PEAKMETER MS2205

Contents

PEAKMETER MS2205 Multifunctional Intelligent Three-Phase Clamp Harmonic Power Meter User Manual

Model: MS2205 | Brand: PEAKMETER

1. Introduction

The PEAKMETER MS2205 is a handheld intelligent harmonic power meter designed for comprehensive electrical measurements. It combines digital current testing and power testing functionalities, making it suitable for on-site power equipment and power-supplying circuit analysis. Its compact, clamp-type design ensures ease of use and portability.

This manual provides detailed instructions for the safe and effective operation of your MS2205 meter. Please read it thoroughly before use and keep it for future reference.

2. Safety Requirements and Instructions

WARNING: Before use, please carefully read this instruction manual, especially the safety contents!

To ensure safe operation, observe the following precautions:

  1. Exercise extreme caution when testing voltages higher than AC 30 V. Ensure your fingers do not extend beyond the hand-shielding part of the test probe.
  2. Do not measure voltage exceeding the allowed input limit.
  3. Before each use, inspect the meter and test probes. Do not proceed with testing if the test probe is exposed, the tester housing is damaged, or the LCD display is not functioning.
  4. The meter meets safety standards only when used with the supplied test probes. If a test probe is damaged, replace it with one of the same model and identical electrical specifications.
  5. Never perform voltage measurements with the test probe inserted into any current outlet.
  6. Avoid exposing the meter to strong light, high temperatures, or damp conditions.

Safety Signs

Sign Description
⚠ Important safety signs; please refer to instruction manual
⚡ High voltage hazard
☇ Earthing
□ Double insulation (Category-II safety equipment)
⚒ Battery low Indicator

The three-phase clamp-type digital power meter is designed and manufactured in accordance with international standard IEC61010-1 and international safety specification IEC1010-2-032. It strictly adheres to the safety standard of double-insulation AC 600 V CAT III.

3. Product Overview and Features

The PEAKMETER MS2205 is a hand-held intelligent harmonic power tester, offering both digital current testing and power testing functions. It incorporates three channels for voltage, current, and power, powered by a micro single-chip system. The device features powerful software for measurement and data processing, enabling it to measure, calculate, and display voltage, current, active power, power factor, apparent power, passive power, frequency, and harmonic parameters with stable performance and operational convenience.

Its handheld clamp structure, small volume, and light weight make it ideal for on-site measurement and examination of power equipment and power-supplying circuits. It is an excellent choice for both single-phase and three-phase power measurements.

Key Features:

  • Measures power, voltage, current, peak value, phase, frequency, power factor, phase angle, and reaction factor for single-phase and three-phase circuits.
  • Automatic phase sequence testing for three-phase measurements.
  • True effective value measurement for accurate readings even with distorted current waveforms.
  • Low-consumption high-speed single-chip microprocessor and sophisticated algorithm for rapid and precise results.
  • Measures up to 20 harmonics and their distortion values.
  • Large memory to save up to 100 groups of test parameters.
  • Equipped with RS232C communication and recording interface, compatible with dedicated WINDOWS graphics software.
  • Hand-held, clamp-type structure, lightweight, and portable.

Appearance and Controls

Labeled diagram of PEAKMETER MS2205 Clamp Power Meter controls
Figure 3.1: PEAKMETER MS2205 Clamp Power Meter - Front Panel Controls
  • Clamp Jaws: For clamping around conductors to measure current.
  • Clamp Trigger: Opens the clamp jaws.
  • Current Measurement Button: Initiates current measurement.
  • Measurement Mode Button (MODE): Switches between test modes.
  • Set Button (SET): Used for setting ranges and confirming selections.
  • Power Measurement Button (WATT): Displays power-related measurements.
  • LCD Display: Shows measurement results, units, and operational functions.
  • Up Selection Button (▲): Used for navigating menus or increasing values.
  • Backlight Button (☀): Toggles display backlight.
  • Input Port (V1, COM/V2, V3): Terminals for connecting test probes.
  • Data Hold Button (HOLD): Freezes the current reading on the display.
  • Function Knob: Rotary switch for selecting measurement functions and powering on/off.
  • Voltage Test Button (U): Initiates voltage measurement.
  • Read Button (READ): Accesses stored data.
  • Clear Storage (CLEAR): Clears stored data.
  • RS232 Communication Button (RS232): Initiates data transfer via RS232.
  • Record/Store Button (REC/SAVE): Records and saves data.
PEAKMETER MS2205 Clamp Power Meter showing 50mm jaw opening
Figure 3.2: Clamp Jaw Opening Size (50mm)
PEAKMETER MS2205 Clamp Power Meter with dimensions 300mm by 103mm
Figure 3.3: Approximate Dimensions of the MS2205 (300mm x 103mm)

4. Setup

4.1 Battery Installation

The MS2205 meter uses 4 AA 1.5V batteries. If the battery low indicator (⚒) is displayed on the LCD, it's time to replace the batteries.

Open battery compartment of PEAKMETER MS2205 showing 4 AA batteries
Figure 4.1: Battery Compartment (Uses 4 AA Batteries)
  1. Ensure the meter is turned OFF and no test probes are connected to any test wire to prevent electrical shock.
  2. Disconnect all test probes from the test circuit and rotate the function-switching knob to the "OFF" position.
  3. Open the battery cover. Use a screwdriver to unscrew the two screws securing the battery cover.
  4. Carefully remove the battery cover. Do not use tapered tools to pry it open, as this may damage the meter housing.
  5. Remove the old batteries and replace them with 4 new 1.5 V AA batteries. Ensure correct polarity. Do not mix new and old batteries.
  6. Properly close and secure the battery cover with the screws.

4.2 Test Probe Connection

The meter comes with a set of test probes (red, yellow, black, green) and an RS232C communication cable.

Set of colored test leads for the PEAKMETER MS2205
Figure 4.2: Included Test Leads
Terminal Function Recommended Probe Color
V1 Input terminal for measuring the first phase Yellow
COM/V2 Input terminal for measuring the second phase; Common terminal (earthing) for all measuring functions Black
V3 Input terminal for measuring the third phase Green

Always ensure test probes are securely connected to the appropriate input terminals before taking measurements.

5. Operating Instructions

5.1 Powering On/Off and Function Selection (Knob Switch)

The function-switching knob is used to power on the meter and select the desired measurement function. To power off, turn the knob to the "OFF" position. If the meter automatically powers off, ensure the knob is set to "OFF" before turning it back on after 5 seconds.

Knob Position Function
OFF Powers off the meter.
KW (1 phase) Measures active power for single-phase circuits.
Φ (1 phase) Measures single-phase/phase-angle, such as cos Φ and sin Φ.
KW/Φ (3 phase) Measures three-phase apparent power.
A~ Measures AC-current harmonics.
V~ Measures AC-voltage harmonics.

5.2 Button Switch Operations

Button Function
MODE Switches between test modes (e.g., active/passive power, harmonic distortion rate).
SET Sets current/voltage ranges, confirms storage/deletion. Press and hold during power-on to set fixed frequency (50Hz, 60Hz, Auto).
I Measures and displays current.
WATT Displays active power, apparent power, power factor, and phase angle.
U Measures and displays voltage.
READ Displays stored data under HOLD mode.
RS232 Transfers data to PC.
CLEAR Clears stored data.
☀ (Backlight) Turns backlight on/off. Automatically turns off after 20 seconds.
▲ (Up) Reverse-search, changes voltage test range, or increases harmonic times.
▼ (Down) Forward-search, changes current test range, or decreases harmonic times.
REC/SAVE Records and stores data, displays MAX/MIN values.
HOLD Holds the current display.

5.3 LCD Display Symbols

Symbol Description Symbol Description
RS232Data transferRECData recording
APSAuto powering-offFFast
HOLDData holdingSSlow
LAGPhase angle lagLEADPhase angle lead
⚒Battery low indicationΦPhase angle (degree)
SINΦReversed power factorCOSΦPower factor
RST3-phase→Normal phase
~AC symbol←Reversed phase
→Phase lacking←Negative symbol
MINMinimum valueMAXMaximum value
USEDUsedMEMOSave
READReadVVoltage
WWattACurrent
VArPassive powerHzFrequency
VAApparent powerPEAKPeak value
%Harmonic percentage⚡High-voltage warning sign
% THDTotal harmonics distortion ratio
H01FTotal harmonics distortion ratio F (relative to base wave)
H01rTotal harmonics distortion ratio r (relative to real effective value)

5.4 AC Voltage (V) Measurement

Diagram showing AC voltage measurement setup with PEAKMETER MS2205
Figure 5.1: AC Voltage Measurement Setup
  1. According to the connection mode shown in the table below, switch the function knob to V~. Select the corresponding sockets (V1, V2, or V3 terminal) and insert the test wire.
  2. Connect the two test probes (V1, V2) to the power source or load to be tested. The meter will automatically test and display the result, with the current harmonics percentage shown on the bottom line.
  3. Under voltage test mode, press the SET button to show "Auto V" and "Auto A" on the LCD. Use the ▲ / ▼ buttons to select a proper voltage range, then press SET to confirm.
  4. Press the MODE button to display harmonics percentage on the LCD. The total harmonic distortion ratio F and R will be cyclically displayed. Use the ▲ / ▼ buttons to display the value of each harmonic measurement.
  5. If the input voltage is greater than 50 V, the "⚡" sign will be shown on the LCD, indicating a high voltage hazard.
Switch Inputting terminal V1 Inputting terminal V2 Inputting terminal V3 Test object
V~V1 socketCOM/V2 socketN/A1-phase
V1 socketCOM/V2 socketN/A2-phase
V1 socketCOM/V2 socketV3 socket3-phase

5.5 AC Current (A) Measurement

Diagram showing AC current measurement setup with PEAKMETER MS2205
Figure 5.2: AC Current Measurement Setup (Illustrative)
  1. Switch the function knob to the A~ position.
  2. Pull the trigger to open the clamp, then clip it around the wire to be tested. The measured current value will automatically be shown on the LCD.
  3. Press the MODE button to display harmonics percentage on the LCD. The total harmonic distortion ratio F and r will be cyclically displayed.
  4. Use the ▲ / ▼ buttons to display the value of each harmonic measurement.
  5. If the current of the wire being tested is greater than 1000 A (RMS), "OL" (Overload) symbol will be displayed instead of the current value.

Note on Frequency Test:

  • You can select 50/60-Hz FIXED or AUTO frequency test. When the input waveform fluctuates, displayed harmonic values can be kept stable if 50/60-Hz FIXED mode is selected.
  • Under AUTO frequency test mode, FFT calculation is performed only when the base-wave frequency is between 45 and 65 Hz. Harmonic analysis is not performed if the base-wave frequency exceeds this range.

5.6 Single-Phase Circuit Measurement

Wiring diagram for single-phase circuit measurement with PEAKMETER MS2205
Figure 5.3: Single-Phase Circuit Measurement Setup
  1. Clip the clamp on the test wire of the power supply or load. If measuring a specific phase of a 3-phase circuit, the clamp should be on the wire of that same phase.
  2. Switch the function knob to the KW position. Select corresponding input sockets from V1 or V2 terminal and insert the test wire.
  3. After correct connection, the meter will measure and display single-phase power (active power, power factor, apparent power, passive power, voltage, current, phase angle, peak value of voltage and current, and frequency).
  4. The meter will automatically measure and display active power. The voltage/current value of the load will be displayed on the bottom line of the LCD. Press MODE to display the Var value of passive power. Press WATT to display apparent power.
  5. Power factor (cos Φ): A negative power factor indicates a load with capacitive characteristics.
  6. The maximum measurement range for active power (kW) is 600 kW. If this range is exceeded, "OL" will be displayed. If the voltage is greater than 600 V or current greater than 1000 A, "OL" will also be displayed.
  7. Minimum input voltage is 50 V and minimum input current is 2A. If active power is below this limit, "0.00 kW" will be displayed.
  8. Press I to display current value, current peak value, and frequency.
  9. Press U to display voltage value, voltage peak value, and frequency.
  10. Press REC/SAVE to show MAX and MIN values.
  11. Passive power (kVAr) is not directly measured but calculated by software based on measured voltage, current, and active power.

5.7 CosΦ, SinΦ, and Phase Angle Measurement

  1. Switch the function knob to Φ (1 phase) position. Insert the test wire into V1/V2 input terminals.
  2. The meter will automatically measure and display power factor, voltage value, and current value.
  3. Press WATT to display phase angle, power factor (cos Φ), and sinΦ. A negative power factor indicates a load with capacitive characteristics.
  4. Press I to display current value, current peak value, and frequency.
  5. Press U to display voltage value, voltage peak value, and frequency.
  6. Press REC/SAVE to show MAX and MIN values.
  7. Press SET to display AUTO, then use ▲ / ▼ to set the measurement range for voltage and current, then press SET to return.
  8. After measuring, press HOLD to keep showing the data on the LCD. Press REC/SAVE to display the saved serial number, then press SET to confirm and return.
  9. When the power factor approaches 1, it is normal for LAG (lag) and LEAD (lead) to switch back and forth.
  10. Note: When measuring current < 6A and voltage < 50V, setting a fixed frequency measurement can improve accuracy.

5.8 Single-Phase Three-Line Circuit Measurement

Wiring diagram for single-phase three-line circuit measurement with PEAKMETER MS2205
Figure 5.4: Single-Phase Three-Line Circuit Measurement Setup

The process for measuring power and power factor for a single-phase three-line circuit is similar to a single-phase two-line circuit. Connect the black clip to the middle wire, and simultaneously connect the red clip and clamp-type sensor to all test wires.

5.9 Three-Phase Load Measurement (Balanced Load)

Wiring diagram for 3-phase 3-line circuit measurement with PEAKMETER MS2205
Figure 5.5: Measurement of Power and Power Factor of 3-Phase 3-Line Circuit
  1. For a balanced load, the process for measuring power and power factor of a 3-phase 4-line circuit is the same as for a 3-phase 3-line circuit; the middle line is not needed.
  2. Three-phase total power parameters include total active power, total passive power, total apparent power, and total power factor. The meter cannot perform 3-phase energy measurement.
  3. Switch the function knob to KW/Φ (3 phase) position. Connect the test clamp to phase-1 test wire of the load. Connect V1 terminal (yellow test probe), V2 terminal (black test probe), and V3 terminal (green test probe) to the live lines of phase 1, phase 2, and phase 3, respectively, of the 3-phase load, without connecting the neutral line.
  4. After proper connection, the meter will automatically measure and display power, voltage, current, and indicate if a phase is missing.
  5. Press MODE to display the Var value of passive power on the LCD.
  6. Press WATT to display apparent power, power factor (cos Φ), and sinΦ. A negative power factor indicates a load with capacitive characteristics.
  7. Press I to display current value, current peak value, and frequency.
  8. Press U to display voltage value, voltage peak value, and frequency.
  9. Press SET to display AUTO, then use ▲ / ▼ to set the measurement range for voltage and current, then press SET to return.
  10. After measuring, press HOLD to keep showing the data on the LCD. Press REC/SAVE to display the saved serial number, then press SET to confirm and return.

Alternative 3-Phase 3-Line Measurement Mode:

Alternative wiring diagram for 3-phase 3-line circuit measurement with PEAKMETER MS2205
Figure 5.6: Another Mode for Measuring Power of 3-Phase 3-Line Circuit

Note: Rotate the gear to single-phase measurement mode, and the V1 measurement line and current clamp must be measuring the same phase. Otherwise, an incorrect reading will be obtained.

5.10 Three-Phase Load Measurement (Imbalanced Load)

Wiring diagram for 3-phase 4-line circuit measurement with PEAKMETER MS2205
Figure 5.7: Measurement of Power and Power Factor of 3-Phase 4-Line Circuit

For an imbalanced load, the measuring process is similar to a 1-phase 2-line system, with the measuring mode set to 1-phase mode. Connect the black clip to the middle line, and then simultaneously connect the yellow clip and clamp sensor to corresponding wires. In this mode, the power and power factor of each line can be tested. To test phase sequence, connect voltage clips to the three lines one by one, with the middle line not connected.

Note: The V1 measurement line and current clamp must be measuring the same phase. Otherwise, an incorrect reading will be obtained.

5.11 Phase Sequence Test

  1. The meter will automatically test the phase sequence.
  2. The display of RST signifies a normal phase sequence.
  3. The display of RST with an arrow pointing left signifies a reversed phase sequence.
  4. The display of RST with a crossed-out arrow signifies a missing phase.
  5. During measurement, press REC/SAVE to show MAX and MIN values and record the results. Then, press REC/SAVE again to transfer the test result to a PC through the infrared communication wire.

5.12 Test Data Storage and Retrieval

The meter can store up to 100 groups of data.

Storing Data:

  1. When the meter is in HOLD mode, press REC/SAVE to display the serial number for saving.
  2. Use the ▲ / ▼ buttons to select the desired serial number, then press SET to confirm saving.
  3. To quit saving before confirming, press REC/SAVE again, and the data will not be saved.

Retrieving Saved Data:

  1. When data is saved, switch the function knob to the READ SAVED DATA position.
  2. Switch the function knob to the SEARCH position and press HOLD to display "HOLD".
  3. Press READ to show the saved serial number and data on the LCD.
  4. To check previous or subsequent records or harmonic levels, use the ▲ / ▼ buttons.
  5. When harmonic level data is displayed, press WATT to select the record number.

Clearing Data:

  1. Under data-reading mode, press CLEAR. "CLR" will be displayed.
  2. Press SET to confirm, and the data will be deleted.
  3. To cancel deletion, press CLEAR again before pressing SET.

5.13 RS232C Data Interface

PEAKMETER MS2205 Clamp Power Meter showing RS232 Communication Input Port
Figure 5.8: RS232C Communication Input Port
RS232C communication cable for connecting the meter to a PC
Figure 5.9: RS232C Communication Cable
Diagram showing RS232C connection between meter and PC
Figure 5.10: RS232C Connection Diagram (Illustrative)
  1. Insert the RS232C interface wire into the socket on the meter and rotate it clockwise to lock. Connect the standard RS232C plug on the other end to your PC's COM port. This enables real-time data transfer via the infrared communication interface.
  2. To unplug, rotate the interface-wire plug counter-clockwise in the meter, then pull it out.
  3. Pressing the RS232 button allows real-time recording of measured data under WINDOWS.
  4. If you press HOLD, then READ, and then RS232, saved data can be uploaded to the PC.
  5. The provided software can be used for managing real-time data records, plotting, and printing outputs.

5.14 Backlight Display

Press the ☀ button to turn the backlight on or off. The backlight will automatically turn off after approximately 20 seconds.

5.15 Auto Power Off

  1. If there is no function change or button press for 10 minutes, the meter will automatically power off. When this occurs, ensure the knob is set to "OFF" before turning the meter on again after 5 seconds.
  2. To disable auto power off, hold down the SET & CLEAR buttons while turning the meter on.
  3. The auto power off function is also disabled when the meter is in MAX/MIN Record mode or communicating with PC software.

6. Maintenance

6.1 Battery Replacement

Refer to section 4.1 for detailed instructions on battery replacement. Always ensure the meter is off and disconnected from any circuits before opening the battery compartment.

6.2 Cleaning

Wipe the meter with a dry, soft cloth. Do not use abrasives or solvents. Keep the clamp jaws clean and free of debris.

6.3 Storage

If the meter is not used for an extended period, remove the batteries to prevent leakage. Store the meter in a cool, dry place, away from direct sunlight and extreme temperatures.

7. Troubleshooting

  • "OL" Display: Indicates an overload condition. This occurs if the measured voltage exceeds 600 V (RMS) or current exceeds 1000 A (RMS), or if active power exceeds 600 kW. Reduce the input or use a meter with a higher range.
  • "0.00 kW" Display: May appear if the active power value is below the minimum test limits (min. input voltage 50 V, min. input current 2A).
  • Inaccurate Readings:
    • Ensure test probes are correctly connected to the appropriate terminals (V1, COM/V2, V3) and the clamp is properly closed around the conductor.
    • For 3-phase 3-line measurement, ensure the V1 measurement line and current clamp are measuring the same phase.
    • When measuring current < 6A and voltage < 50V, setting a fixed frequency (50Hz or 60Hz) instead of AUTO can improve accuracy.
    • Check battery level; low battery can affect measurement accuracy.
  • Meter Not Powering On: Check battery installation and charge. Ensure the function knob is not stuck between positions.
  • No Data Transfer via RS232C:
    • Ensure the RS232C cable is securely connected to both the meter and the PC's COM port.
    • Verify the cable is locked into the meter's socket.
    • Ensure the correct software is installed and running on the PC.

8. Specifications

8.1 General Specifications

  • Safety Standard: Complies with IEC/EN 61010-1 1000V CAT II, 600V CAT III
  • Max. Common-Mode Voltage: 600V AC RMS
  • Display: LCD display; Max. reading: 6000 counts
  • Range Selection: Fully automatic range selection
  • Frequency Detection: Automatic (manual setting recommended for serious harmonics for stability)
  • Over-range Display: "OL"
  • Data Holding: "HOLD" is shown on LCD
  • Power Supply: 4 x 1.5 V AA batteries
  • Power Consumption: 250 mW
  • Storage Temperature: -20℃ ~ 70℃
  • Operating Temperature: 0℃ ~ 40℃
  • Temperature Coefficient: 0.05 × (specified accuracy) per ℃
  • Electromagnetic Compatibility: Accuracy specified in an RF field of 3V/M; otherwise, accuracy is unspecified.
  • Operating Altitude: 2000m CAT III 600V; 3000m CAT II 600V
  • Store Altitude: 12000m
  • Dimensions: 300mm × 103mm × 51mm
  • Weight: Approximately 500 g (with battery)

8.2 Technical Specifications

Accuracy: ±(% read + graduation #) at ambient temperature: 18℃ ~ 28℃, Humidity 80%, frequency for voltage, current: 45 Hz ~ 65 Hz

AC Voltage (RMS)

Range Accuracy Resolution Input Impedance
80V±(1.0%+5)0.1V1 MΩ // 10 pF
180V±(1.0%+5)0.1V
400V±(1.0%+5)1V
600V±(1.0%+5)1V

Max. allowed overload voltage: 750 V (RMS)

AC Current (RMS)

Range Accuracy Resolution
20A±(2%+5)0.01A
40A±(2%+5)0.01A
100A±(2%+5)0.1A
200A±(2%+5)0.1A
450A±(2%+5)1A
1000A±(2%+5)1A

Max. allowed overload current: 1200 A

Single-Phase Active Power (W)

Range Accuracy Resolution
30kW±(3%+5)0.01kW
60kW±(3%+5)0.01kW
120kW±(3%+5)0.1kW
150kW±(3%+5)0.1kW
300kW±(3%+5)0.1kW
600kW±(3%+5)0.1kW

Min. test current: 2A; Min. test voltage: 50V

Three-Phase Active Power (W)

Range Accuracy Resolution
3kW±(3%+5)0.001kW
12kW±(3%+5)0.01kW
30kW±(3%+5)0.01kW
120kW±(3%+5)0.1kW
150kW±(3%+5)0.1kW
600kW±(3%+5)0.1kW

Power Factor

Range Accuracy Resolution
0.3~1 Capacitive±(0.02+2)0.001
0.3~1 Inductive±(0.02+2)0.001

Min. test current: 2A; Min. test voltage: 50V

Apparent Power

Range Precision Resolution
3kVA±(3%+5)0.001kVA
12kVA±(3%+5)0.01kVA
30kVA±(3%+5)0.01kVA
120kVA±(3%+5)0.1kVA
150kVA±(3%+5)0.1kVA
600kVA±(3%+5)0.1kVA

Min. input current: 2A; Min. input voltage: 50V. Apparent power (VA) is calculated based on measured V, A, and kW values.

Passive Power

Range Precision Resolution
3kVAr±(3%+5)0.001kVAr
12kVAr±(3%+5)0.01kVAr
30kVAr±(3%+5)0.01kVAr
120kVAr±(3%+5)0.1kVAr
150kVAr±(3%+5)0.1kVAr
600kVAr±(3%+5)0.1kVAr

Min. input current: 2A; Min. input voltage: 50V. Passive power (VAr) is calculated based on measured V, A, and kW values.

Frequency (Hz)

Range Accuracy Resolution
30Hz~1kHz0.5%+1 graduation0.1Hz

Min. test voltage: 50 V

Harmonic Test

Harmonic Number Precision of Harmonic Voltage
1±(3.0%+10)
2-6±(3.5%+10)
7-8±(4.5%+10)
9-10±(5.0%+10)
11-15±(7%+10)
16-20±(10%+10)

Min. test voltage 50V; Min test current 2A

9. User Tips

  • For stable harmonic readings, especially with fluctuating waveforms, consider using the 50/60-Hz FIXED frequency mode instead of AUTO.
  • Always double-check probe connections and ensure the clamp is fully closed for accurate current measurements.
  • When measuring 3-phase circuits, pay close attention to which phase the V1 line and current clamp are connected to, as mismatch can lead to incorrect results.
  • Regularly check the battery indicator and replace batteries promptly to maintain measurement accuracy.
  • Utilize the data storage feature (REC/SAVE) to log measurements over time for analysis, especially when monitoring system performance or troubleshooting intermittent issues.
  • The RS232C interface and accompanying software can greatly enhance data analysis and reporting capabilities for professional use.

10. Warranty and Support

10.1 Quality Assurance and Warranty

This product comes with a warranty period of one year starting from the purchase date. The manufacturer ensures the product has passed strict quality tests.

In case of any product quality problem occurring during the warranty period, please fill in the warranty card and return it with the product. The service department will repair or replace it free of charge. Users should not attempt to disassemble the meter.

Repairs outside the warranty period will be charged.

10.2 Exclusions from Free Service

Free service does not apply to the following cases:

  • Problems and damages due to improper use or use under environmental conditions not stipulated for this product, including overloading.
  • Problems and damages due to unauthorized dismantling, refitting, or misuse.
  • Problems and damages due to user-induced reasons.
  • Problems and damages due to natural disasters.

For further support or inquiries, please refer to the official product documentation or contact the seller.

A detailed user manual in PDF format is available for download: User Manual (PDF)

11. Accessories

Contents of the PEAKMETER MS2205 package including meter, probes, cables, software CD, and carrying bag
Figure 11.1: Package Contents
Item Quantity
Instruction Manual1
1.5V AA Battery4
Test probe1 set
Test clip3
Interface cable (RS232C)1
PC Software CD1
Package box / Carrying Bag1