi Screwdriver.

Battery Connection Diagram
Figure 4: Battery connection diagram for 3.6KW and 6.2KW inverters, showing series connection of 12V batteries to achieve 24V or 48V systems.
Recommended Battery Cable Size
Model Wire Size Cable (mm²) Torque Value (max)
3.6KW/6.2KW 1 x 2AWG 25 2 Nm

3.4 AC Input/Output Connection

CAUTION!! Before connecting to the AC input power source, install a separate AC breaker between the inverter and the AC input source. This ensures the inverter can be securely disconnected during maintenance and is fully protected from overcurrent. Recommended AC breaker sizes: 32A for 3.6KW and 50A for 6.2KW.

CAUTION!! There are two terminal blocks marked "IN" and "OUT". Do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cables for AC input connection to reduce risk of injury.

Follow these steps for AC input/output connection:

  1. Before making AC input/output connections, ensure the DC protector or disconnector is open.
  2. Remove 10 mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3 mm.
  3. Insert AC input wires according to the polarities indicated on the terminal block and tighten the terminal screws. (L: LINE (brown or black), N: Neutral (blue))
  4. Insert AC output wires according to the polarities indicated on the terminal block and tighten the terminal screws. (L: LINE (brown or black), N: Neutral (blue))
  5. Ensure all wires are securely connected.
Suggested Cable Requirement for AC Wires
Model Gauge Cable (mm²) Torque Value
3.6KW 12 AWG 4 1.2 Nm
6.2KW 10 AWG 6 1.2 Nm

CAUTION: Appliances like air conditioners require 2-3 minutes to restart due to refrigerant gas balance. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your air conditioner has a time-delay function. Otherwise, the inverter/charger may trigger an overload fault and cut off output, but internal damage to the appliance may still occur.

3.5 PV Connection

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING! Use appropriate cables for PV module connection to ensure system safety and efficient operation. Refer to the table below for recommended cable sizes.

Follow these steps for PV module connection:

  1. Remove 10 mm of insulation sleeve from positive and negative conductors.
  2. Apply bootlace ferrules to the ends of positive and negative wires using a proper crimping tool.
  3. Check the correct polarity of wire connection from PV modules and PV input connectors. Connect the positive pole (+) of the connection wire to the positive pole (+) of the PV input connector, and the negative pole (-) to the negative pole (-).

Recommended tool: 4mm blade screwdriver.

Recommended PV Module Cable Size
Model Wire Size Cable (mm²) Torque Value (max)
3.6KW/6.2KW 1 x 12AWG 4 1.2 Nm

PV Module Selection Guidelines:

When selecting PV modules, consider the following parameters:

  • The Open Circuit Voltage (Voc) of PV modules should not exceed the maximum PV array open circuit voltage of the inverter.
  • The Open Circuit Voltage (Voc) of PV modules should be higher than the minimum battery voltage.
Inverter PV Array Specifications
Inverter Model 3.6KW 6.2KW
Max. PV Array Open Circuit Voltage 500Vdc
PV Array MPPT Voltage Range 60Vdc~450Vdc

3.6 Communication Connection

After connecting all wirings, replace the bottom cover by screwing in the two screws.

Wi-Fi Cloud Communication (Optional):

Use the supplied communication cable to connect the inverter to the Wi-Fi module. Download the APP from the APP store and refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status can then be monitored via the mobile phone APP or a computer webpage.

GPRS Cloud Communication (Optional):

Use the supplied communication cable to connect the inverter to the GPRS module, and then apply external power to the GPRS module. Download the APP from the APP store and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status can then be monitored via the mobile phone APP or a computer webpage.

4. Operation

4.1 Power ON/OFF

Once the unit is properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

4.2 Operation and Display Panel

The operation and display panel is located on the front of the inverter. It includes three indicators, four function keys, and an LCD display, providing operating status and input/output power information.

Sumry MPS-VIII ECO Series Inverter Front Panel
Figure 5: Front panel of the Sumry MPS-VIII ECO Series Inverter, showing the LCD display, indicators, and function buttons.

LCD Display Icons:

The LCD display provides various icons to indicate the inverter's status and operational information. These include:

  • Input Source Information: Icons indicating AC input, PV input, input voltage, frequency, PV voltage, charger current, charger power, and battery voltage.
  • Configuration Program and Fault Information: Icons for setting programs, warning, and fault codes.
  • Output Information: Icons for output voltage, frequency, load percentage, load in VA, load in Watt, and discharging current.
  • Battery Information: Icons related to battery status.
  • Load Information: Icon indicating overload.
  • Mode Operation Information: Icons showing connection to mains, PV panel, load supplied by utility power, utility charger circuit working, and DC/AC inverter circuit working.
  • Mute Operation: Icon indicating unit alarm is disabled.

RGB Light (Option):

The inverter features an RGB light indicator for different modes:

  • Battery Mode: Red Light
  • Utility Mode: Blue Light
  • PV Mode: Purple Light

4.3 LCD Setting

To enter the setting mode, press and hold the ENTER button for 3 seconds. Use the "UP" or "DOWN" buttons to navigate through setting programs, and press "ENTER" to confirm a selection or "ESC" to exit.

Key configurable settings include:

  • Output Source Priority (Program 01): Configure whether the utility, solar, or SBU (Solar-Battery-Utility) provides power first.
  • Maximum Charging Current (Program 02): Set the total charging current for solar and utility chargers.
  • AC Input Voltage Range (Program 03): Select between appliance mode (90-150VAC) or UPS mode (90-150VAC).
  • Battery Type (Program 05): Select battery type (AGM, Flooded, User-Defined, Lithium Battery).
  • Auto Restart (Programs 06, 07): Enable or disable auto-restart for overload or over-temperature conditions.
  • Output Frequency (Program 09): Set output frequency to 50Hz or 60Hz.
  • Output Voltage (Program 10): Set output voltage (100V, 105V, 110V, 115V, 120V).
  • Maximum Utility Charging Current (Program 11): Set the maximum charging current from the utility.
  • Setting Voltage Point Back (Programs 12, 13): Configure voltage points for switching back to utility source or battery mode.
  • Alarm Control (Program 18): Enable or disable alarms.
  • Auto Return to Default Display Screen (Program 19): Configure whether the display automatically returns to default after inactivity.
  • Backlight Control (Program 20): Turn backlight on or off.
  • Beeps while Primary Source is Interrupted (Program 22): Enable or disable beeps when the primary power source is interrupted.
  • Overload Bypass (Program 23): Enable or disable transferring to line mode during battery mode overload.
  • Record Fault Code (Program 25): Enable or disable fault code recording.
  • Bulk Charging Voltage (Program 26): Set the bulk charging voltage (C.V voltage).
  • Floating Charging Voltage (Program 27): Set the floating charging voltage.
  • Low DC Cut-off Voltage (Program 29): Set the low DC cut-off voltage.
  • Battery Equalization (Programs 30, 31, 33, 34, 35, 36): Configure battery equalization settings, including voltage, time, timeout, and interval.
  • GRID-tie Current (Program 38): Set the GRID-tie current.
  • Led Pattern Light (Program 39): Turn the LED pattern light on or off.
  • Dual Output (Program 41): Enable or disable dual output.
  • Enter the Dual Output Functional Voltage Point (Program 42): Set the functional voltage point for dual output.

4.4 Display Setting

The LCD display information can be cycled by pressing the "UP" or "DOWN" keys. The displayed information includes input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, DC discharging current, and main CPU Version.

4.5 Operating Mode Description

The inverter operates in various modes, each with specific display information:

  • Standby Mode: Shows input voltage, PV voltage, battery voltage, output voltage, and load when the unit is idle.
  • Line Mode: Displays input voltage, PV current, battery current, output voltage, and load when operating from the AC input.
  • Grid-Tie Operation: Shows input voltage, PV current, battery current, output voltage, and load when feeding power to the grid. The solar icon will flash 3 times in this mode.
  • Battery Mode: Displays input voltage, PV voltage, battery voltage, output voltage, and load when operating solely from battery power.
  • LIC (Lithium Battery Communication Connection): Provides detailed information for lithium batteries, including total battery voltage, residual capacity, charging/discharge current, nominal voltage, total capacity, and remaining capacity.

5. Maintenance

5.1 Clearance and Maintenance for Anti-Dust Kit

Every inverter comes with an anti-dust kit pre-installed from the factory. This kit helps prevent dust from entering the inverter, increasing product reliability in harsh environments. The inverter automatically detects this kit and adjusts its internal thermal sensor to maintain optimal temperature.

Follow these steps for maintenance:

  1. Loosen the screw on the top of the inverter in a counterclockwise direction.
  2. Remove the dustproof case and take out the air filter foam.
  3. Clean the air filter foam and the dustproof case. After cleaning, re-assemble the dust-kit back into the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

6. Troubleshooting

This section provides a guide to common issues and their solutions. If problems persist, contact a qualified service person.

Troubleshooting Table
Problem LCD/LED/Buzzer Explanation / Possible Cause What to do
Unit shuts down automatically during startup process. LCD/LEDs and buzzer active for 3 seconds, then off. Battery voltage is too low (<1.91V/Cell) 1. Re-charge battery.
2. Replace battery.
No response after power on. No indication. 1. Battery voltage is too low (<1.4V/Cell)
2. Internal fuse tripped.
1. Contact repair center for fuse replacement.
2. Re-charge battery.
3. Replace battery.
Mains exist but unit works in battery mode. Input voltage displayed as 0 on LCD, green LED flashing. Input protector is tripped. Check if AC breaker is tripped and AC wiring is connected well.
Green LED is flashing. Insufficient quality of AC power (Shore or Generator). 1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct (UPS Appliance).
When unit is turned on, internal relay switches on and off repeatedly. Green LED is flashing. "Solar First" set as priority of output source. Change output source priority to Utility first.
LCD display and LEDs are flashing. Battery is disconnected. Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on. Fault code 07 Overload error. Inverter is overloaded 110% and time is up. Reduce the connected load by switching off some equipment.
Fault code 05 Output short circuited. Check if wiring is connected well and remove abnormal load.
Fault code 02 Temperature of internal converter component over 120°C. Internal temperature of inverter component over 100°C. Check whether air flow is blocked or ambient temperature is too high.
Fault code 03 Battery is over-charged. Return to repair center.
The battery voltage is too high. Check if battery specifications and quantity meet requirements.
Fault code 01 Fan fault. Replace the fan.
Fault code 06/58 Output abnormal (Inverter voltage below 190Vac or higher than 260Vac). 1. Reduce the connected load.
2. Return to repair center.
Fault code 08/09/53/57 Internal components failed. Return to repair center.
Fault code 51 Over current or surge. Restart the unit. If the error happens again, return to repair center.
Fault code 52 Bus voltage is too low. Restart the unit. If the error happens again, return to repair center.
Fault code 55 Output voltage is unbalanced. Restart the unit. If the error happens again, return to repair center.

7. Specifications

7.1 Line Mode Specifications

Feature 3.6KW 6.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage100Vac
Low Loss Voltage90Vac±5V (UPS); 90Vac±5V (Appliances)
Low Loss Return Voltage95Vac±5V (UPS); 95Vac±5V (Appliances)
High Loss Voltage145Vac±5V
High Loss Return Voltage140Vac±5V
Max AC Input Voltage150Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

7.2 Inverter Mode Specifications

Feature 3.6KW 6.2KW
Rated Output Power3.6KW6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation100/105/110/115/120Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150%; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage (@ load < 50%)22.0Vdc44.0Vdc
Low DC Warning Voltage (@ load ≥ 50%)21.0Vdc42.0Vdc
Low DC Warning Return Voltage (@ load < 50%)22.5Vdc45.0Vdc
Low DC Warning Return Voltage (@ load ≥ 50%)22.0Vdc44.0Vdc
Low DC Cut-off Voltage (@ load < 50%)20.5Vdc41.0Vdc
Low DC Cut-off Voltage (@ load ≥ 50%)20.0Vdc40.0Vdc
High DC Recovery Voltage32Vdc62Vdc
High DC Cut-off Voltage33Vdc63Vdc
No Load Power Consumption45W50W

7.3 Charge Mode Specifications

Feature 3.6KW 6.2KW
Utility Charging Mode
Charging Algorithm3-Step
AC Charging Current (Max)80Amp (@VI/P=100 Vac)
Bulk Charging Flooded Battery Voltage29.258.4
Bulk Charging AGM / Gel Battery Voltage28.256.4
Floating Charging Voltage27Vdc54Vdc
MPPT Solar Charging Mode
Max. PV Array Power4200W6500W
Nominal PV Voltage240Vdc360Vdc
PV Array MPPT Voltage Range60Vdc~500Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)120Amp

7.4 Grid-Tie Operation

Feature 3.6KW 6.2KW
Nominal Output Voltage100/105/110/115/120VAC
Feed-in Grid Voltage Range90~150VAC
Feed-in Grid Frequency Range49~51±1Hz/59~61±1Hz
Nominal Output Current30A51.7A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)97%

7.5 General Specifications

Feature 3.6KW 6.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage Temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm110X334X423
Net Weight, kg910

7.6 Approximate Back-up Time Table

Backup time depends on the quality, age, and type of battery. Battery specifications may vary depending on different manufacturers.

Model Load (W) Backup Time @ 24Vdc 100Ah (min) Backup Time @ 24Vdc 200Ah (min)
3.6KW3004491100
600222525
900124303
120095227
150068164
180056126
210048108
24003594
27003174
32002867
36002560
Model Load (W) Backup Time @ 48Vdc 100Ah (min) Backup Time @ 48Vdc 200Ah (min)
6.2KW5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090

8. Video Demonstration

Watch this video for an unboxing and demonstration of the Sumry Hybrid Solar Inverter, including its setup and use for charging devices and powering appliances.

Video: Unboxing and demonstration of the Sumry Hybrid Solar Inverter, showing how to connect it and power various devices like a smartphone and an electric kettle.

Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.