1. Introduction
The EARU EAEMP3C-100-TY-W is a 100A WiFi Smart Three Phase Energy Meter and Protector designed for comprehensive monitoring and protection of electrical systems. This device offers advanced features including bidirectional energy monitoring, various protection functions, and smart control via the Tuya app.
2. Safety Information and Precautions
- This product does not have an isolation function. Always turn off the power before performing any maintenance or repairs.
- The zero line (Neutral N line) of this product is directly connected without any disconnection function.
- The device must be wired according to the markings on the unit and installed correctly.
- Although this device has protection functions, it cannot replace a normal circuit breaker. Always install a circuit breaker upstream of this device.
- Ensure all clamp screws are tightened firmly to avoid damage due to poor contact.
3. Product Overview
3.1. Main Functions
- Over Voltage Protection
- Under Voltage Protection
- Over Current Protection
- Under Current Protection
- Delay Protection
- Timer Switch
- Bidirectional Energy Monitor
- Voltage Imbalance Protection (App configurable)
- Current Imbalance Protection (App configurable)
- Shortage Phase Protection (App configurable)
- Phase Sequence Protection (App configurable)
- High Temperature Protection (App configurable)
- Leakage Protection (Requires internal or external current transformer)
- Device Sharing
- Remote Control
- Voice Control
3.2. Display Modes
The device features two display modes to show various electrical parameters:
- Mode 1: Displays Voltage, Total Electricity Consumption, Current (Forward), Power (Reverse), Power Factor, Total Electricity Consumption, Frequency, and Total Electricity Consumption.
- Mode 2: Displays A-Phase Power Parameters, B-Phase Power Parameters, and C-Phase Power Parameters, including temperature readings.
3.3. WiFi Indicator Light Status
- Fast flashing: Indicates the device is searching for a WiFi signal.
- Slow flashing: Indicates the device is offline from WiFi.
- Long light: Indicates that WiFi is successfully connected.
4. Specifications
| Parameter | Value |
|---|---|
| Rated Supply Voltage | AC380V |
| Operation Voltage Range | AC80V-400V (Single Phase) |
| Rated Frequency | 50/60Hz |
| Rated Current | 1-100A |
| Power Display Range | 0-99999.9kWh |
| Operating Temperature | -30℃ to 70℃ |
| Protection Trip Action Time | <0.5s |
| Over Voltage Limit | 120-300V (Adjustable, Default: 275V) |
| Under Voltage Limit | 80-210V (Adjustable, Default: 175V) |
| Over Current Limit | 1-100A (Adjustable, Default: 80A) |
| Under Current Limit | 1-100A (Adjustable, Default: 10A) |
| Leakage Current Limit | 10-99A (Adjustable, Default: 29mA) |
| High Temperature Alarm | 10℃-85℃ (Adjustable, Default: 85℃) |
| Display Mode | Mode 1 or 2 (Default: Mode 1) |
| Over & Under Voltage Protection Recovery Time | 1-9999s (Adjustable, Default: 20s) |
| Over & Under Current Protection Delay | 0000-9999s (Adjustable, Default: 5s) |
| Over & Under Current Protection Recovery Time | 0000-9999s (Adjustable, Default: 20s) |
| Under & Over Voltage Protection Delay | 1-9999s (Adjustable, Default: 3s) |
| Three-Phase Current Imbalance Alarm | 10-100% (Adjustable, Default: 20%) |
| Voltage Three-Phase Imbalance Alarm | 0-100% (Adjustable, Default: 20%) |
| Lost Current Recovery Delay Time | 1-9999s (Adjustable, Default: 20s) |
| Time Threshold of Lost Flow Event | 1-999s (Adjustable, Default: 10s) |
| Energy Consumption Zero Clearing | Default OFF |
| Factory Settings Reset | Default OFF |
| Dimensions | 90*77*75.5mm |
| Accuracy Class | 1% |
| Measuring Energy Range | 0-9999999.99kWh |
| Phase | Three |
| Max Operating Current | 80A - 99A |
| Power Supply | AC |
| Display Type | LCD |
| DIY Supplies | Electrical |
| Origin | Mainland China |
| Certification | CE, FCC, RoHS, KC |
5. Installation
5.1. Installation Conditions
- Working Temperature: -30°C to 70°C
- Working Humidity: ≤85%
- Working Altitude: Not Exceeding 2000m
- Pollution Level: Level 3
- Modular design appearance and DIN rail installation.
- Wiring Capacity: Insulated copper wire under 35mm².
5.2. Wiring Diagram
Connect the device according to the following diagram. Ensure correct phase (L1, L2, L3) and neutral (N) connections. The current transformer is essential for leakage detection.
Important Note for Leakage Protection:
One zero wire and three fire wires must pass through the current transformer at the same time. Otherwise, no leakage value will be detected.
6. Initial Setup and App Pairing
6.1. Downloading the App
To use the smart features, download the "Smart Life" or "Tuya Smart" app from Google Play Store (Android) or Apple App Store (iOS). You can also scan the QR code provided in the original manual (PDF) for direct download.
A user manual in PDF format is available for more detailed instructions: User Manual (PDF)
6.2. Creating an Account
Create an account using your mobile number within the app.
6.3. Connecting to WiFi and Pairing
- Connect your mobile phone to your 2.4GHz Wi-Fi router.
- In the app, click the "+" icon in the upper right corner of the homepage or select "Add Device".
- Navigate to the "Electrical" category and select "Breaker" or "Switch module (WI-FI)".
- On the device, long-press the third key (usually labeled "OK" or "REV") on the screen that shows voltage for three seconds. The WiFi indicator light should start flashing quickly.
- Follow the on-screen instructions in the app to complete the pairing process.
7. Operation
7.1. On-Device Fault Settings
You can adjust various protection parameters directly on the device using the physical buttons:
- Long press the "OK" key to enter the settings state. The display will show the current setting.
- Use the Up/Down arrow keys to change the displayed setting value.
- Short press the "OK" key to confirm the setting on the current page and move to the next setting page.
- Long press the "OK" key again to exit the settings state and save all changes.
7.2. App Monitoring and Control
The Tuya Smart / Smart Life app provides comprehensive monitoring and control features:
- Real-time Data: View total forward energy, reverse energy, current, voltage, power factor, and more.
- Energy Statistics: Access daily, monthly, and yearly energy consumption data.
- Operation Records: Review a log of device operations (e.g., open/close events).
- Expense Management: Enable prepayment, manage balance, charge energy, and clear energy data.
8. Alarm Settings
The alarm function is automatically activated after setting the threshold. The protection tripping switch can be toggled on or off for each alarm type. All alarm settings can be configured via the mobile app.
Adjustable alarm parameters include:
- High Temperature Alarm (Default: 85℃)
- Leakage Current Limit (Default: 29mA)
- Over Current Limit (Default: 80A)
- Overvoltage Alarm (Default: 275V)
- Under Voltage Limit (Default: 175V)
- Three-Phase Current Imbalance Alarm (Default: 20%)
- Voltage Three-Phase Imbalance Alarm (Default: 20%)
- Lost Flow Alarm (Default: 10A)
- Over & Under Voltage Protection Recovery Time (Default: 20s)
- Over & Under Voltage Event Time Threshold (Default: 3s)
- Over & Under Current Protection Delay (Default: 5s)
- Over & Under Current Protection Recovery Time (Default: 20s)
- Lost Current Recovery Delay Time (Default: 20s)
- Time Threshold of Lost Flow Event (Default: 10s)
9. Scheduling and Automation
The device supports various scheduling and automation features through the app to manage power consumption efficiently:
- Timing Mode: Set specific times for the device to turn on or off (e.g., turn on living room lights at 18:00).
- Countdown Mode: Set a countdown timer for the device to turn off after a specified duration (e.g., turn off bedroom lights after 20 minutes).
- Cycle Time Mode: Schedule recurring on/off cycles (e.g., turn on at 6:00 AM and off at 9:00 AM).
- Inching: Configure the device to automatically turn off after a set period of operation once it's turned on.
10. Maintenance
To ensure optimal performance and longevity of your EARU Smart Energy Meter & Protector, follow these maintenance guidelines:
- Regularly check all wiring connections to ensure they are tight and secure. Loose connections can lead to overheating and device malfunction.
- Keep the device clean and free from dust and debris. Use a soft, dry cloth for cleaning. Do not use liquid cleaners.
- Ensure the operating environment adheres to the specified temperature (-30°C to 70°C) and humidity (≤85%) ranges.
- Periodically check for any visible signs of damage to the casing or wiring. If damage is found, disconnect power immediately and contact support.
- Keep the device away from strong electromagnetic interference.
11. Troubleshooting
Common Issues and Solutions:
- Device not powering on:
- Check the main power supply and ensure the upstream circuit breaker is on.
- Verify all wiring connections are correct and secure.
- WiFi indicator flashing slowly or not connecting:
- Ensure your router is powered on and broadcasting a 2.4GHz WiFi signal.
- Check if the device is within range of your WiFi router.
- Try long-pressing the third key on the device screen (the "OK" or "REV" button) for three seconds to re-enter WiFi pairing mode (fast flashing).
- Ensure correct WiFi password is entered in the app.
- No leakage value detected:
- Verify that one zero wire and three fire wires are correctly passed through the current transformer at the same time. Incorrect routing will prevent leakage detection.
- Ensure the current transformer is properly connected to the device.
- Protection tripping unexpectedly:
- Check the alarm settings in the app for Over Voltage, Under Voltage, Over Current, Under Current, Leakage, or High Temperature thresholds. Adjust them if they are too sensitive for your application.
- Review the "Alarm Records" in the app for details on recent trips.
- Device not responding to app commands:
- Check the device's WiFi connection status (long light indicates connected).
- Ensure your phone has an active internet connection.
- Restart the app or the device if necessary.
12. User Tips
- For optimal leakage detection, ensure the current transformer is correctly installed with all relevant wires passing through it.
- If you need to purchase a leakage coil separately, please contact the seller directly for compatible parts.
- Utilize the scheduling features in the app to automate power management and potentially save energy.
- Regularly review energy statistics in the app to understand your consumption patterns.
13. Warranty and Support
For technical support, warranty claims, or inquiries about spare parts, please contact EARU Electric directly:
- Company: ZHEJIANG EARU ELECTRONICS CO.,LTD.
- Address: YAMING ROAD 38, XIANGYANG INDUSTRY AREA, LIUSHI TOWN, YUEQING CITY, ZHEJIANG PROVINCE, CHINA
- Email: bob@earuelec.com
- Phone Number: +86 15821639630
- WeChat ID: totybest-2
Please refer to the official user manual (PDF) for any additional information or specific warranty terms.