1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of your Y&H 4.2KW Hybrid Solar Inverter. Please read it carefully before installation and operation, and keep it for future reference.
1.1. Product Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible with mains voltage or generator power
- Auto restart while AC is recovering
- Overload/Over temperature/Short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
- Integrated MPPT 120A Solar Charge Controller
- Battery Management System (BMS) communication support
- Wi-Fi communication for remote monitoring

Figure 1.1: Key features of the Y&H Hybrid Solar Inverter, including pure sine wave output, intelligent temperature control, multiple protection mechanisms, and a clear LCD screen with LED indicators.
1.2. Basic System Architecture
The inverter combines functions of an inverter, solar charger, and battery charger. A complete system typically includes:
- Solar PV modules
- External battery packs
- Generator or Utility grid connection
This inverter can power various appliances in home or office environments, including motor-type appliances like refrigerators and air conditioners.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with a battery.
- NEVER charge a frozen battery.
- For optimum operation, follow the required specifications to select appropriate cable sizes.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts, which could cause an explosion.
- Strictly follow the installation procedure when disconnecting AC or DC terminals.
- One 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
- NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
- Warning: Only qualified service persons are able to service this device. If errors persist after following the troubleshooting table, send the inverter/charger back to your local dealer or service center.

Figure 2.1: Comprehensive 360° protection features include Short Circuit, Over-Load, Over Charge, Over Current, Backfill, Over Voltage, Under Voltage, and Over-Temperature protection.
3. Product Overview
The Y&H 4.2KW Hybrid Solar Inverter features a user-friendly design with clear indicators and accessible ports.
3.1. Front Panel and Indicators
The front panel includes an LCD display, status indicators, and touch function buttons for easy operation and monitoring.
- LCD Display: Shows system data and operating status.
- Status Indicator (Green): Solid On for utility power, Flashing for battery/PV power.
- Charging Indicator (Green): Solid On for fully charged, Flashing for charging.
- Fault Indicator (Red): Solid On for fault, Flashing for warning.
- Touch Function Buttons: ESC, UP, DOWN, ENTER for navigation and settings.
3.2. Connections and Ports
The inverter is equipped with various input and output ports for seamless integration into your solar power system.
- Power on/off switch
- AC input
- Main output
- Second output
- PV1 and PV2 input
- WIFI communication/RS-232 port
- Battery communication/RS-485 port
- Battery input
- Anti-dust kit
4. Setup and Installation
4.1. Unpacking and Inspection
Before installation, inspect the unit for any damage. The package should contain:
- The inverter unit x 1
- User manual x 1
- Ring terminal x 1
- MC4 terminal head x 2
4.2. Preparation
Before connecting any lines, remove the screws under the machine and detach the bottom cover plate.
4.3. Mounting the Unit
Consider the following points for installation:
- Mount on a solid, non-flammable surface (concrete or other non-combustible material).
- Install at eye level for easy LCD display reading.
- Allow approximately 20 cm clearance on sides and 50 cm above/below for proper air circulation.
- Ambient temperature should be between 0°C and 55°C for optimal operation.
- The recommended installation position is vertical on a wall.
- Ensure enough space for heat dissipation and wire removal.
Install the unit using two M4 or M5 screws.
4.4. Battery Connection
CAUTION: For safety and compliance, install a separate DC over-current protector or disconnect device between the battery and inverter.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable sizes.
Recommended Battery Cable Size:
| Model | Wire Size | Cable (mm²) | Torque Value (max) |
|---|---|---|---|
| 8.2KW/10.2KW | 1 x 2AWG | 25 | 2 Nm |
Steps:
- Remove 18 mm insulation sleeve from positive and negative conductors.
- Suggest using bootlace ferrules with a proper crimping tool.
- Connect all battery packs as per the series connection diagram (e.g., four 12V batteries in series for a 48V system).
- Insert battery wires into inverter connectors, ensuring bolts are tightened to 2 Nm. Verify correct polarity at both battery and inverter terminals.
WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION: Before final DC connection, ensure positive (+) connects to positive (+) and negative (-) connects to negative (-).

Figure 4.1: The inverter supports seamless connection with multiple battery types including AGM, GEL, FLD, LI, and SLD. It also features Lithium Battery BMS Communication, specifically compatible with PylonTech.
4.5. AC Input/Output Connection
CAUTION: Install a separate AC breaker between the inverter and AC input power source (recommended 63A for 8.2KW/10.2KW).
CAUTION: Do NOT mis-connect input and output connectors (marked "IN" and "OUT").
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable sizes.
Suggested Cable Requirement for AC Wires:
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 8.2KW/10.2KW | 10 AWG | 6 | 1.2 Nm |
Steps:
- Open DC protector or disconnector first.
- Remove 10 mm insulation sleeve for six conductors. Shorten phase L and neutral N by 3 mm.
- Insert AC input wires according to polarities (Ground: yellow-green, LINE: brown/black, Neutral: blue) and tighten terminal screws.
- Insert AC output wires according to polarities (LINE: brown/black, Neutral: blue) and tighten terminal screws.
- Ensure all wires are securely connected.
WARNING: Disconnect AC power source before hardwiring.
4.6. PV Connection
CAUTION: Install a separate DC circuit breaker between the inverter and PV modules.
WARNING: Use appropriate cable sizes for PV module connection.
Suggested Cable Requirement for PV Wires:
| Model | Wire Size | Cable (mm²) | Torque Value |
|---|---|---|---|
| 8.2KW/10.2KW | 1 x 10AWG | 6 | 1.2 Nm |
PV Module Selection:
- Open circuit Voltage (Voc) of PV modules must not exceed max. PV array open circuit voltage of inverter (500Vdc).
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
- PV Array MPPT Voltage Range: 90Vdc~450Vdc.
CAUTION: Exceeding the maximum input voltage can destroy the unit! Check the system before wire connection.
PV Module Wire Connection Steps:
- Disconnect the DC circuit breaker.
- Assemble provided PV connectors with PV modules (strip cable 8mm, crimp terminals, insert into housings).
- Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive (+) to positive (+) and negative (-) to negative (-).
4.7. Final Assembly
After connecting all wirings, replace the bottom cover by screwing the two screws.
4.8. Communication Connection
The inverter supports Wi-Fi, GPRS, and direct battery communication.
- Wi-Fi Cloud Communication: Use the supplied cable to connect to the inverter and Wi-Fi module. Download the APP, set up the network, and register to monitor inverter status via mobile phone or webpage.
- GPRS Cloud Communication: Similar to Wi-Fi, use the supplied cable to connect to the GPRS module, apply external power, and use the APP for monitoring.
- Battery Communication: Realized through the battery communication interface (Baud rate: 9600) for information exchange between the inverter and lithium battery.
- Lithium Battery and Inverter Connection: Use power cables and communication cables. Ensure correct positive/negative positions. Connect the RJ45 connector of the communication cable to the BMS port of the inverter and the other RJ45 connector to the RS485 port of the lithium battery. Turn off both devices before connecting to avoid sparks.

Figure 4.2: The inverter features Wi-Fi communication, allowing users to check its operational status anytime, anywhere via a mobile application.
5. Operating Instructions
5.1. Power ON/OFF
Once the unit is properly installed and batteries are connected, press the On/Off switch (located on the side of the case) to turn on the unit.
5.2. Operation and Display Panel
The front panel includes three indicators, four function keys, and an LCD display to show operating status and power information.
5.3. LCD Display Icons and Settings
The LCD provides detailed information about the system's status. You can navigate through settings using the touch function buttons.
- Input Source Information: Icons indicate AC input, PV input, and display input voltage, frequency, PV voltage, charger current, charger power, and battery voltage.
- Configuration Program and Fault Information: Displays setting programs, warning codes, and fault codes.
- Output Information: Shows output voltage, frequency, load percent, load in VA, load in Watt, and discharging current.
- Battery Information: Displays battery status.
- Load Information: Indicates overload status.
- Mode Operation Information: Icons show connection to mains, PV panel, load supplied by utility, utility charger circuit working, and DC/AC inverter circuit working.
- Mute Operation: Indicates if the unit alarm is disabled.
To enter setting mode, press and hold the ENTER button for 3 seconds. Use UP/DOWN to select programs and ENTER to confirm or ESC to exit.
5.4. Operating Mode Description
The inverter operates in various modes:
- Standby Mode: Inverter is on but not actively supplying power from PV or battery to the load.
- Line Mode: Inverter is connected to the utility grid, which supplies power to the load and charges batteries.
- Battery Mode: Inverter supplies power to the load from batteries (and PV if available).
- Grid-Tie Operation: Inverter feeds excess solar power back to the utility grid.
- LIC (Lithium Battery Communication) Mode: Displays detailed information from the connected lithium battery BMS (e.g., total voltage, residual capacity, charging/discharge current, temperature).

Figure 5.1: The inverter offers various modes to maximize energy use and reduce electricity bills, including different solar and utility priority settings (CSO, SNU, OSO, SUB, USB, SBU) and multiple charging and discharge modes.
6. Maintenance
6.1. Clearance and Maintenance for Anti-Dust Kit
The inverter comes with a pre-installed anti-dust kit to protect internal components and enhance reliability.
Steps for Cleaning:
- Loosen the screw on the top of the inverter in a counterclockwise direction.
- Remove the dustproof case and take out the air filter foam.
- Clean the air filter foam and dustproof case.
- Re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
7. Troubleshooting
This section provides guidance for common issues, fault codes, and warning indicators.
7.1. Fault Reference Code
The LCD display will show specific fault codes if an error occurs. Refer to the table below for common fault codes and their descriptions:
| Fault Code | Fault Event | Possible Cause / What to do |
|---|---|---|
| 01 | Fan is locked | Replace fan. |
| 02 | Over temperature | Check air flow, ambient temperature. |
| 03 | Battery voltage too high | Check battery specifications. |
| 04 | Battery voltage too low | Re-charge or replace battery. |
| 05 | Output short circuited | Remove abnormal load. |
| 06 | Output voltage too high | Return to repair center. |
| 07 | Overload time out | Reduce connected load. |
| 51 | Over current or surge | Restart unit, if persists, return for service. |
Note: This is a partial list. Refer to the full user manual PDF for a complete list of fault codes.
7.2. Warning Indicator
Warning codes indicate non-critical conditions that require attention.
| Warning Code | Warning Event | Audible Alarm |
|---|---|---|
| 01 | Fan is locked when inverter is on | Beep three times every second |
| 03 | Battery is over-charged | Beep once every second |
| 04 | Low battery | Beep once every second |
| 07 | Overload | Beep once every 0.5 second |
| 6P | Battery is not connected | None |
Note: This is a partial list. Refer to the full user manual PDF for a complete list of warning indicators.
8. Specifications
8.1. General Specifications
| Parameter | Value |
|---|---|
| Model Number | MPS-VIII ECO 4.2KW |
| Output Power | 4.2KW |
| Nominal DC Input Voltage | 24Vdc |
| Nominal Output Voltage | 220/230/240VAC |
| Output Voltage Waveform | Pure Sine Wave |
| Output Frequency | 50Hz/60Hz (Auto sensing) |
| Max. PV Array Voltage | 500Vdc |
| MPPT Charging Current | 120A |
| Rated Load Power | 4200W |
| Size (L*W*H) | 420mm*310mm*110mm |
| Weight | 9KG |
| Certification | CE |
| Operating Temperature | -10°C to 50°C |
Note: For detailed specifications including Line Mode, Inverter Mode, Charge Mode, and Grid-Tie Operation, please refer to the full user manual PDF.

Figure 8.1: Front view of the inverter highlighting key specifications: 4.2KW 24V, DC 24V Battery Voltage, 90-450Vdc Max PV Input, and MPPT 120A Charging Current.
9. User Tips
- Battery Requirement: This is a hybrid solar inverter designed to work with a battery bank for energy storage, off-grid operation, and backup power. While some grid-tied inverters can operate without batteries to feed solar power directly to the grid or loads, this hybrid model's core functionality and priority settings (e.g., SBU priority) are optimized for battery integration. For full functionality, especially off-grid or backup power, batteries are essential.
- Monitoring: Utilize the Wi-Fi communication feature to monitor your system's performance and status remotely via the mobile app.
- Regular Maintenance: Clean the anti-dust kit monthly to ensure optimal performance and longevity of your inverter.
10. Warranty and Support
This Y&H Hybrid Solar Inverter comes with a 2-year warranty from the date of purchase. Please retain your proof of purchase for warranty claims.
For technical support, troubleshooting assistance beyond this manual, or warranty service, please contact your original seller or authorized Y&H service center.
Additional Resources:
A detailed user manual in PDF format is available for download: View User Manual (PDF)