1. Introduction

The GEYA GYPV-32 1P Solar Photovoltaic Fuse Holder is designed to provide essential overcurrent protection for solar photovoltaic (PV) systems. When paired with a GYPV-1038 series fuse link, it safeguards DC circuits from overloads and short circuits, ensuring the longevity and safety of your solar installation. This manual provides detailed instructions for proper installation, operation, and maintenance.

GEYA Company Introduction Video

2. Safety Information

WARNING: Electrical installations should only be performed by qualified personnel. Failure to follow these instructions may result in electric shock, fire, or serious injury.

  • Always disconnect power before installing or servicing the fuse holder.
  • Ensure proper grounding according to local electrical codes.
  • DO NOT OPEN UNDER LOAD: Never open the fuse holder when current is flowing through the circuit.
  • Use only specified wire types and gauges.
  • Ensure all connections are tightened to the specified torque to prevent overheating.
  • Verify that the fuse link rating matches the circuit requirements.

3. Product Overview

The GEYA GYPV-32 is a single-pole (1P) fuse holder designed for DIN rail mounting. It accommodates 10x38mm gPV fuse links, providing reliable protection for DC circuits up to 1000V. The fuse holder features clear markings for specifications and safety warnings.

GEYA GYPV-32 1P Solar PV Fuse Holder
Figure 1: GEYA GYPV-32 1P Solar PV Fuse Holder
GEYA GYPV-32 1P Solar PV Fuse Holder with fuse link
Figure 2: GEYA GYPV-32 Fuse Holder with an inserted fuse link

The compatible fuse links, such as the GEYA GYPV-1038 series, are cylindrical and come in various current ratings to suit different circuit protection needs.

GEYA Solar gPV Fuse Links
Figure 3: GEYA Solar gPV Fuse Links

4. Specifications

4.1. Fuse Holder (GYPV-32)

Parameter Specification
Model NumberGYPV-32
TypeFuse Holder
Rated Voltage1000V DC
Rated Current32A
Fuse Size Compatibility10x38mm
Wire Range1-10mm² (or #4-18 AWG for 75° CU wire)
Torque2-2.5Nm (or 18-24 lb.in for 75° CU wire)
CertificationCE, RoHS
StandardIEC60269-6, GB13539-6
EU LVD VoltageLow voltage: Below 50Vac or 75Vdc
GYPV-32 Fuse Holder Label with specifications
Figure 4: GYPV-32 Fuse Holder Label showing specifications
Parameter Specification
Model NumberGYPV-1038
Rated Voltage1000V DC
Rated Current1A-32A (e.g., 2A, 6A, 10A, 15A, 20A, 25A, 30A)
Fuse Size10x38mm
Class of OperationgPV
Breaking Capacity20kA
Time Constant1-3ms
StandardGB/T 13539.6, IEC 60269-6
Photovoltaic Fuse Model Specifications and Parameters
Figure 5: GYPV-1038 Fuse Link Model Specifications and Parameters

4.3. Dimensions (mm)

GYPV-32 Fuse Holder Dimensions
Figure 6: GYPV-32 Fuse Holder Dimensions

5. Installation

5.1. Mounting

The GYPV-32 fuse holder is designed for DIN rail mounting. Ensure the DIN rail is securely fastened within an enclosure that provides adequate protection from environmental factors.

5.2. Wiring

  1. Prepare Wires: Use 75° CU wire only. Strip insulation to the appropriate length for secure terminal connection.
  2. Connect Wires: Insert the prepared wires into the terminals of the fuse holder.
  3. Tighten Terminals: Use a screwdriver to tighten the terminal screws to the specified torque of 2-2.5Nm (18-24 lb.in). Over-tightening or under-tightening can lead to damage or poor contact.
  4. Insert Fuse Link: Carefully insert the appropriate 10x38mm GYPV-1038 fuse link into the fuse holder. Ensure it is seated correctly.
  5. Close Fuse Holder: Close the fuse holder cover securely.
Fuse Holder Wiring Diagram
Figure 7: Example of fuse holder installation and wiring

6. Operation

The fuse holder is designed for simple operation. When the fuse link is correctly installed and the holder is closed, the circuit is complete. In the event of an overcurrent or short circuit, the fuse link will blow, interrupting the circuit and protecting downstream components.

  • Fuse Replacement: If a fuse link blows, the indicator (if present) may change color or pop out. To replace, first disconnect power to the circuit. Open the fuse holder, remove the blown fuse, and insert a new fuse link of the correct rating. Close the holder securely before restoring power.
  • Important: Always ensure the circuit is de-energized before opening the fuse holder for inspection or replacement.

7. Maintenance

Regular maintenance helps ensure the optimal performance and safety of your fuse holder.

  • Visual Inspection: Periodically inspect the fuse holder for any signs of physical damage, discoloration, or loose connections.
  • Terminal Tightness: Check terminal screws periodically to ensure they remain tightened to the specified torque.
  • Cleaning: Keep the fuse holder clean and free from dust and debris. Use a dry, soft cloth for cleaning.
  • Environmental Conditions: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent premature aging or malfunction.

8. Troubleshooting

Problem Possible Cause Solution
Circuit not protected / Frequent fuse blowing Incorrect fuse rating (too low or too high), persistent overload, short circuit in the system. Verify fuse rating matches circuit requirements. Investigate and resolve the cause of overload or short circuit in the PV system.
Overheating of fuse holder Loose connections, undersized wiring, continuous overload. Check and re-tighten all terminal connections to specified torque. Ensure correct wire gauge is used. Reduce load if consistently overloaded.
Fuse holder difficult to open/close Debris or damage to the mechanism. Clean any debris. If damaged, replace the fuse holder.

9. User Tips

  • Plan Ahead for Delivery: Some users have experienced long delivery times. If your project is time-sensitive, consider ordering well in advance or checking for local availability.
  • Verify Compatibility: Always double-check that the fuse holder and fuse link specifications (voltage, current, and size) are compatible with your solar system requirements before installation.
  • Quality Assurance: Users generally report good quality for this product, indicating it performs as described.

10. Warranty and Support

GEYA products are manufactured to high standards and are certified according to various international industry standards, including CE and RoHS. For specific warranty information or technical support, please refer to the official GEYA website or contact your local distributor.

GEYA is committed to providing top-quality products and service to meet customer needs. For further details, you may consult the official GEYA website: www.cngeya.com.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.