DIANQI DTS771;DTS777

Contents

DIANQI Din Rail AC 230/380V 3 Phase 4 Wire Energy Meter User Manual

Models: DTS771, DTS777

1. Introduction

The DIANQI DTS771 and DTS777 three-phase multifunctional electronic energy meters are new generation devices designed for accurate measurement of AC voltage, current, and power consumption in 3-phase, 4-wire systems. These meters incorporate microelectronic technology and imported special large-scale integrated circuits, applying digital acquisition with advanced sample processing and SMT processes.

The performance of these meters fully meets national standards GB/T117215.321-2008 (IEC 62053-21:2003, IDT) and GB/T Class 1 or 0.55 in 17215.322-2008 (IEC 62053-22:2003, IDT). They can directly and accurately measure AC voltage with a rated frequency of 50/60Hz.

Key measurements include current active electric energy, total active/reactive electric energy, input/output active/reactive electric energy, three-phase voltage, current, total/phase active power, total/phase power factor, and frequency. These meters offer good reliability, small volume, light weight, beautiful appearance, and flexible, convenient installation.

2. Features

  • 35 mm DIN standard rail mounting in accordance with DIN EN-50022.
  • High accuracy measurement of active electric energy (level 1) and reactive electric energy (level 2), or active electric energy (level 0.5) and reactive electric energy (level 2).
  • LCD 6 + 1-bit display (up to 999999.9 kWh).
  • Passive pulse output, conforming to DIN43864 standard.
  • LED indication pulse output.
  • Quick query of various parameters.
  • Optional RS485 communication interface, supporting Modbus communication protocol or DL/645-2007 communication protocol.
  • Measures and displays current, voltage, and power factors.
  • Models available with and without LCD backlight.
  • Unresettable energy measurement.
Overview of DTS771 and DTS777 energy meters
Figure 2.1: Overview of DTS771 and DTS777 energy meters, highlighting the unresettable feature.

3. Specifications

3.1 General Specifications

Parameter Value
Brand NameDIANQI
Model NumbersDTS771; DTS777
Power SupplyAC
PhaseThree
Display TypeLCD (with/without backlight options)
DIY SuppliesElectrical
OriginMainland China
CertificationCE
Battery IncludedNo
High-concerned chemicalNone

3.2 Technical Parameters

Parameter Value
Rated Voltage3x220/380V, 3x57.7/100V, 3x380V/3x100V
AccuracyLevel 1 and 0.5s
Rated Current (Direct Access)10(40)A, 15(60)A, 20(80)A, 30(100)A
Rated Current (Via Transformer)1.5(6)A
Input Frequency50/60Hz
Starting Current0.4%Ib
Working Power Supply3x220VAC ± 20%
Power Waste<2W/10VA Each phase
Operating Temperature-10°C ~ +55°C
Storage Temperature-40°C ~ +70°C
Relative Humidity5% ~ 95%, no condensation
Installation Mode35mm standard guide rail installation
Overall Dimension96x72x68mm (L x W x H)
Dimensional drawings for DTS777 and DTS771 models
Figure 3.1: Dimensions for DTS777 and DTS771 models.
DTS771 Transparent Version dimensions
Figure 3.2: DTS771 Transparent Version, showing dimensions and internal components.

4. Safety Information

Please read this manual carefully before installation and operation. Improper use may result in electric shock, fire, or other hazards. Always adhere to local electrical codes and regulations.

  • Installation and maintenance should only be performed by qualified personnel.
  • Ensure power is disconnected before any installation or wiring work.
  • Use appropriate personal protective equipment (PPE).
  • Verify correct voltage and current ratings before connecting the meter.
  • Do not operate the meter if it appears damaged.

5. Package Contents

The package typically includes:

  • 1 x DIANQI DTS771 or DTS777 Energy Meter
  • 1 x User Manual (this document, or a printed version)

For a detailed user manual in PDF format, please refer to the official document: User Manual (PDF).

6. Installation

6.1 Mounting

The energy meter is designed for 35 mm DIN standard rail mounting. Ensure the mounting location is stable, dry, and free from strong electromagnetic interference.

6.2 Wiring Instructions

The meter is suitable for both direct access type (rated maximum current < 100A) and access type through a transformer. The wiring method is typically upper input and lower output.

DTS771 wiring diagram
Figure 6.1: DTS771 wiring diagram showing upper input and lower output terminals.
DTS777 wiring diagram
Figure 6.2: DTS777 wiring diagram showing upper input and lower output terminals.
DTS771 direct meter wiring diagram
Figure 6.3: DTS771 direct meter wiring diagram. Connect L1, L2, L3, and N (Neutral) for both input and output.
DTS777 wiring diagrams for direct access and transformer connection
Figure 6.4: DTS777 wiring diagrams. Figure 5-1 shows direct access wiring (4P). Figure 5-2 shows wiring when connected through a transformer.

For detailed wiring, refer to the diagrams above. Ensure all connections are secure and correct to prevent damage to the meter or electrical system.

7. Operation

7.1 Display Description

The meter's front panel features an LCD display and indicator lights for voltage, active power, and reactive power. A pulse output indicator light flashes once for each pulse output, indicating energy consumption.

7.2 Key Operation (DTS777 with Modbus RTU)

The DTS777 model with Modbus RTU typically includes 'SET' and 'PRESS' buttons for navigation and configuration.

DTS777 with Modbus RTU buttons
Figure 7.1: DTS777 model showing 'SET' and 'PRESS' buttons.

In the display menu, press the key (usually 'PRESS' or 'SET') to switch repeatedly between different parameters such as voltage, current, power, frequency, and energy readings.

7.3 Programming Menu

To access the programming menu, press and hold the menu key for 6 seconds. The menu allows configuration of parameters such as communication address, baud rate, and current magnification.

Example menu flow:

  1. PS 0000 (Password entry)
  2. Press menu key to switch to PS 0011 (Password confirmation)
  3. d0011 (Displacement)
  4. Id 0020 (Instrument communication address range 1-247)
  5. bd 2400 (Baud rate: 2400bps, 4800bps, 9600bps optional)
  6. PY 0001 NOE (N.8.1: O.8.1: E.8.1)
  7. CT 0001 (Current magnification range 1-9999)
  8. Long press to "Save data"

8. Modbus Communication

The meter provides a serial asynchronous semi-active RS485 communication interface and adopts the Modbus-RTU protocol. This allows for data transmission over a communication line.

8.1 Connection

  • Up to 32 instruments can be connected on a 485 bus.
  • Each instrument must have a unique communication address.
  • Use shielded twisted pair with copper mesh for communication, with a wire diameter not less than 0.5mm².
  • Keep communication lines away from strong electric cables or other strong electric field environments. T-type network is recommended.
  • Star or other complex connection methods are not recommended.

8.2 Modbus RTU Protocol

The Modbus RTU protocol operates in a master-slave response mode. The host computer addresses a single terminal device (slave), which then sends a response signal back to the host. Data is transmitted in half-duplex mode.

8.3 Data Frame Structure

Address Code Function Code Data Code Check Code
1 byte1 byteN bytes2 bytes

Byte Address Code: 0-255 (decimal), with 1-247 used in the system. Indicates the address of the terminal device. Each terminal device must have a unique address.

Function Code: Specifies the function to be performed by the addressed terminal (e.g., read register, set register instruction).

Code Meaning Significance
0x03/0x04Register read/write value
0x10Set register instruction

Data Code: Contains data or terminal response for specific functions (e.g., register values, status).

Check Code (CRC): A 2-byte (16-bit binary) value used for error checking. The receiving device recalculates the CRC and compares it with the received data. A mismatch indicates an error.

For detailed Modbus-RTU communication address information, refer to the "MODBUS-RTU communication address information table" in the official PDF manual.

9. Maintenance

  • Regularly inspect the meter for any signs of physical damage or loose connections.
  • Keep the meter clean and free from dust and moisture.
  • Ensure proper ventilation around the meter to prevent overheating.
  • Do not attempt to open or repair the meter yourself. Contact qualified service personnel for any issues.

10. Troubleshooting

  • No Display: Check power supply connections. Ensure the meter is receiving the correct voltage.
  • Incorrect Readings: Verify wiring connections according to the diagrams. Ensure the current transformers (if used) are correctly installed and rated. Check programming settings like current magnification.
  • Communication Issues (Modbus RTU):
    • Verify RS485 wiring polarity (A/B).
    • Check communication address and baud rate settings on both the meter and the host device.
    • Ensure no more than 32 devices are on the bus.
    • Inspect the communication cable for damage and ensure it's shielded.
    • Confirm the host query message frame (address code, function code, data information code, check code) is correct.
  • Pulse LED not flashing: Check if the load is connected and consuming power. Verify the meter is powered on.

11. User Tips

  • Self-Consumption Display: Please note that these meters will display their own power consumption, which is approximately 3-6W. When running 24 hours, this amounts to about 0.1 kW. This self-consumption will be included in the total power consumption displayed on the meter. If this is a concern for your application, please consider this characteristic before installation.
  • Wiring Best Practices: Always ensure that the communication line is kept separate from strong electric cables to avoid interference.

12. Warranty and Support

For warranty information and technical support, please contact your retailer or the manufacturer directly. Keep your purchase receipt as proof of purchase.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.