1. Introduction
The ELECTESLA D12 Series Variable Frequency Drive (VFD) is designed to control the speed of AC motors, offering precise control and energy efficiency. This inverter is suitable for various applications, including water pumps, compressors, and fans. This manual provides essential information for the safe and effective installation, operation, and maintenance of your D12 VFD.
Figure 1: ELECTESLA D12 Series VFD units
2. Safety Information
WARNING: Read the user manual before operation. Risk of electrical shock. Wait 10 minutes after removing power before servicing.
- Ensure all wiring is performed by qualified personnel in accordance with local and national electrical codes.
- Always disconnect power before performing any installation, maintenance, or inspection.
- Do not touch electrical components immediately after power-off; residual voltage may be present.
- Ensure proper grounding of the VFD and motor.
- Do not operate the VFD with damaged cables or if the enclosure is open.
- Protect the VFD from moisture, dust, corrosive gases, and direct sunlight.
3. Specifications
3.1. General Specifications
| Attribute | Value |
|---|---|
| Brand Name | ELECTESLA |
| Model Number | ES-D12 |
| Type | DC/AC Inverters |
| Output Type | SINGLE |
| Output Frequency | 0-999HZ |
| Output Current | 2.5-10A (varies by model) |
| Output Power | 0.75-2.2KW |
| Input Voltage | 1-phase 220V VFD |
| Output Voltage | 3-phase 380V VFD |
| Size | 143*116*85mm (varies by model) |
| Weight | 1.5kgs (approx.) |
| Certification | CE, FCC, RoHS |
| Origin | Mainland China |
| Protection Level | IP20 |
| Cooling Method | Air cooling with fan control |
| Installation Method | Wall-hanging type, Cabinet type |
3.2. Model-Specific Power and Current
Figure 2: D12 Series Models and Output Specifications
| Model | Power (KW) | Output Current (A) |
|---|---|---|
| Three-phase 380V input, Three-phase 380V output | ||
| D12-T3-0R7G | 0.75 | 3 |
| D12-T3-1R5G | 1.5 | 4 |
| D12-T3-2R2G | 2.2 | 5 |
| Single-phase 220V input, Three-phase 220V output | ||
| D12-S2-0R4G | 0.4 | 2.5 |
| D12-S2-0R7G | 0.75 | 5 |
| D12-S2-1R5G | 1.5 | 7 |
| D12-S2-2R2G | 2.2 | 10 |
3.3. Dimensions
| Voltage | Power (KW) | Output Current (A) | W (MM) | H (MM) | D (MM) | D1 (MM) | Installation Hole Diameter (MM) |
|---|---|---|---|---|---|---|---|
| 1-phase 110V Input | |||||||
| 1-phase 110V | 0.4 | 5 | 85 | 143 | 116 | 126 | 4.5 |
| 1-phase 110V | 0.75 | 10 | 100 | 151 | 120 | 130 | |
| 1-phase 110V | 1.5 | 14 | 100 | 151 | 120 | 130 | |
| 1-phase/3-phase 220V Input | |||||||
| 1-phase/3-phase 220V | 0.4 | 2.5 | 85 | 143 | 116 | 126 | 4.5 |
| 1-phase/3-phase 220V | 0.75 | 5 | 85 | 143 | 116 | 126 | |
| 1-phase/3-phase 220V | 1.5 | 7 | 100 | 151 | 120 | 130 | |
| 1-phase/3-phase 220V | 2.2 | 10 | 100 | 151 | 120 | 130 | 4.5 |
| 3-phase 380V Input | |||||||
| 3-phase 380V | 0.75 | 3 | 100 | 151 | 120 | 130 | 4.5 |
| 3-phase 380V | 1.5 | 4 | 100 | 151 | 120 | 130 | |
| 3-phase 380V | 2.2 | 5 | 100 | 151 | 120 | 130 | |
| 3-phase 380V | 3.7 | 8.5 | 113 | 209 | 188 | 198 | |
| 3-phase 380V | 5.5 | 13 | 113 | 209 | 188 | 198 | 4.5 |
| 3-phase 380V | 7.5 | 17 | 113 | 209 | 188 | 198 | 4.5 |
4. Setup
4.1. Mounting
The D12 VFD can be mounted as a wall-hanging unit or installed within a cabinet. Ensure adequate ventilation for air cooling and maintain proper clearance around the unit to prevent overheating.
4.2. Wiring Instructions
Refer to the wiring diagrams and terminal descriptions below for correct electrical connections. Improper wiring can lead to equipment damage or personal injury.
Figure 3: Main Circuit Wiring Diagram (220V and 380V)
4.2.1. Main Circuit Terminals
| Code of Terminal | Terminal | Function |
|---|---|---|
| R, S/L1, T/L2 | Power input for main circuit | R/S/T 3-phase AC power input terminal (380V, 50Hz/60Hz). L1/L2 for 220V model connect terminals. |
| U, V, W | Output of frequency inverter | Terminal for connection to motor. |
| P, PB | Connection of braking resistor | Terminal for connection to braking resistor (optional). |
| Grounding | Terminal for grounding. For 400V level, grounding resistance should be 4Ω or below. |
4.2.2. Control Circuit Terminals
Figure 4: Control Circuit Terminals
| Code of Terminal | Terminal | Function |
|---|---|---|
| GND | Public terminal of the control circuit. | |
| 10V | 10V output voltage | Commonly used as working voltage of the external potentiometer. Maximum current: 10mA. |
| 12V | 12V output voltage | Commonly used as working voltage of the logic input terminal. Maximum current: 10mA. |
| AVI | Voltage Analog input or Current Analog input | Analog voltage input: 0~+10 V. Analog current input: 0/4~20mA. Set according to parameter F2.00~F2.03. |
| X1 | Digital input X1 | Set according to parameter F2.13, default is FWD. |
| X2 | Digital input X2 | Set according to parameter F2.14, default is REV. |
| X3 | Digital input X3 | Set according to parameter F2.15, default is IDLE. |
| X4 | Digital input X4 | Set according to parameter F2.16, default is IDLE. |
| X5 | Digital input X5 | Set according to parameter F2.17, default is Pulse Frequency Input. |
| TA-TB-TC | Relay output | Set according to parameter F2.20. Contact rating: AC 250V/5A, DC 24V/2.5A. |
| Y1 | Open-collector output | Default running indication. |
| AO | Analog output | Analog voltage output: 0~+10 V. Analog current output: 0/4~20mA. Set according to parameter F2.10~F2.12. |
5. Operating Instructions
5.1. Control Panel Overview
The VFD features a user-friendly control panel for monitoring and adjusting parameters.
Figure 5: Control Panel Functions
- Display: Shows Current, Voltage, and Frequency (Hz).
- Speed Control Knob: Adjusts the output frequency/motor speed.
- PRG (Programming Key): Enters/exits parameter programming mode.
- MF (Multi-function Key): Used for various functions depending on context.
- Arrow Keys (Up/Down/Left/Right): Navigate menus and adjust parameter values.
- ENTER Key: Confirms selections and parameter changes.
- RUN Key: Starts the motor.
- STOP/RESET Key: Stops the motor or resets fault alarms.
5.2. Basic Operation
- Power On: Ensure all wiring is correct and secure. Apply power to the VFD. The display will light up.
- Frequency Setting: Use the Speed Control Knob to set the desired output frequency. The display will show the current frequency.
- Start Motor: Press the RUN button to start the motor. The motor will accelerate to the set frequency.
- Stop Motor: Press the STOP/RESET button to stop the motor. The motor will decelerate and stop.
5.3. Parameter Setting (P0 Group - Basic Operating Parameters)
To access and modify parameters, press the PRG key. Use the arrow keys to navigate and the ENTER key to select and confirm.
| Function Code | Name | Description | Range | Factory Default |
|---|---|---|---|---|
| P0.00 | Power specification of frequency drive | Display current power. | 0.10~99.99kw | Device settings |
| P0.01 | Software version of the master controller | Display current software version number. | 1.00~99.99 | 1.00 |
| P0.02 | Run command channel selection | 0: Panel runs the command channel; 1: Terminal runs the command channel; 2: Communication runs command channel. | 0~2 | 0 |
| P0.03 | Frequency setting selection | 0: Panel potentiometer; 1: Number given 1, adjust by operating ▲/▼ keys; 3: AVI simulation given (0~10V/0~20mA). | 0~8 | 0 |
| P0.04 | Maximum output frequency | The highest frequency allowed by the frequency converter. | MAX (50.0, [P0.05]) ~ 999.9Hz | 50.0Hz |
| P0.05 | Upper frequency | The operating frequency cannot exceed this frequency. | MAX (0.1, [P0.06]) ~ [P0.04] | 50.0Hz |
5.4. Operation Demonstration Video
Watch this video for a visual guide on operating the VFD and controlling a motor.
Video: Demonstration of the D12 VFD controlling a motor, showing frequency and current adjustments.
6. Maintenance
- Regular Cleaning: Keep the VFD clean and free from dust and debris. Use a soft, dry cloth. Do not use liquid cleaners.
- Fan Inspection: Periodically check the cooling fan for proper operation and ensure air vents are not obstructed. Clean fan blades if necessary.
- Terminal Tightness: Annually check all wiring terminals for tightness to prevent loose connections, which can cause overheating or malfunction.
- Environmental Check: Ensure the operating environment remains within specified temperature and humidity ranges.
- Capacitor Life: Electrolytic capacitors have a finite lifespan. Consider professional inspection or replacement after several years of continuous operation.
7. Troubleshooting
This section provides common fault codes and suggested countermeasures. For detailed troubleshooting, refer to the full PDF manual.
| Fault Code | Name | Possible Cause | Countermeasures |
|---|---|---|---|
| E0C1 | Overcurrent during acceleration | Acceleration time is too short; Inverter power is too small; Improper V/F curve or torque boost. | Extend acceleration time; Choose a larger power inverter; Adjust V/F curve or torque boost. |
| E0C2 | Overcurrent during deceleration | Deceleration time is too short; Inverter power is too small; Grid voltage is low. | Extend deceleration time; Choose a larger power inverter; Check input power. |
| EHU1 | Overvoltage during acceleration | Abnormal input voltage; Rotating motor not restarted. | Check input power; Set to start after DC braking. |
| E-OH | Radiator overheating | Ambient temperature is too high; Fan damage; Air duct blocked. | Reduce ambient temperature; Replace the fan; Dredge the air duct. |
| E-LT | Photovoltaic water pump water shortage fault | Sensor disconnected or poorly connected; System has no feedback. | Check sensor installation and wiring. |
| E485 | RS485 communication fault | RS485 channel interference; Communication timeout. | Check communication shielding and wiring; Connect filter capacitor in parallel; Retry. |
8. User Tips
- For optimal performance, ensure the VFD's power rating closely matches your motor's requirements.
- When setting parameters, make small adjustments and observe the motor's response before making further changes.
- If using an external potentiometer for speed control, ensure it is properly calibrated and connected to the AVI and 10V/GND terminals.
- Consider using the PID control function for applications requiring precise process control, such as maintaining constant pressure in a water pump system.
- Always perform a test run after any wiring changes or parameter modifications to confirm correct operation.
9. Warranty and Support
The ELECTESLA D12 Series VFD is certified with CE, FCC, and RoHS, ensuring compliance with international safety and environmental standards.
For technical support, service, or warranty claims, please contact your authorized dealer or ELECTESLA customer service. Please have your product model and serial number ready when contacting support.
A detailed user manual in PDF format is available for download, which includes comprehensive parameter descriptions and advanced settings. You can access it via the following link: ELECTESLA D12 Series Frequency Converter Parameter Description (PDF).
10. Applications
The D12 VFD is versatile and can be used in various industrial and commercial applications to control the speed of AC motors, improving efficiency and control.
Figure 6: Typical Applications
- Water Pumps: For constant pressure control and energy saving.
- Compressors: To optimize air delivery and reduce power consumption.
- General Motors: For precise speed and torque control in various machinery.
- Fans: For ventilation systems, allowing variable airflow control.