1. Overview
The SZBJ BM500A is a digital insulation resistance tester designed for measuring the insulating resistance of various materials and electrical equipment. It offers selectable output test voltages of 250V, 500V, and 1000V, with a measurement range extending up to 1999MΩ. This compact and portable device is suitable for maintenance, testing, and inspection of electrical equipment such as transformers, motors, cables, switches, and other electrical apparatuses.
2. Safety Information
Please read and understand all safety information before operating the meter. Failure to follow these instructions may result in electric shock, fire, or damage to the meter.
2.1. Safety Marks
- Warning: Important safety information the user must read!
- Danger: High-voltage electric shock is present!
- ☐ Double-insulated protection
2.2. General Safety Precautions
- Read the operating instructions carefully before using the meter.
- It is strictly prohibited to use the meter before its rear cover is put in place. Otherwise, it might cause an electric shock.
- Check and ensure the insulating layer of the test cable is in good condition without any breakage.
- To avoid electric shock, do not touch the test cable and the circuit under test when performing a test.
- Ensure one end of the test cable is securely inserted into the terminal.
- During testing, any range must not exceed its specified maximum input value.
- During testing, do not operate the switch knob to change a range to avoid damaging the meter.
- Before performing an insulation test, ensure the range selection switch has been set within an appropriate voltage range.
- Do not perform insulation resistance tests in a combustible environment. Sparks may cause an explosion.
- Stop using the meter if its case or test cable is broken and the metal is exposed.
- When opening the rear cover for changing the battery, ensure the test cable has been removed from the test terminal and the range switch is set to the OFF position.
- Remove the battery when the meter will not be used for a long time.
- When the low battery indicator (☐) is displayed, change the battery promptly to ensure measurement accuracy.
2.3. Special Attention During Operation
- Before testing, ensure the circuit under test is not electrified. Do not measure any electrified equipment or circuit.
- During testing, dangerous voltage output exists in the meter. Operate with extreme care.
- Ensure the object under test is securely clamped and keep your hands away from the test clamp before pressing the TEST key to output high voltage.
- When using 500V measurement voltage to measure resistance less than 1.5MΩ, or 1000V to measure resistance less than 5MΩ, the measurement time must not exceed 10 seconds.
- Do not short-circuit the two test pens with high voltage output or measure insulation resistance immediately after high voltage is output. Improper operation can generate sparks, cause fire, and damage the meter.
3. Product Components
Familiarize yourself with the parts of the BM500A tester:
- LCD: Liquid Crystal Display for readings.
- Data-hold Switch (HOLD): Used to freeze the current reading on the display.
- Rotary Switch: Used to select functions and measurement ranges (OFF, 250V, 500V, 1000V, MΩ).
- L (LINE) input terminal: Connects to the line terminal of the object being tested.
- G input terminal: Shielded terminal for insulating resistance, connected to the surface of the object to prevent surface leakage.
- E (EARTH) input terminal: Connects to the EARTH terminal of the object being tested.
- TEST/STOP key: Used to initiate and stop the insulation resistance measurement.
- Indicator light of high voltage: Illuminates when high voltage is output.
4. Setup
4.1. Battery Installation
The BM500A requires a 9V battery (6F22 or NEDA 1604). Batteries are typically not included. To install or replace the battery:
- Ensure the meter is OFF and test leads are disconnected.
- Open the rear battery cover.
- Insert a new 9V battery, observing correct polarity.
- Close the battery cover securely.
4.2. Connecting Test Leads
The meter comes with a set of test leads. Connect them as follows:
- Insert the red test pen into the L (LINE) terminal socket of the meter.
- Insert one end of the test cable with a red test clamp into the E (EARTH) terminal socket of the meter.
- Insert one end of the test cable with a black test clamp into the G (shielded) terminal socket of the meter.
- Ensure all connections are secure.
5. Operating Instructions
5.1. Insulation Resistance Measurement
Follow these steps to measure insulation resistance:
- Preparation: Ensure the circuit under test is de-energized and safely discharged. The object should be securely earthed.
- Connect Test Leads: As described in Section 4.2.
- Select Rated Voltage: Turn the Rotary Switch to the desired test voltage (250V, 500V, or 1000V) for the insulation resistance test.
- Connect to Object: Connect the test pens/clamps to the appropriate terminals of the object under test (L to line, E to earth, G to shielded surface if applicable).
- Initiate Test: Press the TEST/STOP key. The red indicator light will turn on, indicating high voltage output. The actual high voltage value may be displayed on the meter. The numerical resistance value will be displayed on the LCD.
- Observe Readings: Allow the reading to stabilize. Note the measurement.
- End Test: Release the TEST/STOP key. The red indicator light will turn off, indicating high voltage output has been disconnected.
5.2. Power Off
After completing measurements:
- Release the TEST/STOP switch.
- Turn the Rotary Switch to the OFF position. The LCD screen will turn off.
- If testing capacitive loads, ensure any residual charge is discharged before removing test leads.
6. Maintenance
Warning: Always turn off the power and disconnect test leads before opening the meter case or battery cover to prevent electric shock.
6.1. Battery Replacement
When the low battery indicator (☐) is displayed, the battery needs to be changed:
- Open the battery cover.
- Replace the old 9V battery with a new one of the same type (6F22 or NEDA 1604).
- Close the battery cover securely.
6.2. Cleaning and Storage
- Keep the meter and test leads clean, dry, and undamaged.
- Use a clean cloth or a mild cleaner to wipe the meter's case. Do not use abrasive or organic solvents.
- Avoid mechanical damage, shock, and impact.
- Avoid exposure to high temperatures and strong magnetic fields.
7. Troubleshooting
- Meter does not power on or display is blank:
- Check if the rotary switch is in the OFF position.
- Verify battery installation and ensure the battery has sufficient charge. Replace if necessary (indicated by ☐).
- Inaccurate readings:
- Ensure test leads are securely connected and undamaged.
- Check battery level; low battery can affect accuracy.
- Verify the correct voltage range is selected for the measurement.
- "1" displayed for overload: The measured resistance exceeds the meter's maximum display capacity (1999MΩ). This is normal for very high resistance values.
8. Specifications
8.1. General Characteristics
- Auto Range: "1" will be displayed for overload.
- Display Mode: Liquid crystal display; maximum display: 1999.
- Sampling Rate: 2.5 times per second.
- Voltage Indication: Displays actual insulation test voltage. LED light indicates high voltage output status.
- Operating Environment: 0°C to 40°C, less than 75%RH.
- Storage Environment: -10°C to 60°C, less than 80%RH.
- Low Battery Indication: ☐ is displayed.
- Power Supply: 9V battery, 6F22 or NEDA 1604.
- Dimensions: 69mm x 138mm x 31mm (with holster).
- Weight: Approx. 170g (including battery).
8.2. Technical Characteristics (Accuracy specified for one year after calibration at 18°C to 28°C with relative humidity to 75%)
| Parameter | Specification |
|---|---|
| Rated voltage | 250V/500V/1000V |
| Open circuit voltage | 90%~110% of the rated voltage |
| Measurement range | 0.001~1999MΩ |
| Minimum Resolution | 0.001 MΩ |
| Accuracy | ±(5%RDG+5) |
| Measurement resistance value that can maintain lower limit of the rated voltage |
|
| Short circuit current | Not less than 1.5mA |
9. User Tips
- High Voltage Caution: The device operates with high voltages. Always exercise extreme caution and follow all safety guidelines to prevent injury.
- Test Lead Quality: Some users suggest that the included test leads may not be of the highest quality. Consider replacing them with higher-quality leads for improved durability and reliability, especially for frequent use.
- Batteries Not Included: Remember that the 9V battery (6F22 or NEDA 1604) required for operation is typically not included with the device. Purchase one separately before first use.
10. Warranty and Support
The product includes a conformity certificate/warranty card. Please refer to this document for specific warranty terms and conditions.
For detailed technical information and further assistance, you may refer to the official user manual PDF, which contains the comprehensive instructions and specifications for this device. The PDF can be accessed via the following link: SZBJ BM500A User Manual (PDF).
11. Frequently Asked Questions (FAQ)
- Q: How long does the battery last on a single charge/set of batteries?
- A: The battery life depends on the frequency and duration of use, particularly when performing high-voltage measurements. The meter will display a low battery indicator (☐) when replacement is needed.