1. Welcome
The EARU EASEM-D Multi-Circuit Power Meter is designed to help you monitor the amount of electricity consumed and produced in your facility by connecting current transformer (CT) clamps to your power cables. This guide provides an overview of the product and assists with initial setup and installation.
Key Features:
- Tuya compliant, supporting automation with other Tuya devices.
- Compatible with Single, Split-Phase 120/240VAC, and 3-Phase/4-wire 480Y/277VAC electricity systems.
- Remotely monitors whole home energy and up to 16 individual circuits with 50A Sub CTs (e.g., Solar, lighting, receptacles).
- Bi-Directional measurement capabilities.
- Real-time Voltage, Current, Power Factor, Active Power, and Frequency measurement.
- Provides historical data of energy consumed and energy production.
2. Safety Handling
WARNING: Failure to follow these safety notices could result in fire, electric shock, other injuries, or damage to the Power Meter and other property. Read all the safety notices below before using the Power Meter.
- The Power Meter must be installed and serviced only by qualified electrical personnel.
- Do not touch the terminals of the device during testing.
- Turn off the power before connecting or disconnecting it to an auxiliary device.
- Double check the power is off with a properly rated voltage sensing device.
- Avoid high humidity or extreme temperatures.
- Avoid long exposure to direct sunlight or strong ultraviolet light.
- Do not drop or expose the unit to intense vibration.
- Do not disassemble or try to repair the unit on your own.
- Do not expose the unit or its accessories to flammable liquids, gases or other explosives.
Failure to follow these instructions will result in death or serious injury.
3. Get to Know Your Device
The EARU EASEM-D Multi-Circuit Power Meter consists of a main unit, various CT clamps, an external antenna, a power cable, and a mounting bracket.
Ports and Connections:
All ports are labeled on the back and sides of the main unit:
- Main CT Inputs: Three 3.5mm audio ports on the top of the main unit for Main CTs (labeled L1/A, L2/B, L3/C).
- Sub CT Inputs: Multiple 2.5mm audio ports on the sides of the main unit for Sub CTs.
- Antenna Connector: Located on the top of the main unit.
- Power Input Port: Located at the bottom of the main unit for the power cable.
4. Technical Specifications
| Attribute | Value |
|---|---|
| Brand Name | EARU |
| Model Number | EASEM-D-TY |
| DIY Supplies | Electrical |
| Origin | Mainland China |
| Certification | CE, FCC |
| Operating Voltage | 90~480 Vac 50/60 Hz |
| Rated Current | 200A / 300A (depending on CTs) |
| Max Operating Current | 150A & Above |
| Accuracy Class | ±2% |
| Phase | Three |
| Power Supply | AC |
| Wi-Fi | 802.11 b/g/n @ 2.4GHz (5GHz Wi-Fi not supported) |
| Operating Frequency | 2.4GHz |
| RF Characteristics | External magnetic antenna |
| Supported Systems | Single-Phase up to 277VAC line-neutral, Split-Phase 120/240VAC, Three-Phase up to 480Y/277VAC (No Delta/wye/Y/Star Connection) |
| Reporting Cycle | Every 15 seconds |
| Operating Temperature | -20℃ ~ +55℃ |
| Humidity | ≤ 90% non-condensing |
| Dimensions | 111.3(L) x 81.2(W) x 41.4(H) mm |
| Battery Included | No |
5. Installation and Setup
5.1. Prepare for Installation
-
Turn off power: You must turn off the main breaker in your electrical panel to shut off all power to your home. However, the service mains are always live! Use professional equipment to ensure the power is off before proceeding. Then, remove screws securing the cover to the panel to access the circuit breakers.
Always turn off power and verify with a multimeter before working on electrical panels. -
Find a spot for the Power Meter: You can install the main unit inside your electrical panel or use the mounting bracket to fix it on the wall outside the electrical panel if space is limited.
Mounting options for the Power Meter. -
Install the External Antenna: Locate the External Antenna outside the electrical panel to ensure the Power Meter signal is not blocked by metal. The antenna base is magnetic and can adhere to iron materials. Screw the External Antenna to the Antenna connector on the main unit. If installing the Power Meter inside the panel, punch out a knockout cover and feed the antenna cable through.
Antenna installation for optimal signal.
5.2. Wiring the Power Meter
Refer to the video for a visual guide on 3-phase electricity wiring:
-
Connect the Power Cable: Insert the power cable into the bottom of the main unit until it clicks securely into place.
Connecting the power cable to the main unit. - Secure N and L1 Wires: Secure the N wire from the power cable to the neutral bus bar and the L1 wire to the L1/A breaker pole.
-
Clamp Main CTs around service mains:
- Open the clasps on the Main CTs (3.5mm audio plug) to see the arrow (P1→P2 or K→L) or check the sticker on the outside of the clamp. This indicates the direction of the CT.
- Clamp one Main CT on each main service line. Make sure the arrow on the CT must point towards the breakers! Your system may have 1, 2, or 3 main service lines, requiring a corresponding number of Main CTs.
- If you have Line/Service-side tap solar, the Main CT must be clamped between the electricity meter and incoming feeds from the inverter.
CT clamp direction and dimensions.
Main CT clamping direction and solar integration. -
Insert Main CT Plugs: Insert each 3.5mm audio plug of the Main CT into the corresponding audio jack on the top of the Power Meter:
- The CT measuring the L1/A line should plug into the audio jack labeled L1/A.
- The CT measuring the L2/B line should plug into the audio jack labeled L2/B.
- The CT measuring the L3/C line should plug into the audio jack labeled L3/C.
Main CT plug connections and system wiring examples. -
Clamp Sub CTs around circuits: (Skip if not using Sub CTs)
- Open the clasps on the Sub CTs (2.5mm audio plug) to see the arrow (P1→P2 or K→L) or check the sticker on the outside of the clamp. This indicates the direction of the CT.
- Clamp each Sub CT around the circuit you wish to monitor. Make sure the arrow on the CT must point towards the load or Inverter!
- Insert each 2.5mm audio plug of the Sub CT into the audio jack on the side of the Power Meter. Remember the number of the audio jack connected to the circuit you are measuring, and you may need to match it in your app.
Sub CT clamping and connection details. -
Mounting: The mounting bracket supports DIN-rail installation. Click the three hooks on the mounting bracket to the DIN-Rail. Locate the hooks of the mounting bracket and line them up with the mounting holes on the Power Meter. Fit the hooks into the mounting holes. Installation is now completed.
Mounting the Power Meter using the provided bracket.
5.3. Wiring Reference Diagrams
Below are wiring reference diagrams for different electrical systems:
6. Configure Network
The Power Meter connects via 2.4GHz Wi-Fi. Note that the network cannot support 5GHz Wi-Fi!
6.1. Download the App
Download the Smart Life application from your device's App Store or App Market. You can also scan the QR code below to download and install.
6.2. Network Configuration Methods
Here are three methods to configure the device network:
-
Method 1 (Scan):
- Open the Smart Life app and click the 'Scan' button in the upper right corner of the App Home page.
- Scan the QR code on the device or in the manual.
- The scanned devices will pop up automatically. Click 'Add'.
- Enter your home Wi-Fi account and password (2.4GHz only) and wait for it to be added. Click 'Done'.
Network configuration using the app's scan function. -
Method 2 (Bluetooth Assisted):
- After the device is installed, power on the power clamp.
- Press and hold the reset button for 5 seconds until the LED flashes red 3 times quickly.
- Open the Smart Life app and turn on Wi-Fi and Bluetooth on your phone.
- Open the manual and turn to page 20 to see the QR code. Scan the QR code to configure the network.
- Scanned devices will automatically pop up and be added. If not, click the '+' on the top right of the home page to add the device.
- Enter your home Wi-Fi account and password (2.4GHz only) and wait for it to be added. Click 'Done'.
Network configuration using Bluetooth assistance. -
Method 3 (Manual Selection):
- After the device is installed, power on the power clamp.
- Press and hold the reset button for 5 seconds until the LED flashes red 3 times quickly.
- Open the Smart Life app and turn on Wi-Fi and Bluetooth on your phone.
- Open the app and click the '+' on the top right of the home page to add the device.
- Find the 'Energy' option and click 'Switch Module (Wi-Fi)' in the subdirectory 'Breaker'.
- Enter your home Wi-Fi account and password (2.4GHz only).
- Click 'Confirm the indicator is blinking'. The device indicator light flashes quickly, click 'Blink Quickly'.
- Wait for it to be added and click 'Done'.
7. Operating Instructions
Once your Power Meter is successfully connected to the Smart Life app, you can begin monitoring your energy usage and production.
7.1. App Interface Overview
The Smart Life app provides a comprehensive view of your energy data:
- Home Screen: Displays Net Usage, Solar Usage, Home Usage, and individual circuit data.
- Real-time Data: View total active power, total current, frequency, and individual circuit power/current/voltage.
- Charts: Access historical data for production, usage, to grid, and from grid over day, week, month, or year.
- Settings: Configure circuit settings, solar settings, rate, unit, and billing cycle start.
7.2. Voice Control
The Power Meter is compatible with Amazon Alexa and Google Assistant, allowing for hands-free voice control. Connect the intelligent speaker and use voice commands to manage your smart home devices.
8. Maintenance
- Keep the device clean and free from dust. Use a soft, dry cloth for cleaning.
- Ensure all connections are secure and free from corrosion.
- Regularly check the Smart Life app for firmware updates to ensure optimal performance and security.
- Avoid exposing the device to direct water or extreme weather conditions.
9. Troubleshooting
9.1. LED Indicator Status
The LED indicator on the main unit provides information about the device's status:
| LED Status | Meaning |
|---|---|
| Green LED blinking | Waiting for pairing |
| Green LED solid on | Device has connected to cloud |
| Red LED solid on | Device is connected to the router, but failed to connect to the cloud |
| Red LED blinking | Wi-Fi has been configured, but failed to connect to the router |
9.2. Resetting the Device
To reset the Power Meter to default factory settings (energy data will not be cleared), press and hold the reset button for 5 seconds until the LED indicator flashes red 3 times quickly. If you want to clear the energy data, please delete the device and wipe data on the app and then add it again.
9.3. Common Issues
- Device not connecting to Wi-Fi: Ensure your Wi-Fi network is 2.4GHz. The device does not support 5GHz Wi-Fi. Check your Wi-Fi password and signal strength.
- Inaccurate measurements: Double-check that all CT clamps are installed with the arrow pointing in the correct direction (towards breakers for main CTs, towards load/inverter for sub CTs). If monitoring circuits that generate energy (e.g., with an inverter), manually set the phase of the circuit in the app settings after wiring is complete.
- No bidirectional reading: Verify that the CT clamps are correctly oriented and that your system configuration in the app supports bidirectional measurement.
10. User Tips
- Home Assistant Integration: Users have successfully integrated this device with Home Assistant for advanced automation and data logging. Refer to community forums for specific integration guides.
- Wi-Fi Compatibility: Always ensure your router is configured to provide a 2.4GHz Wi-Fi network for this device, as it does not support 5GHz.
- CT Clamp Direction: Pay close attention to the arrow direction on the CT clamps during installation to ensure accurate energy measurement, especially for bidirectional readings.
11. Warranty and Support
For warranty information, technical support, or service inquiries, please contact the manufacturer or your point of purchase. Keep your purchase receipt as proof of purchase.
A user manual in PDF format is available for download: View User Manual (PDF)