1. Product Introduction
The EARUELETRIC EA777 is a new three-phase multifunctional electronic electric energy meter designed for accurate measurement of AC voltage with a rated frequency of 50/60Hz. It utilizes microelectronic technology and imported large-scale integrated circuits, incorporating advanced digital acquisition, sample processing, and SMT processes to ensure high performance.
This meter fully complies with national standards GB/T117215.321-2008 (IEC 62053-21:2003, IDT) and GB/T 17215.322-2008 (IEC 62053-22:2003, IDT). It displays current active electric energy, total active/reactive electric energy, and input/output active/reactive electric energy via an LCD. The meter also provides readings for three-phase voltage, current, total/phase active power, total/phase power factor, and frequency.
Key advantages of this model include good reliability, small volume, light weight, aesthetic design, and flexible, convenient installation.
2. Functions and Features
- Installation: 35mm DIN standard rail mounting in accordance with DIN EN-50022.
- Accuracy: High accuracy measurement of active electric energy (Level 1) and reactive electric energy (Level 2). Alternatively, active electric energy (Level 0.5) and reactive electric energy (Level 2).
- Display: LCD 6 + 1-bit display, capable of showing up to 999999.9 kWh.
- Pulse Output: Passive pulse output, conforming to DIN43864 standard, with LED indication for each pulse.
- Parameter Query: Quick query function for various parameters.
- Communication: One RS485 communication interface, supporting Modbus communication protocol or DL/645-2007 communication protocol (optional).
- Measurements: Reactive energy measurement, displaying current, voltage, and power factors.
3. Specifications
| Attribute | Value |
|---|---|
| Brand Name | EARUELETRIC |
| Model Number | EA777 |
| Phase | Three Phase |
| Rated Voltage | 3X230/400V (also 3X220/380V, 3X57.7/100V, 3X380V, 3X100V options) |
| Max Operating Current | 50A - 79A (Direct access: 10(40)A, 15(60)A, 20(80)A, 30(100)A; Via transformer: 1.5(6)A) |
| Power Supply | AC (3X220VAC±20%) |
| Display Type | LCD |
| DIY Supplies | Electrical |
| Origin | Mainland China |
| Certification | CE |
| Dimensions | 96x72x68mm |
| Operating Temperature | -10℃ ~ +55℃ |
| Measuring Energy Range | 999999.9 kWh |
| Accuracy | Level 1 and 0.5s |
| Rated current | 20(80)A |
| Input frequency | 50/60Hz |
| Installation mode | 35mm standard guide rail installation |
| Starting current | 0.4%Ib |
| Power waste | <2W/10VA Each phase |
| Working conditions | Storage temperature: -40℃ ~ +70℃, Relative humidity: 5%~95%, no condensation |
| Battery Included | No |
| High-concerned Chemical | None |
4. Installation
The EA777 meter is designed for 35mm standard DIN rail installation. It can be directly installed in a household lighting distribution box.
4.1 Dimensions
The outline dimensions of the 4P meter are approximately 96mm (length) x 72mm (width) x 68mm (height).
4.2 Wiring Mode
The meter supports two main wiring modes: direct access (rated maximum current < 100A) and access through a transformer. Ensure proper wiring according to the diagrams below.
4.2.1 Direct Access Wiring (4P)
For direct access, connect the N, C, B, A phases to terminals 7, 5, 3, 1 respectively, and their corresponding outputs to 8, 6, 4, 2. RS485 communication uses terminals 17 (485B) and 18 (485A).
4.2.2 Connected Through Transformer (4P)
When connecting through a transformer, ensure the Uc, Ub, Ua phases are connected to terminals 24, 26, 28 respectively. Current transformer inputs (Ic+, Ib+, Ia+) connect to terminals 5, 3, 1, and outputs (Ic-, Ib-, Ia-) to 6, 4, 2. P1- and P1+ are connected to terminals 15 and 16. RS485 communication uses terminals 17 (485B) and 18 (485A).
5. Operation
5.1 Display Description
The device panel features indicator lights for voltage, active power, and reactive power. The pulse output indicator light flashes once each time a pulse is output, synchronously indicating the pulse output.
5.2 Key Operation and Menu Navigation
To switch between different display parameters, press the designated key on the front panel. The meter cycles through various measurements such as total active energy, positive active energy, reverse active energy, total reactive energy, phase voltages (UA, UB, UC), phase currents (IA, IB, IC), phase active powers (PA, PB, PC), phase reactive powers (QA, QB, QC), phase power factors (PFA, PFB, PFC), frequency (F), communication address (Id), and constant (C).
6. Programming Menu
To access the programming menu, press and hold the menu key for 6 seconds. Once in the programming menu, you can adjust various settings:
- PS 0000: Initial state.
- PS 0011: Press the menu key to switch.
- d0011: Displacement.
- Id 0001 - Id 0020: Instrument communication address range (1-247).
- bd 2400 - bd 9600: Baud rate (2400bps, 4800bps, 9600bps optional).
- PY 0001 N O E: Data format (N.8.1: O.8.1: E.8.1).
- CT 0001 - CT 0010: Current magnification range (1-9999).
- Long press: Save data.
7. Modbus Communication
The EA777 meter provides a serial asynchronous semi-active RS485 communication interface, adopting the Modbus-RTU protocol. This allows for the transmission of various data information over the communication line.
7.1 RS485 Bus Connection
- Up to 32 instruments can be connected simultaneously on a 485 bus.
- Each instrument must have a unique communication address.
- Use shielded twisted pair with copper mesh for communication, with a wire diameter of not less than 0.5mm².
- Keep communication lines away from strong electric cables or other strong electric field environments. T-type network is recommended.
- Star or other complex connection methods are not recommended.
7.2 Modbus RTU Protocol
The Modbus protocol operates in a master-slave response mode. The host computer addresses a single slave device, which then sends a response signal back to the host. Data exchange between independent terminal devices is not allowed.
7.2.1 Data Frame Structure
A Modbus message frame consists of:
| Field | Size | Description |
|---|---|---|
| Address Code | 1 byte | Indicates the slave device address (0-255, 1-247 used in this system). Must be unique. |
| Function Code | 1 byte | Tells the slave device what function to perform. |
| Data Code | N bytes | Contains data or terminal response. For queries, specifies registers to read and data length. |
| Check Code (CRC) | 2 bytes | Error check field (16-bit binary value). Used to verify data integrity. |
7.2.2 Function Codes
The meter supports the following function codes:
| Code Meaning | Significance |
|---|---|
| 0x03/0x04 | Register read/write value |
| 0x10 | Set register instruction |
7.2.3 Transmission Mode
The transmission mode compatible with Modbus protocol RTU mode defines the following input mode:
- Bits per byte: 1 start bit, 8 data bits, (parity bit), 1 stop bit.
7.2.4 Modbus-RTU Communication Address Information Table
The following table details the communication addresses for various parameters, with a default baud rate of 9600bps and even parity:
| Address (Hex) | Data Content | Data Length (word) | Read/Write | Explain |
|---|---|---|---|---|
| 0x00 | Phase A voltage | 1 | R | Ua (0.1V) |
| 0x01 | Phase B voltage | 1 | R | Ub (0.1V) |
| 0x02 | Phase C voltage | 1 | R | Uc (0.1V) |
| 0x03 | Phase A current | 1 | R | Ia (0.1A) |
| 0x04 | Phase B current | 1 | R | Ib (0.1A) |
| 0x05 | Phase C current | 1 | R | Ic (0.1A) |
| 0x08 | Phase A active power | 1 | R | Pa (W) |
| 0x09 | Phase B active power | 1 | R | Pb (W) |
| 0x0A | Phase C active power | 1 | R | Pc (W) |
| 0x0C | Phase A reactive power | 1 | R | Qa (Var) |
| 0x0D | Phase B reactive power | 1 | R | Qb (Var) |
| 0x0E | Phase C reactive power | 1 | R | Qc (Var) |
| 0x14 | Phase A power factor | 1 | R | cosQ A (0-1.000) |
| 0x15 | Phase B power factor | 1 | R | cosQ B (0-1.000) |
| 0x16 | Phase C power factor | 1 | R | cosQ C (0-1.000) |
| 0x1A | Voltage frequency | 1 | R | FR (0.01Hz) |
| Meter Setting Parameters (Read) | ||||
| 0x61 | Instrument communication address | 1 | R | 1-247 |
| 0x62 | Communication baud rate | 1 | R | 0-600; 1-1200; 2-2400; 3-4800; 4-9600 |
| 0x63 | Communication data format | 1 | R | data format 0-N.8.1 1-O.8.1 2-E.8.1 |
| Meter Setting Parameters (Write) | ||||
| 0x61 | Instrument communication address | 1 | W | 1-247 |
| 0x62 | Communication baud rate | 1 | W | 0-600; 1-1200; 2-2400; 3-4800; 4-9600 |
| 0x63 | Communication data format | 1 | W | data format 0-N.8.1 1-O.8.1 2-E.8.1 |
| Current Electric Energy | ||||
| 0x001D | Current total active electric energy | 2 | R | 0.01Kwh |
| 0x0027 | Current positive total active energy | 2 | R | 0.01Kwh |
| 0x0031 | Current reverse total active energy | 2 | R | 0.01Kwh |
| 0x003B | Current total reactive energy | 2 | R | 0.01Kvarh |
| 0x0045 | Current positive total reactive energy | 2 | R | 0.01Kvarh |
| 0x004F | Current reverse total reactive energy | 2 | R | 0.01Kvarh |
8. Troubleshooting
- No Display: Check power connections and ensure the rated voltage is supplied correctly.
- Incorrect Readings: Verify wiring connections against the diagrams in Section 4.2. Ensure current transformers (if used) are correctly installed and configured. Check the programming menu for correct current magnification settings.
- Communication Errors (RS485): Confirm correct wiring of RS485 A and B terminals. Check communication address, baud rate, and data format settings in the programming menu. Ensure no strong electrical interference near the communication lines.
- Pulse Output Issues: Verify the pulse output indicator LED is flashing. Check connections to external devices receiving pulse signals.
9. Maintenance
- Cleaning: Keep the meter clean and free from dust. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
- Environmental Conditions: Ensure the meter operates within the specified operating temperature and humidity ranges to prevent damage and ensure accuracy.
- Periodic Checks: Periodically inspect wiring connections for tightness and signs of wear or corrosion.
10. User Tips
- Data Logging: For long-term energy monitoring, utilize the RS485 communication interface to connect the meter to a data logging system or PC.
- Safety First: Always ensure power is disconnected before performing any installation, wiring, or maintenance on the meter. Consult a qualified electrician if unsure.
- Parameter Review: Regularly cycle through the display parameters to monitor various electrical values and ensure system health.
11. Warranty and Support
For warranty information and technical support, please refer to the official documentation provided by the seller or contact EARUELETRIC customer service directly. A detailed user manual in PDF format is available for download, which contains comprehensive information on installation, operation, and advanced features. You can find the PDF manual at: User Manual (PDF).