PEAKMETER PM8200B

Contents

PM8200B Multifunction Voltage Tester

User Manual

1. Introduction

The PM8200B is a waterproof and dustproof intelligent AC/DC voltage measurement instrument designed for comprehensive electrical testing. It features RCD testing, polarity detection, resistance, continuity, and phase sequence testing. This manual provides essential information for safe and effective use of the instrument.

PM8200B Multifunction Voltage Tester with key features

Figure 1: PM8200B Multifunction Voltage Tester highlighting key features: AC 1200V Test, DC 1500V Test, 1MΩ Resistance Test, RCD Test, Phase Sequence Test.

Key Characteristics:

  • Probe protective case for physical security.
  • LCD voltage and frequency display.
  • AC and DC voltage measurement.
  • Resistance test range up to 1000kΩ.
  • Continuity test.
  • Indication of three-phase AC voltage phase sequence.
  • Buzzer mode and mute mode.
  • Voltage testing without battery.
  • Lighting function.
  • Low battery indication and over-range voltage indication.
  • RCD testing.
  • Automatic shutdown and wake-up function.

2. Safety Information

For your personal safety, please read this user manual carefully before use. The voltage detector is provided for trained personnel. Unauthorized personnel shall not disassemble the voltage detector.

WARNING

Take special attention to this instrument, as improper use may cause electric shock or damage to the instrument. During use, it is necessary to follow the usual safety regulations and fully comply with the security measures specified in the user manual. To fully utilize the functions of the instrument and ensure safe operation, please carefully read and follow the instructions in this manual.

The instrument complies with the security requirements of EN 61010-1, EN 61243-3:2014, EN 60529, and EN 61326-1 for electronic testing instruments, and belongs to Class 2 pollution. The overvoltage standards are CAT IV 600V, CAT III 1000V. Please follow the security guidelines to ensure safe use of the instrument.

2.1 Security Instructions

  • When using this instrument, the operator must comply with all standard security regulations for preventing electric shock and preventing incorrect use of instruments.
  • This tester is provided for professional trained personnel to use; non-professional trained personnel cannot use it to avoid personal injury.
  • To ensure your physical security, check and ensure that the instrument is in good condition before using it.

2.2 Security Symbols

Symbols used on the instrument body and in this user manual:

Symbol Description
!Warning. Refer to the user manual before using. Incorrect use may cause damage or injury.
~AC (Alternating Current)
---DC (Direct Current)
Working in power-on status is allowed
Grounding
□Double insulation protection
CECompliant with European Union instruction
High voltage warning
CAT IV600V CAT IV overvoltage protection. MEASUREMENT CATEGORY IV is applicable to test and measuring circuits connected at the source of the building's low-voltage MAINS installation.
Do not discard this electrical/electronic product into household garbage.

3. Product Overview and Components

The PM8200B is designed for ease of use and durability, featuring an IP65 waterproof and dustproof rating.

Dimensions of the PM8200B tester

Figure 2: Dimensions of the PM8200B tester. Length: 265mm, Width: 40.5mm, Probe tip length: 20mm, Cable length: 95mm.

PM8200B IP65 Waterproof and Dustproof rating

Figure 3: The PM8200B features an IP65 rating, completely preventing dust entry and allowing rinsing with water without damage.

3.1 Names of Components

Diagram of PM8200B components

Figure 4: Diagram showing the main components of the PM8200B tester.

  1. Probe L1-
  2. Probe L2+
  3. Light
  4. LCD indicator
  5. RCD test button
  6. Data hold key
  7. Light switch, ELV indicator
  8. Battery box
  9. Probe tip protection
  10. Probe tip insulation cap
  11. Probe tip metal threaded cap

Attention: The ELV indication is only used to indicate voltages greater than 50V a.c./120V d.c. and is not intended as an indication of measured voltage values. Voltage values should be read from the LCD indicator.

3.2 Descriptions of Keys

  • RCD Key: Activates RCD testing.
  • HOLD Key: Freezes the current display reading.
  • Lighting Key: Toggles the flashlight and controls mute mode.

3.3 LCD Monitor Display Symbols

Symbol Description
High voltage hazard indication
Battery undervoltage indication
XMute mode indication
Negative data
DC ---DC (Direct Current)
ACAC (Alternating Current)
))Continuity
Hz, kHzFrequency Hz, Frequency kHz
Ω, kΩ, MΩResistance value units: Ω, kΩ, MΩ
®Positive phase sequence
LNegative phase sequence
HOLDData holding
VVoltage unit: Volts

4. Setup and Initial Checks

4.1 Battery Replacement

The PM8200B requires 2 AAA batteries (1.5V each). When the instrument displays the battery undervoltage symbol, the battery should be replaced immediately.

PM8200B tester and manual in protective case

Figure 5: The PM8200B tester and user manual stored in its protective case.

  1. End the testing status of the tester and disconnect the two probes from the tested object.
  2. Unscrew the screw that fixes the battery cover with a screwdriver.
  3. Remove the battery cover.
  4. Remove the old batteries.
  5. Install new batteries according to the battery symbol and direction on the panel.
  6. Insert the battery cover and fasten it with screws.

Note: Batteries contain harmful substances. Dispose of replaced batteries according to local recycling rules at fixed recycling points.

4.2 Pre-Test Checks

  • Before testing, please confirm that the test probe and testing instrument are in good condition.
  • When using this device, hands can only touch the handle part.
  • The equipment should be used within the specified range (based on technical specifications) and with a voltage not exceeding 1200V a.c. / 1500V d.c. Ensure the equipment is in good condition.
  • To ensure normal operation, first test a known voltage value object.

5. Operating Instructions

5.1 Voltage Testing (AC/DC)

WARNING

This instrument cannot test voltage for a long time. If long-term testing is necessary, disconnect the test for more than 240 seconds after testing for more than 30 seconds.

  1. Separate the L1 and L2 ends of the tester. Press any key or power on the tester. After self-test, "----" will be displayed. Use within the nominal voltage range.
  2. Before testing, manually check the tester's quality: Touch the metal nib of L1 and L2 together. The on-off resistance should be <5kΩ.
  3. Connect the two probes to a known voltage object (e.g., a 220V socket) to ensure accuracy. The tester cannot test AC or DC voltages below 5V.
  4. DC Voltage Test: If probe L2 is connected to the positive pole and L1 to the negative pole, the LCD displays the voltage. Otherwise, it displays "-". If the "-" symbol is not lit, L2 is positive and L1 is negative.
  5. AC Voltage Test: Connect probes to either end of the object. The LCD displays "AC", voltage value, and frequency.
AC voltage measurement with frequency and phase sequence indication

Figure 6: AC voltage measurement showing frequency, analog bar, current voltage, and phase sequence symbol on the display.

DC voltage test on a battery

Figure 7: DC voltage test, capable of measuring up to 1500V without button operation, shown measuring a battery.

Note on AC Voltage: When testing AC voltage, the screen may display L and R, and the phase sequence indication at this time is an uncertain state. The L symbol or R symbol may be displayed, and even be displayed alternately. Only when testing three-phase power systems can the symbol L/R be displayed correctly and stably.

5.2 Testing Without Battery

A simple voltage test can be performed even if the battery is depleted or absent. Connect the two probes to the tested object. If the voltage is ≥ 50V, the LED at the bottom of the light switch key will light up, indicating dangerous voltage. The LED brightness increases with voltage.

5.3 Resistance and Continuity Testing

  • Before testing, ensure the object is not charged by testing its voltage.
  • Connect the two probes to both ends of the tested object.
  • If resistance is 0~10kΩ, the continuity symbol "))" will not be displayed, and the buzzer will sound continuously.
  • If resistance is between 10kΩ and 1000kΩ, the LCD will display the resistance value, and the buzzer will not sound.
  • Continuous testing response time is <500ms.

5.4 Phase Sequence Testing (Three-phase AC Phase Sequence Indication)

  • Follow security testing rules.
  • Test results may be unstable under strong electric field interference or radiation.
  • The rotation test is indicated by symbols R and L, applicable only to three-phase AC systems.
  • Range: 150V-400V (50Hz 60Hz).
  • Procedure: Hold the main end of the tester (fingers on the handle part). Connect probe L2 to any one phase and probe L1 to any other phase of the three-phase circuit.
  • One of R or L will be displayed. Moving a probe to another phase will display the other symbol. Exchanging probe positions will also change the displayed symbol.
  • The LCD will simultaneously display the three-phase voltage value.

5.5 RCD Testing

RCD testing helps reduce interference voltage. In normal voltage test mode, connect the two probes to the L and PE terminals of a 230V a.c. system. Press the RCD key on both probes. If the circuit generates an AC current greater than 30mA, the RCD system will trip.

WARNING

Do not test RCD for a long time. At 230V, testing time should be less than 10s. Continuous testing is not allowed. After one test, wait 60s before proceeding. It is prohibited to press two RCD keys during non-RCD testing, as this can damage the instrument and harm the operator.

5.6 Mute Mode Selection

The tester can enter mute mode from standby or during use. Press and hold the flashlight key for about 2 seconds until a "beep" sounds. The mute symbol "X" will appear on the LCD. In mute mode, the buzzer is silent, but all other functions operate normally. To return to normal (buzzer) mode, press and hold the flashlight key again for about 2 seconds until a "beep" sounds, and the "X" symbol disappears.

5.7 Lighting Function

For use in dark environments, gently touch the flashlight key on the panel. The light at the top of the tester will turn on. Touch the key again to turn it off.

5.8 Data Holding Function

During testing, lightly touch the HOLD key to freeze the current voltage and frequency readings on the display for easy recording. Tap the HOLD key again to release the data hold and return to normal testing status.

6. Maintenance

6.1 Equipment Cleaning

Before cleaning, disconnect the tester from any circuits. If the instrument gets dirty, wipe it with a damp cloth and a small amount of mild household cleaning agent. Do not use acidic cleaning agents or solvents. Do not use the tester for approximately five hours after cleaning.

6.2 Storage

If the instrument is not used for a long time, remove the battery to prevent damage. Store the tester in its protective case to prevent physical harm to the probes.

7. Troubleshooting

If you encounter issues with your PM8200B tester, consider the following:

  • No functional indication or functions fail: The tester cannot be used.
  • Inconsistent function or abnormal display: This could be due to prolonged storage in unsuitable conditions, mechanical compression during transport, or internal damage.
  • Incorrect readings or display issues: Replace the battery immediately if the battery undervoltage symbol is displayed.
  • Unstable phase sequence test results: This may occur under strong electric field interference or strong radiation.
  • RCD test not working as expected: Ensure you are following the correct procedure and waiting 60 seconds between tests. Avoid pressing both RCD keys simultaneously during non-RCD testing.
  • Continuity tester beeper not working: Check if the device is in mute mode. If not, and the resistance is within the specified range for continuity, the device may require service.

Important: If the operator's safety cannot be guaranteed (e.g., obvious damage to the instrument), the instrument must be sent for repair. Before opening the bottom case or battery cover, the probes should be removed from the tested circuit.

8. Specifications

8.1 Technical Indicators

Function Range Resolution Accuracy Remarks
DC Voltage200V0.1V±(1.0% reading + 3 digits)-
1500V1V
AC Voltage200V0.1V±(1.0% reading + 3 digits)Frequency 45~500Hz
1200V1V
200V0.1V±(1.5% reading + 8 digits)Frequency 500~1000Hz
1200V1V
Resistance1000kΩ1kΩ±(5.0% reading + 5 digits)< 10kΩ buzzing
  • Input impedance: ELV a.c. 300 kΩ (50V/50Hz).
  • Current peak: ≤ 3.5mA 1000V (Power off state); < 350mA 1000V (Power on state).
  • Working time ton/toff: ≤ 230V without limitation; > 230V ton 30 seconds/toff 240 seconds.
  • Temperature coefficient: 0.1× accuracy/°C.

8.2 Function Description

  • Automatic recognition of test type: Displays "---" when AC/DC voltage is less than 5V or in no testing status.
  • Frequency range: 45Hz~1000 Hz, resolution 1Hz, error ±(3%+5d).
  • Buzzer: Supports two modes (buzzer and mute).
  • Voltage polarity indication: Automatic.
  • Range selection: Automatic.
  • RCD test: Voltage 230V (45-1000Hz); Current 30mA~40mA; Testing time <10s, recovery time: 60s.
  • Continuity test: <10kΩ buzzer.
  • Phase sequence test: Three-phase AC voltage range: 150V~400V, frequency 50Hz~60Hz.
  • Power supply: 1.5V x 2 AAA batteries.
  • Battery undervoltage indication: Less than 2.5V.
  • Response time: <1S.
  • Working temperature: -5°C~+40°C.
  • Storage temperature: -20°C~+60°C.
  • Working humidity: ≤ 85% RH.
  • Altitude: <2000m.
  • Overvoltage protection level: CAT IV 600V, CAT III 1000V.
  • Pollution level: Class 2 pollution.
  • Waterproof and dustproof level: IP65.
  • Wake up: Press any key or wake up when testing an AC/DC voltage greater than 12V.
  • Automatic shutdown: Shuts down automatically after about 30 seconds in no testing status.
  • Size: 290*80*34mm.
  • Weight: About 317g (without battery).

9. User Tips

  • The tester features a backlight for improved visibility in low-light conditions.
  • The product often comes with a protective carrying case, which is useful for storage and transport.
  • Always verify the CAT rating (e.g., CAT III or CAT IV) to ensure it matches the safety requirements of your specific electrical work.
  • If the RCD test or continuity beeper does not function, first check if the device is in mute mode. If the issue persists, refer to the troubleshooting section or contact support.
  • Always prioritize safety when working with electricity. Double-check readings and ensure the device is functioning correctly before relying on its measurements for critical tasks.

10. Warranty and Support

This product is manufactured by Guilin Huayi Peakmeter Technology Co., Ltd.

Address: No.15-3, Xingyuan Road, Sitang Town, Lingui District, Guilin City, Guangxi, China

Telephone number: 0773-3682318

Postcode: 541100

For technical support or warranty inquiries, please contact the manufacturer directly using the provided contact information.

A PDF version of the user manual is available for download. Reference: User manual (PDF)


Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.