1. Introduction
The TAIYEDQ TAC4371CT is a three-phase DIN rail installation multifunction energy meter. It is designed for comprehensive measurement and analysis of various power parameters, including voltage, current, four-quadrant power, power factor, and harmonic content. This meter also provides measurements for multiple electric energy parameters, such as two-way active energy, reactive energy, and daily/monthly electricity consumption statistics.
It supports RJ45 and RS485 communication interfaces with Modbus RTU and Modbus TCP protocols, allowing for remote data reading. The device features a large-screen LCD and touch-sensitive keys for local viewing and parameter configuration. Password protection ensures data security.

2. Safety Information
Read all instructions carefully before installation, operation, service, or maintenance.
- DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
- WARNING: Indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury.
- CAUTION: Indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.
- NOTICE: Used to address practices not related to physical injury.
Important Note:
- Electrical equipment must be installed, operated, serviced, and maintained only by qualified personnel.
- A qualified person is someone with skills and knowledge related to the construction, installation, and operation of electrical equipment, and has received safety training to recognize and avoid associated hazards.
3. Setup
3.1. Package Contents
Verify that your package contains the following items:
- 1 × TAC4371CT Three-Phase TCP Energy Meter
- 3 × Current Transformers (CTs)
3.2. Dimensions
The TAC4371CT meter has compact dimensions suitable for DIN rail mounting.

3.3. Mounting
The TAC4371CT is designed for standard DIN rail mounting. Ensure the DIN rail is securely installed in a suitable enclosure, providing adequate ventilation and clearance for wiring.

3.4. Wiring Diagrams
Proper wiring is crucial for the safe and accurate operation of the energy meter. Refer to the detailed diagrams below for various configurations.

Terminal Specification Parameters:
- Voltage Measurement Input Terminal: Wire size: 0.82 ~ 3.31 mm² (18 ~ 12 AWG), Torque: 0.5 ~ 0.6 N.m
- Current Measurement Input Terminal: Wire size: 1.318 ~ 3.31 mm² (16 ~ 12 AWG), Torque: 0.5 ~ 0.6 N.m
- Auxiliary Power Terminal: Wire size: 0.82 ~ 3.31 mm² (18 ~ 12 AWG), Torque: 0.5 ~ 0.6 N.m
- Communication Terminal: Wire size: 0.82 ~ 3.31 mm² (18 ~ 12 AWG), Torque: 0.5 ~ 0.6 N.m
- Fuse: A 500 mA fast fuse is recommended for auxiliary power.
3.5. Initial Power-Up
After proper wiring and connection to the power supply, the meter will undergo a self-test process. The LCD screen will display a sequence of full screen characters, software version, and self-test results (e.g.,