1. Important Safety Instructions
Please read all safety instructions carefully before installation and operation. Failure to follow these instructions may result in electric shock, fire, or equipment damage.
WARNING
- Disconnect Power: Always ensure the power supply is completely disconnected before wiring. Do not operate while live to prevent the risk of electric shock.
- Rated Usage: This product is only applicable to circuits within its rated voltage and current range. Refer to the product casing or specifications table for specific parameters. Overloading can cause fires or equipment damage.
- Environment: Avoid installing this product in damp, dusty, or flammable/explosive environments. It is suitable only for indoor use in dry, non-corrosive gas conditions.
- No Disassembly: Do not disassemble or modify this product. Non-professional operation may damage the insulation performance and cause safety hazards.
- Keep Out of Reach: Keep this product out of reach of children.

Figure 1: QHJIA UKK Series Din Rail Terminal Blocks
2. Product Overview
The QHJIA UKK Series Din Rail Terminal Blocks are designed for efficient power distribution, offering a one-input, multiple-output solution. They are suitable for various cable branches and can be easily spliced together for modular configurations.

Figure 2: UKK Series Model Identification

Figure 3: Splice Card Slot Design for Modular Connection
3. Setup and Installation
Follow these steps for safe and correct installation of your UKK Series terminal block. Refer to the safety instructions in Section 1 before proceeding.
Installation Steps:
- Prepare the Terminal: Push the two side clips upward on the terminal block.
- Open Wire Cover: Open the transparent wire clip cover.
- Insert Wire: Insert the stripped wire or cable into the appropriate hole. Ensure proper polarity if applicable (e.g., 'Red' to '+' and 'Black' to '-').
- Secure Wire: Close the clip cover tightly to secure the wire.
- Connect Other Parts: Connect other necessary electrical components as per your wiring diagram.
- Mounting: The UKK series is designed for DIN rail mounting. Secure the terminal block onto the DIN rail by pressing it down until it clicks into place.

Figure 4: Internal View of Connection Points (Hexagon Socket Screw, Brass Tinning)
4. Operating Instructions
Once installed, the UKK Series terminal block functions as a passive power distribution component. Ensure all connections are secure and within specified ratings before applying power.
- Power Application: After all wiring is complete and thoroughly checked, apply power to the main input.
- Load Distribution: The terminal block will distribute power to the connected output wires.
- Visual Inspection: Periodically inspect the terminal block for any signs of overheating, loose connections, or damage.

Figure 5: One-Input Multiple-Output Distribution Line
5. Maintenance
The UKK Series terminal blocks are designed for durability and require minimal maintenance.
- Regular Inspection: Periodically (e.g., every 6-12 months, or as required by your electrical system's maintenance schedule) inspect all connections for tightness. Vibrations can sometimes loosen screws over time.
- Cleaning: Ensure the terminal block is free from dust, dirt, and moisture. Use a dry, non-abrasive cloth for cleaning. Disconnect power before cleaning.
- Damage Check: Check for any physical damage, discoloration (indicating overheating), or corrosion on the terminals. Replace any damaged units immediately.
6. Troubleshooting
If you experience issues with your electrical connections, consider the following troubleshooting steps:
- No Power Output:
- Check if the main power input to the terminal block is live.
- Verify all wires are correctly inserted and securely tightened.
- Ensure the wire gauge matches the terminal block's specifications (refer to Section 7).
- Overheating:
- Immediately disconnect power.
- Check if the total current draw through the terminal block exceeds its rated capacity.
- Ensure all connections are tight; loose connections can cause resistance and heat.
- Verify the wire gauge is sufficient for the current being carried.
- Loose Connections:
- Disconnect power.
- Re-tighten all hexagon socket screws.
- Ensure wires are fully inserted into the terminals.
7. Specifications
The QHJIA UKK Series Din Rail Terminal Blocks are made from PC material and are CE and RoHS certified. Detailed specifications for each model are provided below:
| Model | Current (Amp) | Voltage (V) IEC | Conductor Connection Range (mm²) | Quantity of Holes (pcs) | Dimensions (mm) |
|---|---|---|---|---|---|
| UKK-80A | 80A | 690V | 1x (6 to 16), 2x (2.5 to 16) | x1, x2 | 65.1 x 77.3 x 29.55 |
| UKK-125A | 125A | 690V | 1x (10 to 35), 2x (2.5 to 16) | x1, x7 | 70.5 x 87.87 x 31.94 |
| UKK-160A | 160A | 690V | 1x (10 to 70), 2x (2.5 to 16) | x1, x7 | 70.5 x 90.27 x 32.72 |
| UKK-250A | 250A | 690V | 1x (35 to 120), 2x (6 to 35), 2x (2.5 to 16), 4x (2.5 to 10) | x1, x2, x5, x4 | 88.2 x 100 x 43.36 |
| UKK-400A | 400A | 690V | 1x (95 to 185), 2x (6 to 35), 2x (2.5 to 16), 4x (2.5 to 10) | x1, x2, x5, x4 | 95 x 100 x 48.39 |
| UKK-500A | 500A | 690V | 1x (4x15.5x0.8 to 8x24), 2x (6 to 35), 2x (2.5 to 16), 4x (2.5 to 10) | x1, x2, x5, x4 | 95 x 100 x 48.39 |

Figure 6: UKK Series Detailed Specifications
General Specifications:
- Material: PC (Polycarbonate)
- Certification: CE, RoHS
- Origin: Mainland China
- Wireless Functionality: No
- Battery Included: No
- High-Concerned Chemical: None
8. User Tips
No specific user tips were available from buyer reviews or Q&A for this product. However, general best practices for electrical terminal blocks include:
- Always use the correct tool (e.g., hexagon wrench) for tightening screws to ensure a secure connection without stripping.
- Ensure proper wire stripping length to maximize contact area and prevent stray strands.
- When splicing multiple blocks, ensure they are fully engaged to maintain mechanical and electrical integrity.
9. Warranty and Support
For warranty information, technical support, or further inquiries regarding your QHJIA UKK Series Din Rail Terminal Block, please contact your original point of purchase or the manufacturer directly. Keep your purchase receipt as proof of purchase.
This manual is based on information available at the time of publication. Specifications and features are subject to change without notice.