TOMZN TOQ7 Series Dual Power Automatic Transfer Switch User Manual

Model: TOQ7 | Brand: TOMZN

1. Safety Information

⚠Warning: To avoid danger of suffocation, keep this bag away from babies and children. Do not use this bag in cribs, beds, carriages, or play pens. This bag is not a toy.

This device operates with high voltage (above 50Vac or 75Vdc). Installation and maintenance should only be performed by qualified electrical professionals. Always disconnect power before working on the device.

The product is certified with CE standards, indicating compliance with EU safety, health, and environmental protection requirements.

Applicable Regulations and Harmonized Standards:

  • Low Voltage Directive 2014/35/EU
  • Electromagnetic compatibility Directive 2014/30/EU
  • Restriction of the use of certain hazardous substances (RoHS) Directive 2011/65/EU

2. Product Overview

The TOMZN TOQ7 series Dual Power Automatic Transfer Switch (ATS) is a miniature household power switch designed to automatically switch between a main power supply and a standby power supply. This ensures continuous, reliable, and safe power supply, especially in situations where power failure cannot be tolerated.

It is specifically designed for household rail installation and is suitable for PZ30 distribution boxes.

2.1 Function Overview

When the main power supply is interrupted, the ATS automatically switches to the backup power supply. Upon restoration of the main power supply, the device switches back to the main supply.

2.2 Key Features

  • Control Device: Built-in controller.
  • Product Structure: No power off during switching, guide rail type, high current capacity, small volume, two-stage type, simple structure, ATS integration.
  • Performance: Fast switching speed, low failure rate, convenient maintenance, and reliable performance.
  • Wiring Mode: Front plate wiring.
  • Conversion Modes: Supports power grid to power grid, power grid to generator, and photovoltaic to urban power, with automatic switching and self-recovery functions.
  • Pole Numbers: Available in 2, 3, and 4 poles.
  • Switching Time: 0.008s / 8ms.
TOMZN ATS Product Family Overview
Figure 2.1: TOMZN TOQ7 Series ATS Product Family Overview.
Safe arc extinguishing chamber design
Figure 2.2: Safe arc extinguishing chamber design for safer product switching.
Manual and Automatic mode switch
Figure 2.3: The switch features both manual and automatic modes, with a durable chain structure.
Isolation plates for input and output
Figure 2.4: Isolation plates are used for input and output terminals to enhance security.
Automatic switching after power off in less than 50ms
Figure 2.5: Automatic switching after power off, realizing uninterrupted power in less than 50ms.
Safety shield to prevent accidental contact
Figure 2.6: Safety shield to prevent accidental contact, enhancing operational safety.

2.3 Model and Meaning

The model designation TOQ7 provides information about the product's characteristics:

  • TOQ7: Base model series.
  • First blank: Indicates special features, e.g., 'e' for Photovoltaic special (PV).
  • Second blank: Denotes the current grade (e.g., 63A, 100A, 125A).
  • Third blank: Specifies the type, e.g., 'Mini track type'.
  • Fourth blank: Represents the Enterprise code.

3. Specifications

3.1 Main Technical Parameters

ParameterValue
Specification125A
Rated current Ie(A)16, 20, 25, 32, 40, 50, 63, 80, 100, 125
Insulation voltage UiAC690V, 50/60Hz
Rated voltage UeAC400V, 50/60Hz
ClassificationPC class: can be manufactured and withstood without short circuit current
Utilization categoryAC-33iB, AC-31B
Pole No.2P, 3P, 4P
Weight (kg)1.7 (2P), 2.1 (3P), 2.6 (4P)
Electrical Life2000 times; Manual operation: 5000 times
Rated short circuit current Iq50kA
Short circuit protection device (fuse)RT16-00-63A
Rated impulse withstand voltage8kV
Control circuitRated control voltage Us: AC220V 50/60Hz; Normal working conditions: 85-110%Us
Auxiliary circuit2 relays, each with two sets of contact converter contact capacity: AC220V/50Hz Ie=5y
Conversion time of contactor<50ms
Operation conversion time<50ms
Return conversion time<50ms
Power off time<50ms

4. Normal Operation and Installation Conditions

4.1 Ambient Air Temperature

  • Maximum temperature shall not exceed 40°C.
  • Minimum temperature shall not be lower than -5°C.
  • Average temperature within 24 hours shall not be higher than 35°C.

4.2 Altitude

  • The altitude of the installation site should not be higher than 2000m.

4.3 Atmospheric Conditions

  • When the maximum temperature reaches 40°C, the relative humidity of the installation site should not exceed 50%.
  • When the temperature is the minimum temperature -5°C, the relative humidity can be higher (e.g., at 25°C, relative humidity can be 90%).
  • Special measures should be taken to deal with occasional condensation on the product surface due to temperature changes.

4.4 Pollution Grade

  • The pollution grade of ATS conforms to grade 3 specified in IEC/EN60947-6-1 and GB/T14048.11.

4.5 Installation Category

  • The installation type of ATS conforms to the category specified in IEC/EN60947-6-1 and GB/T14048.11.

4.6 Installation Conditions

  • ATS can be installed vertically in a control cabinet or distribution cabinet.
  • Ensure the installation distance meets the requirements shown in Figure 5.9.

5. Setup and Wiring

5.1 General Instructions for Use

  1. After receiving the product, please have an electrical professional perform the operation.
  2. Connect the equipment in accordance with the wiring diagram specifications provided in this manual.
  3. According to the instructions, adjust the equipment parameters as needed.

5.2 Wiring Diagrams

The following diagrams illustrate various wiring configurations for the TOMZN TOQ7 ATS. Always refer to the specific diagram relevant to your model and application.

Internal wiring diagram for TOMZN TOQ7 ATS
Figure 5.1: Internal Wiring Diagram. K1: manual/automatic selector switch; K2, K3: internal valve position switch; J1: common 220V A power relay; J2: standby 220V B power relay; 1: passive signal output of A power supply; 2: passive signal output of B power supply.
Controller wiring diagram for TOMZN TOQ7 ATS
Figure 5.2: Controller Wiring Diagram. Shows common incoming line, common control line, standby power indicator, standby incoming line, standby control line, and load output.
125/2P wiring diagram for TOMZN TOQ7 ATS
Figure 5.3: 125/2P Wiring Diagram. Illustrates connections for 2-pole configuration with common and standby power inputs and load output.
125/3P wiring diagram for TOMZN TOQ7 ATS
Figure 5.4: 125/3P Wiring Diagram. Shows connections for 3-pole configuration, including common zero line input.
125/4P wiring diagram for TOMZN TOQ7 ATS
Figure 5.5: 125/4P Wiring Diagram. Details connections for 4-pole configuration.
125/3P wiring diagram with timer for TOMZN TOQ7 ATS
Figure 5.6: 125/3P Wiring Diagram with Timer. Shows integration with an external programmable timer switch (AHC3DA).
Special connection mode for photovoltaic inverter with TOMZN TOQ7 ATS
Figure 5.7: Special Connection Mode for Photovoltaic Inverter. Illustrates how to connect the ATS with a PV power station and inverter.

5.3 Installation Dimensions

Overall and installation dimensions of TOMZN TOQ7 ATS
Figure 5.8: Overall and Installation Dimensions (mm). Safe distance S1: ≥30mm, S2: ≥203mm. Key components: ① Main power terminal and passive signal (AC220V), ② Manual/automatic switch, ③ Manual handle, ④ Main terminal of common power side, ⑤ Main terminal of standby power side, ⑥ Main terminal of load connection side, ⑦ A power indicator, ⑧ B power indicator, ⑨ Standby power terminal and passive signal (AC220V).
Correct installation direction of TOMZN TOQ7 ATS
Figure 5.9: Correct Installation Direction of 125. Ensure the trademark is visible in front of the product. The safe distances S1, S2 should not be lower than the labels in Fig. 5.8.

5.4 Wiring Precautions

  • Ensure that professionals read this manual before installation and wiring.
  • Check the integrity of the ATS before installation. Operate the ATS with the handle to check the flexibility of the transmission device and detect load generation and disconnection conditions for both common and standby power supplies at each stage.
  • The detection control voltage is 50/60Hz, AC220V. The coil in the control circuit should not be too long.
  • The cross-sectional area of copper wire for the control circuit should not be greater than 2.0mm².
  • According to the installation requirements of the power distribution system, appropriate circuit breakers must be provided to ensure the safety of personnel and equipment.

6. Operating Modes

6.1 Manual/Automatic Operation

The ATS can guarantee power generation and power failure performance during circuit operation in automatic mode. However, for manual operation, this performance cannot be guaranteed due to variations in power generation and power failure speed or operator action. Excessive silver alloy loss may occur during manual power generation and power failure.

Therefore, when all power supplies are cut off for checking and maintaining the operating system and contacts, it is only necessary to pull the selector switch to the manual position. Under normal circumstances, always keep the selector switch in the automatic position.

When operating manually, pull the selector switch to the manual position. After manual operation is completed, return the selector switch from the manual position to the automatic position.

6.2 Control Circuit

The ATS instantly becomes active upon power detection. After the conversion is completed, the coil in the control circuit will be disconnected by the internal converter. Under the rated voltage of 80%-110%, the coil can operate normally. Low voltage will cause coil heating and even spontaneous combustion.

Video 6.1: Product demonstration video showing the operation and features of the TOMZN ATS.

7. Maintenance, Inspection, and Storage

7.1 General Maintenance Guidelines

  • Maintenance and inspection shall be operated by qualified professionals only.
  • All power supplies must be cut off in advance before any maintenance work.

7.2 Maintenance Frequency

  • To ensure optimal performance, the first maintenance and inspection should be carried out within 6 months after initial use.
  • Thereafter, the device should be maintained and inspected at least once a year.
  • In harsh installation conditions (e.g., dusty, humid environments), the frequency of maintenance and inspection should be increased.

7.3 Maintenance and Inspection Items

  1. Remove any dust and dirt from the device.
  2. Check whether the contact parts of the electrical contacts are deformed or damaged. Remove any burnt metal particles attached to and around the surface.
  3. Inspect for rust, acidification, or dust on the contact surface, which can lead to poor contact. If necessary, operate the device manually multiple times and measure the contact resistance.
  4. If the ATS has been exposed to long-term moisture or suspension, dry it thoroughly before use. After removing dust and dirt, use a 500V megohmmeter to measure the insulation resistance between the normal supply, alternating power supply, load side bar, live parts, and metal plate. The insulation resistance should not be less than 10MΩ.

7.4 Storage

  • The ATS should be stored in an environment equivalent to normal working conditions.
  • Ensure dust-proof, moisture-proof, and collision-proof measures are in place during storage.

8. Troubleshooting

This section provides guidance on common issues you might encounter with your ATS.

8.1 Common Issues and Solutions

  • Device not switching automatically:
    • Ensure the selector switch is in the 'Auto' position.
    • Check both main and standby power supplies for voltage presence.
    • Verify control circuit wiring and connections.
  • Coil heating or spontaneous combustion:
    • This can occur due to low voltage in the control circuit. Ensure the control voltage is within the rated 80%-110% Us range (AC220V 50/60Hz).
    • Check for proper wire gauge in the control circuit; cross-sectional area should not exceed 2.0mm².
  • Poor contact or intermittent operation:
    • Perform maintenance as described in Section 7.3, focusing on cleaning contacts and checking for deformation or damage.
    • Measure contact resistance if issues persist.
  • Loud clicking noise during switching:
    • This is a normal characteristic of the mechanical switching mechanism.

9. User Tips

  • The ATS switches clearly and offers both manual and automatic modes for flexibility.
  • Terminals are designed for convenience, and DIN-rail mounting is straightforward.
  • When correctly connected and under appropriate load, the device operates stably, and contacts do not overheat.
  • Mechanical parts inside the unit are typically lubricated from the factory.
  • For wiring, note that for some configurations, the lower contacts for Standby and Load may need to be connected before the upper ones. Plan your wiring carefully, especially in existing installations, to ensure ease of connection.

10. Frequently Asked Questions

Q: Can I ask a general question about these ATS switches?
A: Yes, this manual aims to provide comprehensive information. If you have specific questions not covered, please refer to the support contact information.

11. Warranty and Support

For technical support, service, or inquiries, please contact TOMZN ELECTRIC CO.,LTD. directly.

  • Address: No.11, Xinhe Road, Huabei, Liushi Town, Yueqing City, Zhejiang Province, China
  • Service Hotline: 4006-020-158
  • Website: http://www.tomzn.com

The product is manufactured in China.

© 2024 TOMZN ELECTRIC CO.,LTD. All rights reserved.