ELECTESLA D12

Contents

ELECTESLA D12 Series Variable Frequency Drive Inverter User Manual

Models: 0.75KW, 1.5KW, 2.2KW

1. Introduction

The ELECTESLA D12 Series Variable Frequency Drive (VFD) is designed to control the speed of AC motors, offering precise control and energy efficiency. This inverter is suitable for various applications, including water pumps, compressors, and fans. This manual provides essential information for the safe and effective installation, operation, and maintenance of your D12 VFD.

Three ELECTESLA D12 VFD units of different sizes, showing the front panel with display and controls.

Figure 1: ELECTESLA D12 Series VFD units

2. Safety Information

WARNING: Read the user manual before operation. Risk of electrical shock. Wait 10 minutes after removing power before servicing.

  • Ensure all wiring is performed by qualified personnel in accordance with local and national electrical codes.
  • Always disconnect power before performing any installation, maintenance, or inspection.
  • Do not touch electrical components immediately after power-off; residual voltage may be present.
  • Ensure proper grounding of the VFD and motor.
  • Do not operate the VFD with damaged cables or if the enclosure is open.
  • Protect the VFD from moisture, dust, corrosive gases, and direct sunlight.

3. Specifications

3.1. General Specifications

Attribute Value
Brand NameELECTESLA
Model NumberES-D12
TypeDC/AC Inverters
Output TypeSINGLE
Output Frequency0-999HZ
Output Current2.5-10A (varies by model)
Output Power0.75-2.2KW
Input Voltage1-phase 220V VFD
Output Voltage3-phase 380V VFD
Size143*116*85mm (varies by model)
Weight1.5kgs (approx.)
CertificationCE, FCC, RoHS
OriginMainland China
Protection LevelIP20
Cooling MethodAir cooling with fan control
Installation MethodWall-hanging type, Cabinet type

3.2. Model-Specific Power and Current

Four VFD units of varying power ratings with a table showing power and output current for 3-phase 380V and single-phase 220V inputs.

Figure 2: D12 Series Models and Output Specifications

Model Power (KW) Output Current (A)
Three-phase 380V input, Three-phase 380V output
D12-T3-0R7G0.753
D12-T3-1R5G1.54
D12-T3-2R2G2.25
Single-phase 220V input, Three-phase 220V output
D12-S2-0R4G0.42.5
D12-S2-0R7G0.755
D12-S2-1R5G1.57
D12-S2-2R2G2.210

3.3. Dimensions

Voltage Power (KW) Output Current (A) W (MM) H (MM) D (MM) D1 (MM) Installation Hole Diameter (MM)
1-phase 110V Input
1-phase 110V0.45851431161264.5
1-phase 110V0.7510100151120130
1-phase 110V1.514100151120130
1-phase/3-phase 220V Input
1-phase/3-phase 220V0.42.5851431161264.5
1-phase/3-phase 220V0.75585143116126
1-phase/3-phase 220V1.57100151120130
1-phase/3-phase 220V2.2101001511201304.5
3-phase 380V Input
3-phase 380V0.7531001511201304.5
3-phase 380V1.54100151120130
3-phase 380V2.25100151120130
3-phase 380V3.78.5113209188198
3-phase 380V5.5131132091881984.5
3-phase 380V7.5171132091881984.5

4. Setup

4.1. Mounting

The D12 VFD can be mounted as a wall-hanging unit or installed within a cabinet. Ensure adequate ventilation for air cooling and maintain proper clearance around the unit to prevent overheating.

4.2. Wiring Instructions

Refer to the wiring diagrams and terminal descriptions below for correct electrical connections. Improper wiring can lead to equipment damage or personal injury.

Wiring diagrams for 220V (single-phase input) and 380V (three-phase input) VFDs connected to a motor and a circuit breaker.

Figure 3: Main Circuit Wiring Diagram (220V and 380V)

4.2.1. Main Circuit Terminals

Code of Terminal Terminal Function
R, S/L1, T/L2Power input for main circuitR/S/T 3-phase AC power input terminal (380V, 50Hz/60Hz). L1/L2 for 220V model connect terminals.
U, V, WOutput of frequency inverterTerminal for connection to motor.
P, PBConnection of braking resistorTerminal for connection to braking resistor (optional).
Grounding symbolGroundingTerminal for grounding. For 400V level, grounding resistance should be 4Ω or below.

4.2.2. Control Circuit Terminals

Two VFD units with their terminal covers removed, showing the internal wiring terminals and a table describing control circuit terminal functions.

Figure 4: Control Circuit Terminals

Code of Terminal Terminal Function
GNDPublic terminal of the control circuit.
10V10V output voltageCommonly used as working voltage of the external potentiometer. Maximum current: 10mA.
12V12V output voltageCommonly used as working voltage of the logic input terminal. Maximum current: 10mA.
AVIVoltage Analog input or Current Analog inputAnalog voltage input: 0~+10 V. Analog current input: 0/4~20mA. Set according to parameter F2.00~F2.03.
X1Digital input X1Set according to parameter F2.13, default is FWD.
X2Digital input X2Set according to parameter F2.14, default is REV.
X3Digital input X3Set according to parameter F2.15, default is IDLE.
X4Digital input X4Set according to parameter F2.16, default is IDLE.
X5Digital input X5Set according to parameter F2.17, default is Pulse Frequency Input.
TA-TB-TCRelay outputSet according to parameter F2.20. Contact rating: AC 250V/5A, DC 24V/2.5A.
Y1Open-collector outputDefault running indication.
AOAnalog outputAnalog voltage output: 0~+10 V. Analog current output: 0/4~20mA. Set according to parameter F2.10~F2.12.

5. Operating Instructions

5.1. Control Panel Overview

The VFD features a user-friendly control panel for monitoring and adjusting parameters.

Close-up of a single VFD unit's front panel, detailing the function of each button and display element.

Figure 5: Control Panel Functions

  • Display: Shows Current, Voltage, and Frequency (Hz).
  • Speed Control Knob: Adjusts the output frequency/motor speed.
  • PRG (Programming Key): Enters/exits parameter programming mode.
  • MF (Multi-function Key): Used for various functions depending on context.
  • Arrow Keys (Up/Down/Left/Right): Navigate menus and adjust parameter values.
  • ENTER Key: Confirms selections and parameter changes.
  • RUN Key: Starts the motor.
  • STOP/RESET Key: Stops the motor or resets fault alarms.

5.2. Basic Operation

  1. Power On: Ensure all wiring is correct and secure. Apply power to the VFD. The display will light up.
  2. Frequency Setting: Use the Speed Control Knob to set the desired output frequency. The display will show the current frequency.
  3. Start Motor: Press the RUN button to start the motor. The motor will accelerate to the set frequency.
  4. Stop Motor: Press the STOP/RESET button to stop the motor. The motor will decelerate and stop.

5.3. Parameter Setting (P0 Group - Basic Operating Parameters)

To access and modify parameters, press the PRG key. Use the arrow keys to navigate and the ENTER key to select and confirm.

Function Code Name Description Range Factory Default
P0.00Power specification of frequency driveDisplay current power.0.10~99.99kwDevice settings
P0.01Software version of the master controllerDisplay current software version number.1.00~99.991.00
P0.02Run command channel selection0: Panel runs the command channel; 1: Terminal runs the command channel; 2: Communication runs command channel.0~20
P0.03Frequency setting selection0: Panel potentiometer; 1: Number given 1, adjust by operating ▲/▼ keys; 3: AVI simulation given (0~10V/0~20mA).0~80
P0.04Maximum output frequencyThe highest frequency allowed by the frequency converter.MAX (50.0, [P0.05]) ~ 999.9Hz50.0Hz
P0.05Upper frequencyThe operating frequency cannot exceed this frequency.MAX (0.1, [P0.06]) ~ [P0.04]50.0Hz

5.4. Operation Demonstration Video

Watch this video for a visual guide on operating the VFD and controlling a motor.

Play video
Watch video online

Video: Demonstration of the D12 VFD controlling a motor, showing frequency and current adjustments.

6. Maintenance

  • Regular Cleaning: Keep the VFD clean and free from dust and debris. Use a soft, dry cloth. Do not use liquid cleaners.
  • Fan Inspection: Periodically check the cooling fan for proper operation and ensure air vents are not obstructed. Clean fan blades if necessary.
  • Terminal Tightness: Annually check all wiring terminals for tightness to prevent loose connections, which can cause overheating or malfunction.
  • Environmental Check: Ensure the operating environment remains within specified temperature and humidity ranges.
  • Capacitor Life: Electrolytic capacitors have a finite lifespan. Consider professional inspection or replacement after several years of continuous operation.

7. Troubleshooting

This section provides common fault codes and suggested countermeasures. For detailed troubleshooting, refer to the full PDF manual.

Fault Code Name Possible Cause Countermeasures
E0C1Overcurrent during accelerationAcceleration time is too short; Inverter power is too small; Improper V/F curve or torque boost.Extend acceleration time; Choose a larger power inverter; Adjust V/F curve or torque boost.
E0C2Overcurrent during decelerationDeceleration time is too short; Inverter power is too small; Grid voltage is low.Extend deceleration time; Choose a larger power inverter; Check input power.
EHU1Overvoltage during accelerationAbnormal input voltage; Rotating motor not restarted.Check input power; Set to start after DC braking.
E-OHRadiator overheatingAmbient temperature is too high; Fan damage; Air duct blocked.Reduce ambient temperature; Replace the fan; Dredge the air duct.
E-LTPhotovoltaic water pump water shortage faultSensor disconnected or poorly connected; System has no feedback.Check sensor installation and wiring.
E485RS485 communication faultRS485 channel interference; Communication timeout.Check communication shielding and wiring; Connect filter capacitor in parallel; Retry.

8. User Tips

  • For optimal performance, ensure the VFD's power rating closely matches your motor's requirements.
  • When setting parameters, make small adjustments and observe the motor's response before making further changes.
  • If using an external potentiometer for speed control, ensure it is properly calibrated and connected to the AVI and 10V/GND terminals.
  • Consider using the PID control function for applications requiring precise process control, such as maintaining constant pressure in a water pump system.
  • Always perform a test run after any wiring changes or parameter modifications to confirm correct operation.

9. Warranty and Support

The ELECTESLA D12 Series VFD is certified with CE, FCC, and RoHS, ensuring compliance with international safety and environmental standards.

For technical support, service, or warranty claims, please contact your authorized dealer or ELECTESLA customer service. Please have your product model and serial number ready when contacting support.

A detailed user manual in PDF format is available for download, which includes comprehensive parameter descriptions and advanced settings. You can access it via the following link: ELECTESLA D12 Series Frequency Converter Parameter Description (PDF).

10. Applications

The D12 VFD is versatile and can be used in various industrial and commercial applications to control the speed of AC motors, improving efficiency and control.

Examples of applications for the VFD: water pump, compressor, motor, and fan.

Figure 6: Typical Applications

  • Water Pumps: For constant pressure control and energy saving.
  • Compressors: To optimize air delivery and reduce power consumption.
  • General Motors: For precise speed and torque control in various machinery.
  • Fans: For ventilation systems, allowing variable airflow control.