1. Introduction
This manual provides essential information for the installation, operation, and maintenance of your XINJE 7-inch TouchWin Human Machine Interface (HMI) Touch Screen. The TouchWin HMI series offers a robust and user-friendly interface for industrial control applications, featuring various connectivity options and a high-resolution display. Please read this manual thoroughly before using the device to ensure proper and safe operation.

2. Product Overview
The XINJE 7-inch TouchWin HMI is designed for industrial automation, providing a visual interface for controlling and monitoring machinery. Key features include a 7.0-inch TFT LCD with 16 million colors, 800*480 resolution, and LED backlight. It is powered by an ARM9 CPU with a 400MHz dominant frequency, 128M of memory, and 128M storage capacity.
Model Differences:
- TG765-MT: Features a USB-B port.
- TG765-UT: Includes a USB-B port and a USB-A port.
- TG765-ET: Equipped with a USB-B port, a USB-A port, and an Ethernet port.
- TG765-XT-C: A streamlined version of the HMI.
- TG765S-MT, TG765S-XT, TG765S-UT: These are additional variants within the 7-inch series, offering similar core functionalities with potential minor differences in specific features or form factor.
Core Product Features:
- ARM9 CPU, 400MHz dominant frequency, 128M memory, 128M storage capacity.
- 7.0 inches, 16 million colors, TFT LCD, LED backlight, 800*480 resolution.
- Two COM ports for independent communications, supporting RS232, RS485, RS422 protocols.
- Standard real-time clock (RTC).
- Two USB ports for fast data transfer and storage.
- USB-A interfaces (front and/or behind, depending on model) for data backup.
- Supports multiple Ethernet communication protocols, including MODBUS TCP devices and S7-1200PLC (for models with Ethernet).


Video 1: Demonstration of HMI touch screen testing and functionality.
3. Specifications
The following table details the technical specifications for the XINJE 7-inch TouchWin HMI (TG765-MT model shown as an example, other models may vary slightly in port configuration).

| Category | Item | Specification |
|---|---|---|
| Electrical | Input voltage | DC22-26V |
| Current consumption | 200mA | |
| Momentary power off allowance | Less than 10ms | |
| Port | COM0 | PLC RS232/PLC RS485-2/4 |
| COM1 | PLC RS232/PLC RS485-2/4 | |
| COM2 | PC/PL | |
| USB2 | USB-B (USB2.0) | |
| Ambient | Operate temperature | 0-50°C |
| Storage temperature | -20-60°C | |
| Humidity | 10-90% (no condensation) | |
| Withstand vibration | 10-25HZ (X, Y, Z each direction 30 minutes 2G) | |
| Noise immunity | Voltage noise: 1500Vp-p, pulse 1Ms, 1 minute | |
| Protection level | IP65 | |
| Screen | Screen size | 7 inch |
| Resolution | 800*480 | |
| Touch panel | 4-wire resistance mode | |
| Using life | More than 50000 hours (at 25°C) | |
| Memory | FLASH | 128M |
| DDR2 | 64M | |
| Construction | Cooling method | Natural air cooling |
| Dimension | 204.0*150.5*43.9 mm | |
| Mounting dimension | 192.0*138.5 mm |
4. Setup
Careful setup is crucial for the optimal performance and longevity of your HMI unit.
4.1 Mounting
The HMI unit is designed for panel mounting. Ensure the cutout in your panel matches the mounting dimensions of 192.0mm x 138.5mm. Secure the unit using appropriate fasteners to prevent vibration.
4.2 Power Connection
Connect the HMI to a stable DC power source within the specified voltage range of DC22-26V. Ensure the power supply can provide at least 200mA. Incorrect voltage or unstable power can damage the unit.
4.3 Communication Port Connections
Depending on your HMI model and application, connect the necessary communication cables:
- COM Ports (COM0, COM1, COM2): Use these ports for connecting to PLCs (Programmable Logic Controllers) or PCs via RS232, RS485, or RS422 protocols. Refer to your PLC's documentation for specific wiring requirements.
- USB-B Port (USB2.0): Used for programming the HMI and transferring data.
- USB-A Port (Host): Available on TG765-UT and TG765-ET models for connecting USB devices for data backup or other functions.
- Ethernet Port: Available on TG765-ET models for network communication, supporting protocols like MODBUS TCP and S7-1200PLC.
4.4 Software Installation
The necessary programming software for the TouchWin HMI is provided free of charge. If you are unable to download it, please contact support for assistance.
5. Operating
Once the HMI is properly installed and powered, it is ready for operation. The 7-inch 4-wire resistance mode touch panel allows for intuitive interaction with your industrial processes.
- Interface Navigation: Use the touch screen to navigate through the programmed screens and control connected devices.
- Data Transfer: Utilize the USB ports for transferring project files to the HMI or backing up operational data.
- Multi-Screen Support: The HMI supports multiple screens, allowing for comprehensive visualization of complex systems.
- Ethernet Communication: For models with Ethernet, configure network settings to communicate with MODBUS TCP devices or S7-1200 PLCs, enabling advanced control and data exchange.
6. Maintenance
Regular maintenance ensures the longevity and reliable operation of your HMI unit.
- Cleaning: Clean the screen and casing with a soft, dry cloth. Avoid using abrasive cleaners or solvents that could damage the display or plastic.
- Environmental Conditions: Ensure the HMI operates within the specified temperature (0-50°C) and humidity (10-90% non-condensing) ranges. Avoid exposure to corrosive gases.
- Firmware Updates: Periodically check for firmware updates from the manufacturer to ensure optimal performance and access to new features.
- Data Backup: Regularly back up your HMI project files and operational data to an external storage device via the USB-A port (if available) or PC connection.
7. Troubleshooting
If you encounter issues with your HMI, consider the following general troubleshooting steps:
- No Power: Verify the power supply connections and ensure the input voltage is within the DC22-26V range.
- Display Issues: Check cable connections, power supply, and ensure the operating temperature is within limits.
- Touch Screen Unresponsive: Recalibrate the touch screen if the option is available in the system settings. Ensure the screen is clean and free from obstructions.
- Communication Errors: Verify all communication cables are securely connected and that the correct protocols (RS232, RS485, RS422, Ethernet) and settings are configured in both the HMI and the connected device (PLC/PC).
- Software/Programming Issues: Ensure you are using the correct version of the programming software. If issues persist, try reinstalling the software or contacting technical support.
For complex issues, refer to the detailed troubleshooting guide in the software documentation or contact XINJE technical support.
8. User Tips
- PLC Communication Cables: When connecting to a PLC, ensure you have the correct communication cable for your specific PLC brand and model. Compatibility can vary.
- Software Access: The HMI programming software is provided free. If you have difficulty downloading it, contact the seller or manufacturer for direct assistance via email.
- Data Backup: Regularly back up your HMI project files to prevent data loss.
9. Warranty and Support
XINJE provides warranty and support services for its products:
- Warranty: New products come with a 6-month warranty.
- Technical Support: For any needs or questions, you can consult XINJE support. Inquiries are typically answered within 24 hours.
For specific support requests, please have your product model and any relevant error messages ready.