1. Introduction
The Aideepen BT13 Coulombmeter is a versatile battery management module designed for bidirectional current detection, charge and discharge management, and protection. It supports a wide voltage range (DC 10-110V) and current up to 30A, featuring a dedicated liquid crystal display and support for serial communication via the Modbus protocol. This manual provides detailed instructions for its setup, operation, and maintenance.
2. Safety Information
- Ensure all connections are secure and correct before applying power to prevent damage to the device or connected components.
- Operate within the specified voltage (DC 10-110V) and current (30A for BT13L) limits.
- Avoid short circuits during wiring and operation.
- Keep the device away from moisture, extreme temperatures, and corrosive environments.
- If an external temperature probe is used, ensure it is correctly installed and rated for the expected temperature range.
3. Product Overview and Features
The BT13 Coulombmeter integrates a display, control buttons, and relay switches for comprehensive battery management. Key features include:
- Bidirectional Current Detection: Accurately measures current flow in both charging and discharging directions.
- Precision Capacity Measurement: Monitors battery capacity in Ampere-hours (Ah).
- Overcharge & Overdischarge Protection: Safeguards batteries from damage due to extreme charge levels.
- Dedicated Liquid Crystal Display: Provides real-time data on voltage, current, capacity, energy, runtime, and temperature.
- UPS Mode: Supports uninterruptible power supply functionality.
- Protection Features: Includes Over Voltage Protection (OVP), Low Voltage Protection (LVP), Over Current Protection (OCP), Over Temperature Protection (OTP), Low Battery Alarm, Delayed Conduction, and Forced Conduction.
- Serial Communication: Supports standard Modbus protocol for remote control and data acquisition.

Figure 1: BT13 Coulombmeter highlighting key features and protection modes.

Figure 2: Front view of the BT13 Coulombmeter with its display and terminal blocks.

Figure 3: Internal view of the BT13 PCB, showcasing the high-precision external clock crystal oscillator, 30A bidirectional current sampling chip, and 48-pin MCU controller.
4. Specifications

Figure 4: Product Specifications.
| Parameter | Value (BT13L) |
|---|---|
| Brand | Aideepen |
| Model | XY-BT13L |
| Battery Voltage Range | 10-110V |
| Adapter Input Voltage Range | 10-110V |
| Maximum Current | 30A |
| Voltage Accuracy | ±0.5%+1 word |
| Current Accuracy | ±0.5%+3 words |
| Current Resolution | 0.01A |
| Voltage Resolution | 0.01V |
| Operating Temperature | -10 ~ 60 °C |
| Product Size (L x W x H) | 80 x 78 x 22 mm |
| Product Weight | 100g |

Figure 5: Device and packaging dimensions.
5. Setup and Installation
5.1. Wiring Diagram
Proper wiring is crucial for the safe and correct operation of the BT13 Coulombmeter. Refer to the diagram below for connections.

Figure 6: Wiring Diagram and Component Functions.
- IN+ / IN-: Connect to the charger (input power source).
- BT+ / BT-: Connect to the battery/rechargeable battery.
- OUT+ / OUT-: Connect to the load.
- 30A Charging Relay Switch: Controls the charging circuit.
- 30A Discharging Relay Switch: Controls the discharging circuit.
- NTC OUT: For external temperature probe connection.
- Buzzer: Provides audible alerts.
- Serial Communication Interface: For TTL-to-RS485 module or WiFi module connection.
5.2. Initial Setup: Capacity Correction
For accurate battery capacity monitoring, it is essential to perform capacity correction when using the device for the first time or when replacing the battery. There are two methods:
5.2.1. Unknown Battery Capacity (Learning Mode)
- Connect: Simply connect both the charger and the battery to the BT13 to initiate capacity learning mode.
- Switch Interface: Briefly press the SET button to switch the display to the capacity parameter (Ah) interface.
- Enter Correction Mode: Press and hold the UP button for more than 5 seconds to enter the Capacity Correction Mode. The device will then learn the battery's capacity through a full charge/discharge cycle.
- Exit Correction Mode: To forcibly exit during the process, press and hold the UP button for more than 5 seconds.
5.2.2. Known Battery Capacity (Manual Setting)
- Enter Settings: Press and hold the SET button for 2 seconds on the main UI to enter the settings interface.
- Navigate to CAP: Use the UP/DOWN buttons to navigate to the CAP (Set Battery Full Capacity) parameter.
- Adjust Value: Briefly press the UP/DOWN buttons to adjust the parameter value to your battery's known capacity.
- Exit Settings: After setting, press and hold the SET button for 2 seconds again to exit the settings interface. The parameters will be saved automatically.
6. Operating Instructions
6.1. Basic Operation
Video 1: Demonstration of charging, discharging, display cycling, and parameter settings.
- Power On: Ensure all connections (charger, battery, load) are secure. The device will power on and display current battery status.
- Cycle Displays: Briefly press the SET button to cycle through various display parameters on the lower screen: Power (W), Capacity (Ah), Energy (Wh), Battery Level (%), Runtime (h), and Temperature (°C/°F).
- Charging Mode: When charging, the charging relay closes, the charging icon flashes, and the battery capacity icon dynamically displays the charging process.
- Discharge Mode: When discharging, the discharge relay closes, the discharge icon flashes, and the battery capacity icon dynamically displays the discharging process.
- STOP Button Functions:
- Short Press: Emergency stop.
- Long Press (Charging Mode): Force switch to discharge mode.
- Long Press (Discharge Mode): Force switch to charging mode.
6.2. System Parameter Settings
Long press the SET button to enter the system parameter settings menu. Use UP/DOWN buttons to adjust values and short press STOP to shift position. Long press SET again to confirm and exit.
| Parameter | Description |
|---|---|
| CAP | Set Battery Full Capacity (Ah) |
| FUC | Charging Mode Operation: CH (Charging), DCK (Discharging), UPS (UPS Mode) |
| LBP | Low Battery Alarm Threshold (%) |
| LVP | Low Voltage Protection (V) |
| OVP | Over-Voltage Protection (V) |
| LAP | Threshold Current (A) for auto-switching modes |
| OCP | Over-Current Protection (A) |
| OHP | Operating Time Protection (h:min) |
| OTP | Device Over-Temperature Protection (°C/°F) |
| ETP | External Over-Temperature Protection (°C/°F) |
| DOP | Delayed Turn-on Time (s) |
| FOP | Forced Turn-on Time (s) |
| LOP | LOP Auto Charge-Discharge Cycle Control (cycles) |
| POd | Power-On Status (ON: Auto-operate in FUC mode; OFF: Inactive) |
| BEP | Buzzer Enable/Disable (ON/OFF) |
| Add | ModBus Address (1-247) |
| C-F | Temperature Unit Switch (°C/°F) |
| CLU | Voltage Calibration |
| CLA | Current Calibration |
| ZERO | Current Zero-Point Calibration |
| RET | Factory Reset |
6.3. UPS Mode
In UPS mode, both charging and discharging relays remain simultaneously closed. The charger supplies power to both the battery (charging) and the load. If AC power fails, the battery automatically powers the load. When AC power resumes, the system restores charging while continuing to power the load. This mode requires the charger's output power to exceed the sum of charging power and load power.
To enable UPS mode, set the FUC parameter to