TOMZN TOQ5-125/3

Contents

TOMZN 3P 3 Phase Din Rail ATS Dual Power Automatic Transfer Switch User Manual

Model: TOQ5-125/3

1. Safety Information

Warning: To avoid danger of suffocation, keep this bag away from babies and children. Do not use this bag in cribs, beds, carriages, or play pens. This bag is not a toy.

This product is designed for professional installation and operation. All work must be performed by a qualified electrical professional.

Always disconnect power before installation, maintenance, or inspection to prevent electric shock.

Ensure adequate ventilation during operation and do not place the device near flammable materials.

The device is certified with CE marking, indicating compliance with European safety standards.

TOMZN ATS Dual Power Automatic Transfer Switch with CE mark

Image: TOMZN ATS Dual Power Automatic Transfer Switch with CE mark and product details.

2. Product Overview

The TOMZN TOQ5 series Dual Power Automatic Transfer Switch (ATS) is a miniature household power switch designed to automatically switch between a main power supply and a backup power supply. This ensures continuous, reliable, and safe power delivery, especially in situations where power failure cannot be tolerated.

The ATS is suitable for emergency power supply systems operating at 50 or 60Hz and rated 400V AC. It features a solid structure, reliable conversion, convenient installation, and a long service life. It can be operated electrically or manually and is composed of a Transfer Switching Equipment (TSE) and a controller.

This product is specifically designed for household rail installation and is compatible with PZ30 distribution boxes.

Function Overview

When the main power supply of the circuit fails, the equipment will immediately switch to the backup power supply. Once the main power supply is restored, the ATS will automatically switch back to the main power supply, ensuring uninterrupted power.

TOMZN ATS with 'Millisecond Switching Without Interruption' text

Image: TOMZN ATS highlighting millisecond switching for uninterrupted power.

TOMZN ATS with 'Automatic Switching After Power Off <8MS' text and stopwatch

Image: TOMZN ATS demonstrating automatic switching within 8 milliseconds.

3. Specifications

The TOQ5 series ATS is available in various rated currents: 63A, 100A, and 125A.

Table of TOQ5 Dual Power Switch specifications

Image: Detailed specifications table for TOQ5 Dual Power Switch.

Main Technical Parameters (TOQ5-125/3)
SpecificationValue
Rated Current (Ie)63A, 100A, 125A (3P)
Insulation Voltage (Ui)AC690V, 50Hz
Rated Voltage (Ue)AC400V, 50Hz
ClassificationPC class: can be manufactured and withstood without short circuit current
Utilization CategoryAC-31B, AC-33iB
Pole No.3P
Weight (kg)0.722 kg (package weight)
Electrical Life2000 times; Manual operation: 5000 times
Rated Short Circuit Current (Iq)50kA
Rated Impulse Withstand Voltage8kV
Control Circuit Voltage (Us)AC220V/50Hz (Normal working conditions: 85-110%Us)
Conversion Time<50ms (Operation, Return, Power off)

Dimensions

Dimension Diagram of TOMZN ATS

Image: Dimension diagram of the TOMZN ATS. Height (A): 95mm, Length (B): 68mm, Length (C): 124mm. Dimensions are for reference only.

4. Setup

Before installation, ensure you have read and understood all safety information and technical specifications.

Installation Conditions

  • Ambient Air Temperature: Maximum 40°C, minimum -5°C. Average temperature within 24 hours not higher than 35°C.
  • Altitude: Installation site should not be higher than 2000m.
  • Atmospheric Conditions: At 40°C, relative humidity should not exceed 50%. At -5°C, relative humidity can be higher, e.g., 90% at 25°C. Take measures to address occasional condensation.
  • Pollution Grade: Conforms to grade 3 specified in GB/T14048.11.
  • Installation Category: Conforms to the category specified in GB/T14048.11.

Mounting

The ATS can be installed vertically in a control cabinet or distribution cabinet. It supports 35mm standard DIN rail installation.

35mm Standard Rail Installation of TOMZN ATS in a distribution box

Image: TOMZN ATS installed on a 35mm standard DIN rail within a household lighting distribution box.

Wiring

Connect the equipment in accordance with the wiring diagram specifications. Ensure all connections are secure and correct. The cross-sectional area of copper wire for the control circuit should not be greater than 2.0mm².

Easy Wiring Diagram for TOMZN ATS

Image: Easy wiring diagram for the TOMZN ATS, showing common power supply, backup power, common neutral line, backup neutral line, and load output connections. When power lines are input through L and N, screw down to penetrate the insulating layer of the power lines.

TOMZN ATS with 'Easy Wiring, DIY by Yourself' text and wiring diagram

Image: TOMZN ATS with a simplified wiring diagram for DIY installation.

Internal Wiring Diagram (Fig. 1 from PDF)

This diagram illustrates the internal components and connections:

  • K1: Manual/automatic selector switch
  • K2, K3: Internal valve position switch
  • J1: Common 220V A power relay
  • J2: Standby 220V B power relay
  • 1: Passive signal output of A power supply
  • 2: Passive signal output of B power supply

Controller Wiring Diagram (Fig. 2 from PDF)

Shows connections for common incoming line, common control line, standby incoming line, main power supply A (RSTN), standby power supply B, standby power indicator, load output, and standby control line.

100/3P Wiring Diagram (Fig. 4 from PDF)

Details the wiring for a 3-phase system, including common incoming line, common control line, common zero line input, main power supply A (RST), standby incoming line, standby power supply B, load output, standby control line, and standby zero line input.

Special Connection Mode of Photovoltaic Inverter (Fig. 7 from PDF)

Illustrates how to connect the ATS with a photovoltaic power station and inverter as the main power supply, and city electricity as the standby power supply.

Provide appropriate circuit breakers according to the power distribution system requirements to ensure safety.

5. Operating Instructions

Manual/Automatic Operation

The ATS offers both manual and automatic operation modes. The switch comes with a manual handle and a manual/automatic selector switch.

TOMZN ATS showing manual handle and manual/automatic switch

Image: TOMZN ATS illustrating the manual handle and manual/automatic switch for mode selection.

  • Automatic Mode: In normal circumstances, keep the selector switch in the automatic position. The ATS will automatically detect power failures and restore power, switching between main and backup supplies as needed.
  • Manual Mode: For checking and maintaining the operating system and contacts, pull the selector switch to the manual position. After manual operation is completed, always return the selector switch to the automatic position.

Controller Circuit

The ATS instantly becomes active upon power events. After the conversion is completed, the coil in the control circuit will be disconnected by the internal converter. The coil operates normally under a rated voltage of 80%-110%. Low voltage can cause coil heating and even spontaneous combustion.

Video: Demonstration of the automatic switching function of the TOMZN ATS.

6. Maintenance and Inspection

Maintenance and inspection should only be performed by qualified professionals with all power supplies disconnected.

  • Initial Inspection: The first maintenance and inspection should be carried out within 6 months after initial use.
  • Regular Inspection: Inspect and maintain the device at least once a year. In harsh installation conditions, increase the frequency of maintenance.

Maintenance Items

  1. Cleaning: Remove dust and dirt from the device.
  2. Contact Check: Inspect electrical contacts for deformation or damage. Remove any burnt metal particles from the contact surfaces.
  3. Contact Resistance: If rust, acidification, or dust on contact surfaces leads to poor contact, operate the switch manually multiple times and measure the contact resistance.
  4. Insulation Resistance: If the ATS has been exposed to long-term moisture or suspension, dry it before use. After cleaning, use a 500V megohmmeter to measure the insulation resistance between the normal supply, alternating power supply, load side bar, live parts, and metal plate. The insulation resistance should not be less than 10MΩ.

Storage

Store the ATS in an environment equivalent to normal working conditions, ensuring it is dust-proof, moisture-proof, and collision-proof.

7. Troubleshooting

If you encounter issues with your TOMZN ATS, consider the following:

  • No Power Transfer: Verify that both main and backup power sources are active and correctly wired according to the diagrams. Check the manual/automatic selector switch position.
  • Coil Overheating/Spontaneous Combustion: This can occur due to low voltage. Ensure the control circuit voltage is within the rated 80%-110%Us range.
  • Poor Contact: If the switch is not making proper contact, it might be due to dirt, rust, or acidification on the contact surfaces. Perform manual operations multiple times to clear the contacts, or clean them as described in the maintenance section.
  • Physical Damage: Inspect the device for any visible damage or loose connections.

For complex issues or if troubleshooting steps do not resolve the problem, it is recommended to contact a qualified electrician or the manufacturer for assistance.

8. User Tips

  • Professional Installation: Always have an electrical professional perform the initial installation and wiring to ensure safety and correct functionality.
  • Regular Checks: Periodically check the device for any signs of wear, dust accumulation, or loose connections, especially in industrial or harsh environments.
  • Understand Wiring: Familiarize yourself with the wiring diagrams provided to ensure proper connection of common power, backup power, and control lines.
  • Mode Selection: Use the automatic mode for daily operation to benefit from seamless power transfer. Reserve manual mode for specific maintenance or testing procedures.

9. Warranty and Support

This product is qualified after inspection and meets the standard GB/T 14048.11. For specific warranty details, please refer to the product packaging or contact your vendor.

For technical support, questions, or to provide feedback on the product, please contact the manufacturer or your vendor directly. This manual is for reference only, and product or version upgrades may occur without notice.

A user manual in PDF format is available for download: Download User Manual (PDF)