1. Introduction
The KONLEN WIFI digital temperature controller is designed for temperature monitoring, heating, or cooling control, with remote management via a smartphone application or manual buttons. It provides real-time temperature display, alarm notifications for temperature limits, and historical data logging. This controller is suitable for various commercial and industrial applications, including HVAC systems, thermal processes, boilers, breeding, aquaculture, incubation, and intelligent electromechanical equipment.
2. Main Features
- Real-Time Supervision: Controller and App display real-time temperature simultaneously.
- Remote Start/Stop: Control heating or cooling equipment remotely via the App.
- Preset Working Modes: Can automatically turn equipment on/off when it reaches preset temperature values for heating or cooling.
- Temperature Alarm: Set upper and lower limit values for temperature alarms, with real-time push notifications to your smartphone.
- Offline Manual Operation: Use physical buttons (CONFIG and SWITCH) to turn equipment on/off and set auto-start/stop temperature values manually when Wi-Fi is offline. Note: Alarm notifications require an active network connection.
- Time Period Control: Supports setting up to 9 groups of time-period temperature control for energy saving and consumption reduction.
- History Record: Users can check device status, alarm messages, and historical temperature curve charts from the App log.
- Compact Design: The product body size is designed to fit most power meter boxes or waterproof boxes.
3. Specifications
| Feature | Specification |
|---|---|
| Product Size | 91mm × 36mm × 59mm |
| Installation | Standard 35mm mounting rail |
| Power Supply (Version A) | AC90V to 250V |
| Power Supply (Version B) | DC5V |
| Temperature Sensor Cable | 2 meters with probe |
| Detecting Temperature Range | -40°C to +140°C |
| Measurement Error | ±1°C |
| Output | 1 relay output (normal open or normal closed) |
| Relay Lifespan | Approximately 100,000 times On/Off |
| Contact Current Capacity | 10A (resistive load), 2A (inductive load) |
| Max Resistive Load | 2000W |
| Max Motor/Water Pump Load | 400W |
| Working Environment Temperature | -10°C to 50°C |
| Package Dimensions | 13cm (Length) x 9cm (Width) x 8cm (Height) |
| Package Weight | 0.186 kg |
4. Setup
4.1 Wiring Diagram
Carefully follow the wiring diagram below. Ensure all connections are secure before applying power. The relay output acts as a switch and provides no voltage.
- Relay Output (Terminals 1, 2, 3):
- 1 & 2: Normally Closed (N.C)
- 2 & 3: Normally Open (N.O)
- 2: Common (COM)
- Note: The relay output is a switch and provides no voltage.
- Working Power Input (Terminals 4, 5):
- Version A: AC90V to 250V
- Version B: DC5V
- Temperature Sensor (Terminals 6, 7): Connect the temperature sensor here. There is no distinction between positive and negative terminals.
- Terminals 8, 9: Not used.
4.2 App Installation
- Download the Tuya Smart App from Google Play Store (for Android devices) or Apple App Store (for iOS devices).
- Install the Tuya Smart App on your smartphone.
- Register a new account using your email address.
4.3 Wi-Fi Configuration (App Device Addition)
- Before adding the temperature controller, ensure Bluetooth is enabled on your phone.
- Open the Tuya Smart App and tap the "+" icon to add a device. The app will automatically search for nearby devices.
- If the device is not found, press and hold the left button (CONFIG) on the controller for 3-5 seconds until the display shows "---". This indicates the device has entered Wi-Fi configuration mode.
- Follow the app prompts to add the device and configure its Wi-Fi connection. Note that the device only supports 2.4G Wi-Fi, not 5G Wi-Fi. Most 5G routers also include a 2.4G band; ensure your phone is connected to the 2.4G network during setup.
- Wait approximately 15 to 50 seconds for the configuration to complete.
5. Operating Instructions
5.1 App Interface Functions
The KONLEN Temp Control interface within the Tuya Smart app provides comprehensive control and monitoring. Refer to the image below for a visual guide to the numbered functions:
- Device Name: Can be edited for easy identification.
- Real-Time Temperature: Displays the current temperature detected by the sensor.
- Work Mode: Indicates whether the controller is set to Heating or Cooling mode.
- Sensor Status: Shows the current status of the temperature sensor (e.g., Normal).
- Control Relay Switch (ON/OFF): Manually turn the connected equipment on or off. Note: This manual switch is only effective when the current temperature is between the preset start and stop temperature values.
- Alarm On/Off: Enable or disable the temperature alarm function.
- Log: Access status records and historical temperature curve charts.
- Set Start-Temperature: Define the temperature at which the equipment should start operating.
- Set Stop-Temperature: Define the temperature at which the equipment should stop operating.
- Set Alarm Temperature (Lower Limit): Configure the minimum temperature threshold for an alarm.
- Set Alarm Temperature (Upper Limit): Configure the maximum temperature threshold for an alarm.
- Temperature Calibration: Adjust the temperature reading for accuracy if needed.
- Relay Output Delay: Set a time delay for the relay to activate.
- Set Control Time Period: Configure specific time intervals for temperature control.
- Set Temperature Control Schedule: Manage and view your programmed temperature control schedules.
5.2 Preset Heating or Cooling Working Mode
- Cooling Mode: When the preset start temperature is higher than the stop temperature value. For example, if the temperature is ≥25°C, the cooling equipment starts; if the temperature is ≤10°C, it stops.
- Heating Mode: When the preset start temperature is lower than the stop temperature value. For example, if the temperature is ≤5°C, the heating equipment starts; if the temperature is ≥20°C, it stops.
5.3 Setting Temperature Alarms
You can set upper and lower temperature limits to receive alarm notifications on your smartphone.
- Ensure that app notification authority is enabled on your phone (App > Me > Settings > App Notification > Enable all options).
- On the App's main interface, tap the alarm icon to enable the "alarm" function. The icon will light up. To disable alarm messages, tap the icon again to switch off the alarm light.
Example: If the temperature range is set to 12.5°C to 37.9°C, the controller will operate normally within this range. If the temperature falls below 12.5°C or rises above 37.9°C, an alarm notification will be pushed to your smartphone.
5.4 History Record
Users can inquire about the history record of device power on/off status, alarm messages, and view historical temperature curve charts directly from the App log.
5.5 Time-period Control
After setting the work mode (cooling or heating), users can add time-period controls as needed. The device supports up to 9 groups of time periods. All settings will only be active within the defined control time period, providing an effective solution for energy saving and consumption reduction.
Example: In cooling mode, with a start temperature of 30°C and a stop temperature of 15°C, if two control time periods are set (e.g., 8:00 to 10:00 and 16:00 to 18:00), the refrigeration equipment will automatically start to reduce the temperature when it exceeds 30°C during these periods, and stop when the temperature drops to 15°C. Outside these control periods, users can manually turn the relay output on or off.
5.6 Manual Control Temperature Controller
The device can be operated manually using its physical buttons, especially useful when Wi-Fi is offline. Note that time period and alarm functions are only configurable via the App.
- Enter Setting Mode: Long press the right button (SWITCH) for 2 seconds to enter the temperature value setting. The digital display will show P00 (for start temperature) or P01 (for stop temperature).
- Select Parameter: Continue to long press the right button (SWITCH) for 2 seconds to toggle between P00 and P01.
- Adjust Value:
- Short press the left button (CONFIG) to increase the set value.
- Short press the right button (SWITCH) to decrease the set value.
- Long press either button for rapid adjustment.
- Save Settings: If there is no button operation within 2 seconds, the device will automatically save the setting and return to the temperature value display.
Note: In normal working mode, long pressing the right button enters the temperature value start or stop setting. After setting the start temperature, wait 2 seconds, then select the stop temperature. The temperature adjustment step is 0.1 degrees.
6. Maintenance
- Environmental Conditions: The controller itself is not waterproof and must be located indoors. The temperature sensor with its 2-meter cable is waterproof and can be used for indoor and outdoor detection.
- Load Management: For loads larger than 2000W (resistive) or 400W (inductive motor/water pump), an external AC contactor must be added. Failure to do so can cause burning danger and damage to the device.
- Cleaning: Keep the device clean and free from dust. Use a soft, dry cloth for cleaning.
- Sensor Care: Ensure the temperature sensor probe is not damaged or kinked, as this can affect measurement accuracy.
7. Troubleshooting
- Device not found during Wi-Fi setup:
- Ensure Bluetooth is enabled on your phone.
- Press and hold the CONFIG button on the device for 3-5 seconds until "---" displays to enter Wi-Fi configuration mode.
- Wi-Fi connection issues:
- Verify your router supports 2.4G Wi-Fi. The device does not support 5G Wi-Fi.
- Ensure your phone is connected to the 2.4G network during the setup process.
- Alarm notifications not received:
- Check if app notifications are enabled in your phone's system settings.
- Confirm that the alarm function is activated (alarm icon lit) within the KONLEN Temp Control app.
- Relay not switching or equipment not responding:
- Review the wiring diagram (Section 4.1) to ensure all connections are correct and secure.
- Check if the connected load (heater/freezer) is within the specified limits (10A resistive, 2A inductive). For larger loads, an external AC contactor is required.
- Inaccurate temperature readings:
- Check the physical connection of the temperature sensor to terminals 6 and 7.
- If a known accurate reference thermometer is available, use the temperature calibration function in the app (Function 12) to adjust the reading.
- Manual control buttons not responding as expected:
- For the ON/OFF button (SWITCH) to be effective, the current temperature must be between the preset start and stop values.
- Remember that time period control and alarm functions are exclusively managed through the app.
8. User Tips
- Sensor Cable Extension: The included 2-meter sensor cable can be safely extended up to 10 meters using a standard 0.5mm² or 0.75mm² electrical cable. This extension will not negatively impact the thermostat's temperature readings.
- Sensor Type for Replacement: While not officially specified, some users have indicated that the temperature sensor might be an NTC 10 kOhm type. If you need to replace the sensor, it is advisable to verify the exact type for compatibility.
- No Power Consumption Monitoring: This device is designed solely for temperature control and does not offer features for monitoring or logging power usage statistics.
- App Experience: The controller integrates seamlessly with the Tuya Smart / SmartLife app, which is generally praised for its user-friendliness and ease of setup.
9. Frequently Asked Questions (FAQ)
- Q: Can the sensor cable be extended?
- A: Yes, the sensor cable can be extended up to 10 meters using a 0.5mm² or 0.75mm² cable without affecting the thermostat readings.
- Q: What is the temperature adjustment step?
- A: The temperature adjustment step is 0.1 degrees Celsius.
- Q: What is the maximum output current?
- A: The maximum contact current capacity is 10A for resistive loads and 2A for inductive loads.
- Q: Is this compatible with other temperature sensors like Ni1000 or NTC 10K B3950?
- A: The manual specifies a 2-meter probe. Compatibility with other sensor types is not guaranteed and should be verified by the user or manufacturer.
- Q: Does it have power usage statistics and graphs?
- A: No, this device does not monitor power usage statistics or provide graphs for power consumption.
- Q: Can recorded temperature data be downloaded?
- A: The app provides a historical temperature curve chart, but direct data download functionality is not explicitly mentioned in the instructions.
- Q: What is the maximum temperature it can handle? Can I use this in a sauna up to 90 degrees?
- A: The detecting temperature range is -40°C to +140°C for the sensor. However, the controller's working environment is -10°C to 50°C. Using the controller itself in a 90°C sauna would exceed its operational environment limits, even if the probe can withstand it.
- Q: How can I program an on/off calendar from Monday to Sunday?
- A: The device supports setting up to 9 groups of time-period temperature control via the app, which allows for scheduling operations over specific days or times.
- Q: Can the setpoint be set to 50°C?
- A: Yes, the detecting temperature range is -40°C to +140°C, so a setpoint of 50°C is well within its operational range.
- Q: Is the temperature display on the board in Celsius or Fahrenheit?
- A: The display on the device and within the app shows temperature in Celsius (°C).
10. Warranty and Support
For warranty information and technical support, please refer to the seller's policies or contact the manufacturer directly. Keep your purchase receipt for any warranty claims.
A detailed user manual in PDF format is available for download: User manual (PDF)