1. Introduction
Welcome to your new NJTY T26C Leakage Current Clamp Meter. This manual provides essential information for the safe and effective operation, maintenance, and troubleshooting of your device. Please read it thoroughly before use.
The NJTY T26C is a digital leakage current meter featuring a 1999-digit display and stable performance. It is designed for electricians and can measure microcurrents (mA, µA), AC current, and AC/DC voltage up to 600V.
Figure 1: NJTY T26C Clamp Meter - Microcurrent Leakage Current Clamp Meter suitable for AC Current, Small Current Measurement with 0.01mA Resolution. Manual Range Switching: 20mA-200mA-2A-60A. AC/DC Voltage 600V Test.
2. Safety Information
This meter is designed according to IEC1010-standard. Please read the following notes carefully before operation to ensure your safety.
- Ensure the input voltage is less than 600V.
- For DCV measurements exceeding 36V and ACV exceeding 25V, always check the test leads for proper connection and insulation to prevent electrical shock.
- Always disconnect the test leads from the test point when changing measurement ranges.
- Select the correct function and range to avoid errors. Although this meter has protective circuitry, proper selection is crucial for safety.
- Ensure the input current does not exceed the maximum current specified for the input terminals.
Safety Symbols:
- ⚠ Caution
- ⚡ Danger of high voltage shock
- ◻ Double insulation protection
3. Product Overview
The NJTY T26C is a compact and portable clamp meter designed for ease of use in various electrical testing scenarios.
Figure 2: Mini and Compact Design for Easy Portability.
Key Features:
- Max Display: 1999 counts
- Data Hold: "H" displayed on LCD to hold readings.
- Low Battery Display: Indicates when battery replacement is needed.
- Max Jaw Distance: 30mm.
- Auto Power-off: Device powers off after 15 minutes of no operation to conserve battery.
- Power: 2 x AAA batteries (not included).
Figure 3: Clamp Jaw with a Maximum Diameter of 30mm.
4. Specifications
| Parameter | Value |
|---|---|
| Max Display | 1999 counts |
| Max Jaw Distance | 30mm |
| Body Size | 183 x 63 x 29 mm |
| Net Weight | 136g (battery excluded) |
| Working Environment | 0°C ~ 40°C, ≤70% RH |
| Storage Environment | -20°C ~ 60°C, ≤85% RH |
| Power | 2 x AAA batteries |
| Auto Power-off | After 15 minutes of inactivity |
Measurement Ranges and Accuracy (1-year guarantee, Environment: 23°C ± 5°C, Relative Humidity < 75%):
| Range | Resolution | Accuracy |
|---|---|---|
| 20mA | 0.01mA | ±(2.5% + 5 digits) |
| 200mA | 0.1mA | |
| 2A | 1mA | |
| 60A | 100mA | ±(3% + 8 digits) |
| DC600V | ||
| AC600V |
Note: The accuracy is lower when testing voltage below 100V.
5. Setup
Battery Installation:
The NJTY T26C requires two AAA batteries (not included) for operation.
- Ensure the meter is turned OFF.
- Locate the battery compartment on the back of the meter.
- Use a screwdriver to open the battery compartment cover.
- Insert two AAA batteries, observing the correct polarity (+ and -).
- Replace the battery compartment cover and secure it with the screw.
Warning: Do not attempt to operate the meter with incorrect battery polarity or without the battery cover securely fastened.
6. Operation Method
6.1 Power On/Off and Function Selection
- To turn on the meter, rotate the central dial from the "OFF" position to the desired measurement function (e.g., 20mA, 200mA, 2A, 60A, 600V).
- To turn off the meter, rotate the central dial back to the "OFF" position.
- The meter features an Auto Power-off function, which will turn off the device after 15 minutes of inactivity.
- Use the "SELECT" button to switch between ACV and DCV modes when the dial is set to 600V.
6.2 Data Hold Function
- Press the "HOLD" button to freeze the current reading on the LCD. The "H" symbol will appear on the display.
- Press the "HOLD" button again to release the data hold and resume live measurements.
6.3 Alternative Leakage Current Measurement
Many factories and companies use three-phase and five-wire systems with three-phase lines, one working zero line, and a ground lead. When checking leakage current, the ground line should be tested alone.
- Check the leakage current of the ground lead:
- First, set the meter to a high range of ACA (AC Current).
- Clamp the ground lead to take a reading.
- If the reading is relatively small, switch to a lower range for a more precise measurement. The reading obtained is the leakage current of the ground lead.
- Check the leakage current of the unbalanced working power line:
- Clamp the power line (single-phase alternative current, two-phase, three-phase three-wire system, or three-phase four-wire system).
- Important: Do NOT clamp the ground line together with the power line if one is present.
Wiring System Diagrams:
(1) single-phase alternative current
L
|
|
N
Figure 4: Single-Phase Alternative Current
(2) three phase three-wire system
L1
|
L2
|
L3
Figure 5: Three-Phase Three-Wire System
(3) three phase four-wire system
L1
|
L2
|
L3
|
N
Figure 6: Three-Phase Four-Wire System
(4) three phase five-wire system
L1
|
L2
|
L3
|
N
|
PE
Figure 7: Three-Phase Five-Wire System
Note: L is live wire, N is zero line, PE is ground line.
6.4 AC Current (ACA) Measurement
- Rotate the dial to an ACA range (20mA, 200mA, 2A, or 60A).
- First, set the meter to a high range of ACA.
- Clamp the live wire to take a reading.
- If the reading is relatively small, switch to a lower range for a more precise measurement.
- Note: Ensure the two parts of the clamp jaws are completely closed while testing, otherwise the reading may not be accurate.
Figure 8: AC Current Measurement Example.
6.5 ACV/DCV Measurement
- Rotate the dial to the 600V range.
- Insert the black test lead into the "COM" terminal and the red test lead into the "V/Ω" terminal.
- For DCV (DC Voltage) measurement, the meter will display the reading directly.
- For ACV (AC Voltage) measurement, press the "SELECT" button to switch to ACV mode, then read the display.
Figure 9: AC Voltage Test Example.
Figure 10: DC Voltage Test Example.
7. Maintenance
⚠ Warning: Before opening the battery door or performing any maintenance, turn off the power and remove all test leads to avoid electrical shock.
7.1 Battery Replacement
When the battery symbol ("+") is displayed on the LCD, the batteries need to be replaced.
- Turn off the meter and disconnect all test leads.
- Open the battery compartment cover on the back of the meter.
- Remove the old AAA batteries.
- Insert two new AAA batteries, ensuring correct polarity.
- Close the battery compartment cover securely.
7.2 General Care
- Avoid subjecting the meter to shock, impact, high temperatures, or high-intensity magnetic fields.
- Clean the meter with a soft, dry cloth. Do not use abrasive cleaners or solvents.
- Store the meter in a cool, dry place when not in use.
8. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| Meter does not power on | Dead or incorrectly installed batteries | Replace batteries, ensuring correct polarity. |
| "H" symbol displayed | Data Hold function is active | Press the "HOLD" button to release. |
| Inaccurate current readings | Clamp jaws not fully closed; incorrect range selected | Ensure jaws are fully closed around the wire; select appropriate range. |
| Inaccurate voltage readings (below 100V) | Inherent meter characteristic | Note that accuracy is lower for voltages below 100V as per specifications. |
| Meter powers off unexpectedly | Auto Power-off activated due to inactivity | This is normal behavior. Turn the dial to OFF and then back to the desired function to restart. |
9. User Tips
- Accuracy: Some users have reported excellent precision, comparable to professional equipment. For critical measurements, always ensure proper technique and environmental conditions.
- Compact Design: The meter's mini and compact size makes it easy to carry and use in tight spaces.
- Display Backlight: This model does not feature a display backlight. Ensure adequate lighting when taking readings.
10. Warranty and Support
The NJTY T26C Leakage Current Clamp Meter is designed for reliability and performance. For specific warranty details, please refer to the product packaging or contact your point of purchase. Keep your purchase receipt as proof of purchase.
For technical support or inquiries, please contact the manufacturer or your retailer.