1. Introduction
The PEAKMETER MS2205 is a hand-held intelligent harmonic power tester designed for comprehensive electrical measurements. It combines digital current testing and power testing functionalities, making it an ideal choice for on-site power equipment and power-supplying circuit examinations.
Equipped with a micro single-chip system and powerful software, the MS2205 can accurately measure, calculate, and display various parameters including voltage, current, active power, power factor, apparent power, passive power, frequency, and harmonic parameters. Its stable performance, user-friendly operation, hand-held clamp structure, small volume, and light weight ensure easy portability and quick measurements for single-phase and three-phase power systems.
Key Features:
- Measures power, voltage, current, peak value, phase, frequency, power factor, phase angle, and reaction factor for single-/three-phase circuits.
- Automatic phase sequence testing for 3-phase measurements.
- True effective value measurement, ensuring accuracy even with distorted current waveforms.
- Low-consumption high-speed single-chip microprocessor for rapid and precise results.
- Measures up to 20 harmonics and their distortion values.
- Large memory capacity to save up to 100 groups of test parameters.
- RS232C communication and recording interface with dedicated WINDOWS graphics software for data transfer and analysis.
- Hand-held, clamp-type design for portability and ease of use.
2. Safety Information
WARNING: Before use, please carefully read this instruction manual, especially the safety contents!
The three-phase clamp-type digital power meter is designed and manufactured in accordance with international standard IEC61010-1 and international safety specification IEC1010-2-032. The meter strictly follows the safety standard of double-insulation AC 600 V CAT III.
Safety Requirements:
- Exercise extreme caution when test voltage exceeds AC 30 V. Ensure your fingers do not extend beyond the hand-shielding part of the test probe.
- Do not measure voltage higher than the allowed input limit.
- Before each use, inspect the meter and test probes. Do not proceed with testing if the test probe is exposed, the tester housing is damaged, or the LCD display is not functioning.
- The meter meets safety standards only when used with the supplied test probes. If a test probe is damaged and requires replacement, use a test probe of the same model and identical electrical specifications.
- Never perform voltage measurements with the test probe inserted into any current outlet.
- Avoid exposing the meter to strong light, high temperatures, or dampness.
Safety Signs:
| Sign | Description |
|---|---|
| ⚠ | Important safety signs; please refer to instruction manual |
| ⚡ | High voltage hazard |
| ☇ | Earthing |
| □ | Double insulation (Category-II safety equipment) |
| ⏰ | Battery low Indicator |
3. Product Overview
3.1. Appearance
3.2. Knob Switch Operations
The function-switching knob is used for powering on the device and selecting different measurement functions.
| Sign | Knob position | Functions |
|---|---|---|
| OFF | Powering-off position | For powering-off |
| KW (1 phase) | Active power position | For measuring active power, etc. |
| Φ (1 phase) | Single-phase/phase-angle Test position | For measuring phase angle, such as cos Φ and sin Φ, etc. |
| KW/Φ (3 phase) | 3-phase apparent power position | For measuring 3-phase apparent power, etc. |
| A~ | AC-current harmonics test position | For measuring AC-current harmonics, etc. |
| V~ | AC-voltage harmonics test position | For measuring AC-voltage harmonics, etc. |
Note:
When the meter automatically powers off, ensure to switch the knob to "OFF" position. Turn on the meter after 5 seconds.
3.3. Button Switch Operations
| SN | Button | Function-selection button |
|---|---|---|
| 1 | MODE | Test-mode switching button |
| 2 | SET | SET button |
| 3 | I | Current test button |
| 4 | WATT | Power test switching button |
| 5 | U | Voltage test button |
| 6 | READ | Data-Reading button |
| 7 | RS232 | RS232C button |
| 8 | CLEAR | Clear memory button |
| 9 | ☀ | Backlight button |
| 10 | ▲ | Reverse-search button |
| 11 | ▼ | Forward-search button |
| 12 | REC/SAVE | Data recording & storage button |
| 13 | HOLD | Hold button |
3.4. LCD Display
The LCD provides a 4-digit digital display and a 7-segment LCD for showing measurement functions, test results, and unit signs.
LCD Symbol Descriptions:
| LCD symbol | Description | LCD symbol | Description |
|---|---|---|---|
| RS232 | Data transfer | REC | Data recording |
| APS | Auto powering-off | F | Fast |
| HOLD | Data holding | S | Slow |
| LAG | Phase angle lag | LEAD | Phase angle lead |
| ⏰ | Battery low indication | Φ | Phase angle (degree) |
| SINΦ | Reversed power factor | COSΦ | Power factor |
| RST | 3-phase | → | Normal phase |
| ~ | AC symbol | ↺ | Reversed phase |
| Phase lacking | ↻ | Negative symbol | |
| MIN | Minimum value | MAX | Maximum value |
| USED | Used | MEMO | Save |
| READ | Read | V | Voltage |
| W | Watt | A | Current |
| VAr | Passive power | Hz | Frequency |
| VA | Apparent power | PEAK | Peak value |
| % | Harmonic percentage | ⚡ | High-voltage warning sign |
| % THD | Total harmonics distortion ratio | ||
| H01F | Total harmonics distortion ratio F (relative to base wave) | ||
| H01r | Total harmonics distortion ratio r (relative to real effective value) |
4. Setup
4.1. Battery Installation
The meter requires 4 x 1.5V AA batteries for operation. Refer to the 'Battery Replacement' section for detailed instructions on how to install or replace batteries.
4.2. Connecting to PC (RS232C Data Interface)
The MS2205 is equipped with an RS232C interface for communication with a PC, allowing for real-time data transfer, recording, and graphical analysis using the dedicated WINDOWS software.
- Insert the RS232C interface wire into the socket on the meter and rotate it clockwise to lock it securely.
- Connect the standard RS232C plug on the other end of the interface wire to your PC's COM port.
- Real-time data transfer can now be achieved through the infrared communication RS232C interface.
- To unplug, rotate the interface-wire plug counter-clockwise in the meter, then carefully remove it once unlocked.
The dedicated software can be used for managing real-time data records, plotting, and printing outputs.
5. Operating Instructions
5.1. AC Voltage (V) Measurement
To measure AC voltage, follow these steps:
- Switch the function-switching knob to the V~ position.
- Select the appropriate input sockets (V1, V2, or V3 terminal) and insert the test wires. Use the yellow test probe for V1 (first phase), black for COM/V2 (second phase and common/earthing), and green for V3 (third phase).
- Connect the two test probes (e.g., V1 and V2) to the power source or load to be tested.
- The meter will automatically test and display the result. The present harmonics percentage will be shown on the following line.
- Under voltage test mode, press the SET button to show "Auto V" and "Auto A" on the LCD. Use the ▲ / ▼ buttons to select a proper voltage range, then press SET to confirm.
- Press the MODE button to display harmonics percentage on the LCD. The total harmonic distortion ratio F and R will be cyclically displayed. Use the ▲ / ▼ buttons to display the value of each harmonic measurement.
- If the input voltage is greater than 50 V, the "⚡" sign will appear on the LCD, indicating high voltage and prompting caution.
For a visual guide on AC voltage measurement connections, please refer to the diagram on page 10 of the official user manual PDF: User manual (PDF).
5.2. AC Current (A) Measurement
To measure AC current, follow these steps:
- Switch the function knob to the A~ position.
- Pull the trigger to open the clamp, then clip it around a single wire of the circuit to be tested.
- The measured current value will be automatically shown on the LCD.
- Press the MODE button to display harmonics percentage on the LCD. The total harmonic distortion ratio F and R will be cyclically displayed. Use the ▲ / ▼ buttons to display the value of each harmonic measurement.
- If the current of the wire being tested is greater than 1000 A (RMS), "OL" (Overload) will be displayed instead of the current value.
Note on Frequency Test:
- You can select 50/60-Hz FIXED/AUTO frequency test (AUTO).
- When input waveform fluctuates, displayed harmonic values can be kept stable if 50/60-Hz FIXED mode is selected.
- Under AUTO frequency test mode, FFT calculation is performed only when the base-wave frequency is between 45 and 65 Hz. Harmonic analysis is not performed if the base-wave frequency exceeds this range.
5.3. Single-Phase Circuit Measurement
This section covers measuring power and power factor for single-phase circuits.
- Clip the clamp on the test wire of the power supply or load. For a specific phase in a 3-phase circuit, clip the clamp on the wire of that phase.
- Switch the function-switching knob to the KW position. Select corresponding input sockets from V1 or V2 terminal and insert the test wire.
- After correct connection, the meter can measure single-phase power (active power, power factor, apparent power, passive power, voltage, current, phase angle, peak value of voltage and current, and frequency).
- The meter will automatically measure and display active power. The voltage/current value of the load being tested will be displayed on the bottom line of the LCD.
- Press the MODE button to display the VAr value of passive power.
- Press the WATT button to display apparent power and power factor (cos Φ). A negative power factor indicates a load with capacitor characteristics.
- The maximum measurement range for active power (kW) is 600 kW. If this range is exceeded, "OL" will be displayed. Similarly, "OL" will be displayed if voltage exceeds 600 V or current exceeds 1000 A.
- Minimum input voltage is 50 V and minimum input current is 2A. If active power is below this limit, "0.00 kW" will be displayed.
- Press SET to display AUTO, then use ▲ / ▼ to set the measurement range for voltage and current, and press SET to return.
- Press I to display current value, current peak value, and frequency on the bottom line.
- Press U to display voltage value, voltage peak value, and frequency on the bottom line.
- Press REC/SAVE to show MAX and MIN values.
- Passive power (kVAr) is calculated by software based on measured V, A, and kW values.
For a visual guide on single-phase circuit measurement connections, please refer to the diagram on page 13 of the official user manual PDF: User manual (PDF).
5.4. 3-Phase Load Measurement (Balanced and Imbalanced)
For Balanced Load:
The process for measuring power and power factor of a 3-phase 4-line circuit with a balanced load is similar to a 3-phase 3-line circuit. The middle line is not required. The meter cannot perform 3-phase energy measurement.
- Switch the function-switching knob to KW/Φ (3 phase) position.
- Connect the test clamp to the phase-1 test wire of the load.
- Connect V1 terminal (yellow test probe), V2 terminal (black test probe), and V3 terminal (green test probe) to the live lines of phase 1, phase 2, and phase 3, respectively, of the 3-phase load. Do not connect the neutral line.
- After proper connection, the meter will automatically measure and display power, voltage, current, and indicate if a phase is missing.
- Follow steps 5-12 from the 'Single-Phase Circuit Measurement' section for further readings and settings.
For a visual guide on 3-phase 3-line circuit measurement, please refer to the diagram on page 17 of the official user manual PDF: User manual (PDF).
Important Note for 3-Phase 3-Line Circuit:
When using an alternative mode for measuring power of a 3-phase 3-line circuit, rotate the gear to single-phase measurement mode. The V1 measurement line and current clamp must be measuring the same phase. Failure to do so will result in an incorrect reading.
For Imbalanced Load (3-Phase 4-Line Load):
The measuring process is similar to a 1-phase 2-line system, with the measuring mode set to 1-phase mode.
- Connect the black clip to the middle (neutral) line.
- Simultaneously switch the yellow clip and clamp sensor to corresponding wires for each phase.
- Under this mode, the power and power factor of each line can be tested individually.
- To test phase sequence, connect voltage clips to the three lines one by one, with the middle line not connected.
For a visual guide on 3-phase 4-line circuit measurement, please refer to the diagram on page 18 of the official user manual PDF: User manual (PDF).
Important Note for 3-Phase 4-Line Circuit:
The V1 measurement line and current clamp must be measuring the same phase. Failure to do so will result in an incorrect reading.
5.5. Phase Sequence Test
The meter automatically tests the phase sequence.
- Display of RST signifies normal phase sequence.
- Display of RST with a reversed symbol signifies reversed phase sequence.
- Display of RST with a missing symbol signifies missing phase.
During measurement, press REC/SAVE to show MAX and MIN values and record the results. Then, press REC/SAVE again to transfer the test result to PC via the infrared communication wire.
5.6. Test Data Storage and Retrieval
The meter can store up to 100 groups of data.
Storing Data:
- When the meter is in HOLD mode, press REC/SAVE to display the serial number for saving.
- Use the ▲ / ▼ buttons to select the desired serial number.
- Press SET to confirm saving.
- If you press REC/SAVE again before pressing SET, the data will not be saved, and the meter will return to the previous menu.
Reading Saved Data:
- Switch the function-switching knob to the READ SAVED DATA position.
- Press HOLD to display the saved data.
- Press READ to show the saved serial number and data on the LCD.
- Use the ▲ / ▼ buttons to navigate through records (backward/forward).
- When harmonic level data is displayed, press WATT then ▲ / ▼ to select the record number.
Clearing Data:
- In data-reading mode, press CLEAR. "CLR" will be displayed.
- Press SET to confirm deletion. If CLEAR is pressed again before SET, data will not be deleted.
5.7. Backlight Display
Press the backlight button (☀) to turn the backlight on or off. The backlight will automatically turn off after approximately 20 seconds.
5.8. Auto Power Off
- If there is no function change or button press for 10 minutes, the meter will automatically power off. When this occurs, switch the knob to "OFF" position, then turn on the meter after 5 seconds.
- To disable auto power off, hold down the SET & CLEAR buttons while turning the meter on.
- Auto power off is also disabled when the meter is in MAX/MIN Record mode or communicating with PC software.
6. Maintenance
6.1. Battery Replacement
WARNING: Ensure the meter is turned off and no test probes are connected to any test wire before opening the back lid to replace batteries, to avoid electrical shock. Ensure the back lid is tightly closed before using the meter.
If the battery voltage is low, the ⏰ symbol will be displayed on the upper right corner of the LCD, indicating that new batteries are needed.
- Disconnect test probes from the test circuit and rotate the function-switching knob to "OFF". Remove test probes from the input sockets.
- Open the battery cover. Note the self-locking structure. Use a screwdriver to unscrew the two screws securing the battery cover, then remove the cover.
- Do not use a tapered tool to pry open the cover, as this may damage the meter housing.
- Remove the old batteries and replace them with 4 new 1.5 V AA batteries. Do not mix new batteries with old ones.
- Properly close the battery cover, ensuring it is securely fastened.
6.2. Cleaning
To clean the meter, use a soft, dry cloth. Do not use abrasive cleaners or solvents. Ensure the meter is powered off and disconnected from any circuits before cleaning.
7. Troubleshooting
- "OL" Display: This indicates an over-range condition. The input voltage is over 600 V (RMS) or the current is over 1000 A (RMS). Reduce the input to within the meter's specified limits.
- Battery Low Indication (⏰): The battery voltage is low. Replace the batteries as described in the 'Battery Replacement' section.
- Incorrect Reading in 3-Phase Measurement: When measuring power of a 3-phase 3-line circuit in single-phase measurement mode, ensure the V1 measurement line and current clamp are measuring the same phase. Mismatch will lead to incorrect readings.
- Meter Automatically Powers Off: This is a normal function (Auto Power Off) after 10 minutes of inactivity. To resume, switch the knob to "OFF" and then back on after 5 seconds. To disable this feature, refer to the 'Auto Power Off' section.
- Burned Input Resistors: If internal components like input resistors are damaged, it is recommended to contact the manufacturer or an authorized service center for repair or replacement parts. Attempting to repair without proper knowledge and parts may cause further damage or safety hazards.
8. Specifications
For detailed technical specifications, please refer to the official user manual PDF: User manual (PDF).
8.1. General Specifications
- Compliance: IEC/EN 61010-1 1000V CAT II, 600 V CAT III
- Max. Common-Mode Voltage: 600V AC RMS
- Mode of Display: LCD display; Max. reading: 6000
- Range Selection: Fully automatic range selection
- Frequency Detection: Automatic (manual settings recommended for serious harmonics for reading stability)
- Over-range Display: "OL"
- Data Holding: "HOLD" is shown on LCD
- Power Supply: 4 batteries of 1.5 V, AA
- Power Consumption: 250 mW
- Storage Temperature: -20℃ ~ 70℃
- Operating Temperature: 0℃ ~ 40℃
- Temperature Coefficient: 0.05 × (specified accuracy) per ℃
- Electromagnetic Compatibility: In an RF field of 3V/M, accuracy is specified accuracy; otherwise, accuracy is unspecified.
- Operating Altitude: 2000m CAT III 600V; 3000m CAT II 600V
- Store Altitude: 12000m
- Dimensions: 300mm × 103mm × 51mm
- Weight: About 500 g (with battery)
8.2. Technical Specifications (Accuracy: ±(% read + graduation #) at 18℃ ~ 28℃, Humidity 80%, frequency for voltage, current: 45 Hz ~ 65 Hz)
AC Voltage (RMS)
| Range | Accuracy | Resolution | Input impedance |
|---|---|---|---|
| 80V | ±(1.0%+5) | 0.1V | 1 MΩ // 10 pF |
| 180V | ±(1.0%+5) | 0.1V | |
| 400V | ±(1.0%+5) | 1V | |
| 600V | ±(1.0%+5) | 1V |
Max. allowed overload voltage: 750 V (RMS)
AC Current (RMS)
| Range | Accuracy | Resolution |
|---|---|---|
| 20A | ±(2%+5) | 0.01A |
| 40A | ±(2%+5) | 0.01A |
| 100A | ±(2%+5) | 0.1A |
| 200A | ±(2%+5) | 0.1A |
| 450A | ±(2%+5) | 1A |
| 1000A | ±(2%+5) | 1A |
Max. allowed overload current: 1200 A
Single-phase active power (W)
| Range | Accuracy | Resolution |
|---|---|---|
| 30kW | ±(3%+5) | 0.01kW |
| 60kW | ±(3%+5) | 0.01kW |
| 120kW | ±(3%+5) | 0.1kW |
| 150kW | ±(3%+5) | 0.1kW |
| 300kW | ±(3%+5) | 0.1kW |
| 600kW | ±(3%+5) | 0.1kW |
Min. test current: 2A; Min. test voltage: 50V
Three-phase active power (W)
| Range | Accuracy | Resolution |
|---|---|---|
| 3kW | ±(3%+5) | 0.001kW |
| 12kW | ±(3%+5) | 0.01kW |
| 30kW | ±(3%+5) | 0.01kW |
| 120kW | ±(3%+5) | 0.1kW |
| 150kW | ±(3%+5) | 0.1kW |
| 600kW | ±(3%+5) | 0.1kW |
Power Factor
| Range | Accuracy | Resolution |
|---|---|---|
| 0.3~1 Capacitive | ±(0.02+2) | 0.001 |
| 0.3~1 Inductive | ±(0.02+2) | 0.001 |
Min. test current: 2A; Min. test voltage: 50V. When measuring current < 6A and voltage < 50V, setting a fixed frequency measurement can improve accuracy.
Apparent Power
| Range | Precision | Resolution |
|---|---|---|
| 3kVA | ±(3%+5) | 0.001kVA |
| 12kVA | ±(3%+5) | 0.01kVA |
| 30kVA | ±(3%+5) | 0.01kVA |
| 120kVA | ±(3%+5) | 0.1kVA |
| 150kVA | ±(3%+5) | 0.1kVA |
| 600kVA | ±(3%+5) | 0.1kVA |
Min. input current: 2A; Min. input voltage: 50V. Apparent power (VA) is calculated according to the measured V, A, and kW values.
Passive Power
| Range | Precision | Resolution |
|---|---|---|
| 3kVAr | ±(3%+5) | 0.001kVAr |
| 12kVAr | ±(3%+5) | 0.01kVAr |
| 30kVAr | ±(3%+5) | 0.01kVAr |
| 120kVAr | ±(3%+5) | 0.1kVAr |
| 150kVAr | ±(3%+5) | 0.1kVAr |
| 600kVAr | ±(3%+5) | 0.1kVAr |
Min. input current: 2A; Min. input voltage: 50V. Passive power (VAr) is calculated according to the measured V, A, and kW values.
Frequency (Hz)
| Range | Accuracy | Resolution |
|---|---|---|
| 30Hz~1kHz | 0.5% + 1 graduation | 0.1Hz |
Min. test voltage: 50 V
Harmonic Test (Precision of harmonic voltage)
| Harmonic number | Precision |
|---|---|
| 1 | ±(3.0%+10) |
| 2-6 | ±(3.5%+10) |
| 7-8 | ±(4.5%+10) |
| 9-10 | ±(5.0%+10) |
| 11-15 | ±(7%+10) |
| 16-20 | ±(10%+10) |
Min. test voltage 50V; Min test current 2A
9. Accessories
The following accessories are included with your PEAKMETER MS2205:
| Item | Quantity |
|---|---|
| Instruction Manual | 1 |
| 1.5V AA Battery | 4 |
| Test probe | 1 |
| Test clip | 3 |
| Interface cable | 1 |
| PC Software CD | 1 |
| Package box | 1 |
10. Warranty and Support
10.1. Quality Assurance and Warranty
This product comes with a warranty period of one year starting from the purchase date. The manufacturer ensures that this product has passed strict quality tests.
In case of any problem due to product quality during the warranty period, please fill in the warranty card and mail it with the product. The service department will repair or replace it free of charge. The user should not disassemble the meter.
Repairs outside the warranty period will be charged.
10.2. Free Service Exclusions
Free service does not apply to the following cases:
- Problems and damages due to improper use or use under environments not stipulated for this product, including overloading.
- Problems and damages due to unauthorized dismantling, refitting, or misuse.
- Problems and damages due to user reasons.
- Problems and damages due to natural disasters.
10.3. Contact and Support
For technical support, service, or inquiries regarding replacement parts, please contact your retailer or the manufacturer's customer service. Refer to the product packaging or the official website for contact details.
11. User Tips
- Handle with Care: The device is a precision instrument. Always use the wrist belt provided to prevent accidental drops, as shown in the 'Diagram of Safe Holding' (refer to page 20 of the PDF manual).
- Replacement Parts: If any internal components, such as resistors, are damaged, it is crucial to seek professional assistance. Contact the manufacturer or an authorized service center for genuine replacement parts and repair services to ensure the meter's accuracy and safety.