1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the Sumry 3.6KW Hybrid Solar Inverter. Please read this manual carefully before installations and operations. Keep this manual for future reference.
1.1 Product Overview
This is a multi-function inverter/charger, combining functions of inverter, solar charger, and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
1.2 Key Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible with mains voltage or generator power
- Auto restart while AC is recovering
- Overload/Over temperature/Short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
1.3 Basic System Architecture
The illustration below shows a basic application for this inverter/charger. It also includes the following devices for a complete running system: Generator or Utility, and PV modules. Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.

The inverter features an intelligent cooling fan system that adjusts rotation speed based on ambient temperature and power quality, ensuring optimal performance and longevity.

The inverter provides multi-functional safety protection for you and your devices, including overload, short circuit, battery, overheating, overcurrent, and high/low voltage protection.

The inverter is capable of powering various household appliances. For example, a 3600W inverter with 7200VA peak power can run a fridge for 40 hours, an air conditioner for 5 hours, a washing machine for 12 hours, or a microwave oven for 4 hours.

2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION - Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for the details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. Setup and Installation
3.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside the package:
- The unit x 1
- User manual x 1
3.2 Preparation
Before connecting all wirings, please take off the bottom cover by removing two screws.
3.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It's recommended to use M6 screws.
3.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in the table below as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 3.6KW/6.2KW | 1 x 2AWG | 25 | 2 Nm |
Please follow below steps to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as shown in the chart below.

4. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
3.5 AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 32A for 3.6KW and 50A for 6.2KW.
CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 3.6KW | 12 AWG | 4 | 1.2 Nm |
| 6.2KW | 10 AWG | 6 | 1.2 Nm |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws.
L → LINE (brown or black)
N → Neutral (blue)
WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
4. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
L → LINE (brown or black)
N → Neutral (blue)
5. Make sure the wires are securely connected.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
3.6 PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 3.6KW/6.2KW | 1 x 12AWG | 4 | 1.2 Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
| INVERTER MODEL | 3.6KW | 6.2KW |
|---|---|---|
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| PV Array MPPT Voltage Range | 60Vdc~450Vdc | |
3.7 Final Assembly
After connecting all wirings, please put the bottom cover back by screwing two screws.
3.8 Communication Connection
The inverter supports cloud communication for monitoring:
- Wi-Fi cloud communication (option): Use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP from the APP store and refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or computer webpage.
- GPRS cloud communication (option): Use the supplied communication cable to connect to the inverter and GPRS module, and then apply external power to the GPRS module. Download the APP from the APP store and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or computer webpage.
4. Operation
4.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
4.2 Operation and Display Panel
The operation and display panel, shown in the chart below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.
LCD Display Icons
| Icon | Function Description |
|---|---|
| AC Input Icon | Indicates the AC input. |
| PV Input Icon | Indicates the PV input. |
| Output Voltage/Frequency/PV Voltage/Charger Current/Power/Battery Voltage | Indicates input voltage, input frequency, PV voltage, charger current (if PV is charging for 3.6KW models), charger power, battery voltage. |
| Setting Programs | Indicates the setting programs. |
| Warning and Fault Codes | Indicates the warning and fault codes. |
| Output Information | Indicates output voltage, output frequency, load percent, load in VA, load in Watt and discharging current. |
| Battery Information | Displays battery status. |
| Overload Indicator | Indicates overload. |
| Mains Connection | Indicates unit connects to the mains. |
| PV Panel Connection | Indicates unit connects to the PV panel. |
| AC Bypass | Indicates load is supplied by utility power. |
| Utility Charger Circuit | Indicates the utility charger circuit is working. |
| DC/AC Inverter Circuit | Indicates the DC/AC inverter circuit is working. |
| Mute Operation | Indicates unit alarm is disabled. |
Function Keys
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
4.3 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit. Refer to the detailed tables in the PDF manual for specific program settings.
4.4 Operating Mode Description
The inverter supports various operating modes, including Standby mode, Line mode, and Grid-Tie operation. Each mode has specific display information and functionalities. Refer to the detailed tables in the PDF manual for specific operating mode descriptions and display information.
5. Maintenance
5.1 Clearance and Maintenance for Anti-Dust Kit
Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environments.
Step 1: Loosen the screw in a counterclockwise direction on the top of the inverter.
Step 2: The dustproof case can then be removed, and the air filter foam taken out.
Step 3: Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
6. Troubleshooting
This section provides solutions for common problems you might encounter with your inverter. If the issue persists after following these steps, please contact a qualified service person or return the inverter to your local dealer.
| Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped. | 1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
| Mains exist but the unit works in battery mode. | Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. |
| Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS/Appliance) | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | Green LED is flashing | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. |
| LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. | |
| Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 03 | Battery is over-charged. The battery voltage is too high. | Return to repair center. Check if spec and quantity of batteries are meet requirements. | |
| Fault code 01 | Fan fault | Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center | |
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 Fault code 52 Fault code 55 | Over current or surge. Bus voltage is too low. Output voltage is unbalanced. | Restart the unit, if the error happens again, please return to repair center. |
7. Specifications
7.1 Line Mode Specifications
| INVERTER MODEL | 3.6KW | 6.2KW |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 100Vac | |
| Low Loss Voltage | 90Vac±5V (UPS); 90Vac±5V (Appliances) | |
| Low Loss Return Voltage | 95Vac±5V (UPS); 95Vac±5V (Appliances) | |
| High Loss Voltage | 145Vac±5V | |
| High Loss Return Voltage | 140Vac±5V | |
| Max AC Input Voltage | 150Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Circuit Breaker | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
7.2 Inverter Mode Specifications
| INVERTER MODEL | 3.6KW | 6.2KW |
|---|---|---|
| Rated Output Power | 3.6KW | 6.2KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 100/105/110/115/120Vac±5% | |
| Output Frequency | 50Hz | |
| Peak Efficiency | 93% | |
| Overload Protection | 3s@≥150%; 5s@101%~150% load | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 24Vdc | 48Vdc |
| Cold Start Voltage | 23.0Vdc | 46.0Vdc |
| Low DC Warning Voltage @ load < 50% | 22.0Vdc | 44.0Vdc |
| Low DC Warning Voltage @ load ≥ 50% | 21.0Vdc | 42.0Vdc |
| Low DC Warning Return Voltage @ load < 50% | 22.5Vdc | 45.0Vdc |
| Low DC Warning Return Voltage @ load ≥ 50% | 22.0Vdc | 44.0Vdc |
| Low DC Cut-off Voltage @ load < 50% | 20.5Vdc | 41.0Vdc |
| Low DC Cut-off Voltage @ load ≥ 50% | 20.0Vdc | 40.0Vdc |
| High DC Recovery Voltage | 32Vdc | 62Vdc |
| High DC Cut-off Voltage | 33Vdc | 63Vdc |
| No Load Power Consumption | 45W | 50W |
7.3 Charge Mode Specifications
| INVERTER MODEL | 3.6KW | 6.2KW |
|---|---|---|
| Charging Algorithm | 3-Step | |
| AC Charging Current (Max) | 80Amp (@VI/P=100 Vac) | |
| Bulk Charging: Flooded Battery Voltage | 29.2 | 58.4 |
| Bulk Charging: AGM / Gel Battery Voltage | 28.2 | 56.4 |
| Floating Charging Voltage | 27Vdc | 54Vdc |
| Max. PV Array Power | 4200W | 6500W |
| Nominal PV Voltage | 240Vdc | 360Vdc |
| PV Array MPPT Voltage Range | 60Vdc~500Vdc | |
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| Max Charging Current (AC charger plus solar charger) | 120Amp | 120Amp |
7.4 Grid-Tie Operation Specifications
| INVERTER MODEL | 3.6KW | 6.2KW |
|---|---|---|
| Nominal Output Voltage | 100/105/110/115/120VAC | |
| Feed-in Grid Voltage Range | 90~150VAC | |
| Feed-in Grid Frequency Range | 49~51±1Hz/59~61±1Hz | |
| Nominal Output Current | 30A | 51.7A |
| Power Factor Range | >0.99 | |
| Maximum Conversion Efficiency (DC/AC) | 97% | |
7.5 General Specifications
| INVERTER MODEL | 3.6KW | 6.2KW |
|---|---|---|
| Safety Certification | CE | |
| Operating Temperature Range | -10°C to 50°C | |
| Storage temperature | -15°C~60°C | |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
| Dimension (D*W*H), mm | 110X334X423 | |
| Net Weight, kg | 9 | 10 |
8. User Tips
- For Sensitive Appliances: If sensitive appliances like refrigerators experience issues when switching from mains to battery power, consider installing a capacitor to smooth out the transition.
- Reliable Backup Power: This inverter is highly effective for providing backup power during outages, capable of supporting multiple household loads.
- Longevity: To ensure long-lasting performance, adhere strictly to installation guidelines and perform regular maintenance, especially cleaning the anti-dust kit monthly.
- Monitoring: The inverter supports Wi-Fi and GPRS cloud communication for remote monitoring via a mobile app or web page, allowing you to track its status and performance.
9. Warranty and Support
For detailed warranty information, technical support, or service inquiries, please refer to the official user manual PDF or contact your local dealer or service center. The manufacturer provides a 1-year warranty.
A comprehensive user manual is available in PDF format for further details: View User Manual (PDF)