PowMr POW-SunSmart 10K

Contents

PowMr Dual MPPT Hybrid Solar Inverter 10KW 48V User Manual

Model: POW-SunSmart 10K

1. Introduction

The PowMr POW-SunSmart series hybrid solar inverter is an all-in-one solution combining the functions of a solar controller, AC controller, and inverter. It is designed for solar energy storage, utility charging, and AC sine wave output, suitable for both single-phase and split-phase applications. This manual provides essential information for the safe and efficient installation, operation, and maintenance of your inverter.

1.1 Key Features

  • Dual MPPT PV Input: Features two Maximum Power Point Tracking (MPPT) inputs for optimized solar energy harvesting.
  • Time-Slot Charge & Discharge: Allows setting specific time periods for charging and discharging to optimize energy usage and cost.
  • Single/Split Phase Output: Supports 100-120Vac and 200-240Vac (optional) output for versatile applications.
  • High Power Output: Rated power up to 10KW.
  • High Charging Current: Max Hybrid Charging Current of 200A and Max AC Charging of 120A.
  • Battery Compatibility: Compatible with 48V Lead-acid (AGM, GEL, Flooded) and Lithium batteries. Supports batteryless operation.
  • Comprehensive Protection: Includes 360° protection against short circuit, over current, over voltage, under voltage, overload, backfill, over-temperature, and over charge.
  • Communication Interfaces: Supports CAN, USB, and RS485 communication for monitoring and control.
  • User-Friendly Interface: LCD large screen with dynamic flow diagram for easy understanding of system data and operation status.

1.2 Unboxing and Overview

Watch this video for an unboxing and initial overview of the PowMr POW-SunSmart 10K inverter and its components.

Video: Unboxing and initial overview of the PowMr POW-SunSmart 10K inverter.

Inside the packaging, you will find the POW-SunSmart 10K inverter, an installation manual, two exploded screws, two terminals for battery cables, and a warranty card.

2. Important Safety Instructions

Please read all instructions and cautions in this manual before beginning installation or operation. Save these instructions for future reference.

DANGER

  • Installation and wiring must comply with Local and National Electric Codes (NEC) and be performed by a certified technician.
  • Do NOT disassemble or attempt to repair the inverter. There are no serviceable parts.
  • DO NOT parallel this device with other AC input sources to avoid damage.
  • DO NOT touch the unit while operating; temperatures can be very high. Do not open the terminal cover while the unit is in operation.
  • Ensure all connections are tight. Sparks may occur during connections, so keep flammable materials or gases away from the installation area.
  • Do NOT let positive (+) and negative (-) battery terminals touch each other.
  • Explosive battery gases may be present while charging. Ensure adequate ventilation.
  • Wear eye protection and have fresh water available when working with lead-acid batteries.
  • Over-charging or excessive gas precipitation can damage battery plates. Review specific battery requirements.

WARNING

  • Beware of high voltage. Turn off all power sources before and during installation to avoid electric shock.
  • For optimum operation, follow specifications for cable size and protective devices.
  • Do not connect or disconnect any connections when the inverter is working.
  • Make sure the inverter is well grounded.
  • Never cause AC output and DC input short circuits.
  • Do not disassemble this unit; for all repair and maintenance, take it to a professional service center.
  • Never charge a frozen battery.
  • Keep children away from touching or mishandling the inverter.
  • Ensure this inverter is the ONLY input power source for the load. Do not use it in parallel with other input AC power sources to avoid damage.

CAUTION

  • Do not install the inverter where highly flammable materials are nearby or in potential explosive areas.
  • Do not install the inverter with lead-acid batteries in a confined space.
  • Do not install the inverter in direct sunlight.
  • Do not install or use the inverter in a humid environment.

3. Installation and Setup

3.1 Selecting the Mount Location

The POW-SunSmart series is designed for INDOOR USE ONLY (IP20). Consider the following:

  • Choose a solid wall for installation.
  • Mount the inverter at eye level for easy access and visibility.
  • Provide adequate heat dissipation space around the inverter.
  • The ambient temperature should be between -10°C to 55°C (14°F to 131°F) for optimal operation.

3.2 Mounting the Inverter

To mount the inverter:

  1. Make 4 mounting holes in the wall using an electric drill according to the specified dimensions.
  2. Insert 2 expansion screws into the upper holes.
  3. Fix the inverter with 2 M5 screws in the lower holes.

3.3 Removing Terminal Cover and Insect Screen

Use a screwdriver to remove the terminal protection cover and the insect screen. This is necessary for wiring and maintenance. When using the device in areas with poor air quality, regularly clean the dust screen to prevent blockage by airborne particles, which can affect internal airflow and potentially trigger an over-temperature fault.

3.4 Connection Overview

A complete system consists of PV modules, a utility grid or generator, a battery, home loads, and the inverter. The inverter acts as the energy conversion device.

The inverter supports both Split-phase and Single-phase modes. Refer to the diagrams below for visual guidance.

Split-Phase and Single-Phase Wiring Diagrams
Figure: Split-Phase and Single-Phase Wiring Diagrams. Note: The open circuit voltage of PV panels in series connection must be below 500V. Over-voltage will cause damage not covered by warranty.

3.5 Cable & Circuit Breaker Requirements

Ensure correct cable diameters and circuit breaker specifications for PV input, AC input, AC output, and battery connections. Using incorrect wiring can lead to safety hazards and damage.

PV Input

ModelCable DiameterMax. PV Input CurrentCircuit Breaker Spec
8KW Model5mm² / 10 AWG22A2P-25A
10KW Model5mm² / 10 AWG22A2P-25A

AC Input

ModelOutput ModeMax. Input CurrentCable DiameterCircuit Breaker Spec
8KW ModelSplit-phase63A (L1/L2/N)13mm² / 6AWG (L1\L2\N)3P-63A
Single-phase63A (L1/L2), 126A (N)13mm² / 6AWG (L1/L2), 26mm² / 3AWG (N)2P-125A
10KW ModelSplit-phase63A (L1/L2/N)13mm² / 6AWG (L1\L2\N)3P-63A
Single-phase63A (L1/L2), 126A (N)13mm² / 6AWG (L1/L2), 26mm² / 3AWG (N)2P-125A

AC Output

ModelOutput ModeMax. Output CurrentCable DiameterCircuit Breaker Spec
8KW ModelSplit-phase42A (L1/L2/N)13mm² / 6AWG (L1\L2\N)3P-63A
Single-phase42A (L1/L2), 84A (N)13mm² / 6AWG (L1/L2), 26mm² / 3AWG (N)2P-125A
10KW ModelSplit-phase63A (L1/L2/N)13mm² / 6AWG (L1\L2\N)3P-63A
Single-phase63A (L1/L2), 126A (N)13mm² / 6AWG (L1/L2), 26mm² / 3AWG (N)2P-125A

Battery

ModelCable DiameterMax. Battery CurrentCircuit Breaker Spec
8KW Model34mm² / 2 AWG180A2P-200A
10KW Model42mm² / 1 AWG220A2P-250A

Note: The wire diameter is for reference only. If the distance between the PV array and the inverter or between the inverter and the battery is long, using a thicker wire will reduce voltage drop and improve system performance.

3.6 Wiring Connections

Always ensure circuit breakers are open before making any connections to avoid electric shock. Use appropriate tools like a wire stripper to prepare cables.

AC Input & Output Connection

Connect the live, neutral, and ground wires as shown in the diagram. Verify cable sufficiency; too thin or poor-quality cables are a serious safety hazard.

Battery Connection

Connect the positive and negative battery cables. Ensure correct polarity to prevent inverter damage.

PV Connection

Connect the positive and negative wires of the two strings of PV. The open circuit voltage of PV modules in series must not exceed 500V to prevent inverter damage.

Dry Contact Connection

Use a small screwdriver to insert the communication cable (0.2-1.5mm² diameter) into the dry junction port. This port has functions for Remote ON/OFF, ON/OFF signal output, Battery temperature sampling, and Remote generator start/stop.

Grounding Connection

Ensure the grounding terminal is connected to the Grounding Busbar. The grounding cable should have a diameter of not less than 4mm² and be as close as possible to the grounding point.

3.7 Inverter Start-up Procedure

  1. After confirming reliable wiring and correct sequence, restore the terminal cover.
  2. Close the circuit breaker of the battery.
  3. Press the rocker switch at the bottom of the inverter to ON. The screen and indicator will light up, indicating the inverter is enabled.
  4. Close the circuit breakers for PV input, AC input, and AC output in sequence.
  5. Start loads one by one, in order of power from smallest to largest.

3.8 Parallel Connection

The inverter supports parallel operation for up to six units. For detailed wiring diagrams and settings for single-phase, two-phase, and three-phase parallel connections, please refer to the full user manual (Section 10 Appendix: Parallel Connection). Key considerations for parallel operation include:

  • PV Wiring: Each inverter's PV array must be independent.
  • Battery Wiring: All inverters must be connected to the same battery bank with correct polarity.
  • AC OUT Wiring: Inverters must be connected in a consistent manner (L-to-L, N-to-N, PE-to-PE).
  • AC IN Wiring: AC source input must be consistent and unique across all parallel inverters.
  • Communication Wiring: Use a DB15 standard computer cable for parallel communication.
  • Settings: The inverter defaults to single mode. For parallel operation, specific settings (e.g., item [31] for parallel mode, item [68] for phase difference) must be configured on each inverter.

4. Operation

4.1 Operation and Display Panel

The inverter features an LCD screen, three LED indicators, and four touchable keys for operation and monitoring.

Touchable Keys

KeyDescription
Enter/ExitEnter/exit the setting menu
Up ArrowGo to the previous selection
Down ArrowGo to the next selection
ConfirmConfirm/Enter the selection in setting menu

LED Indicators

IndicatorColorDescription
AC/INVYellowSteady on: utility grid bypass output
Flash: inverter output
CHARGEGreenSteady on: charging complete
Flash: charging
FAULTRedSteady on: level-1 fault
Flash: level-2 fault
Off: level-3 fault or level-4 fault

4.2 Display Panel Icons

The display panel provides various icons to indicate system status, including PV panel, utility grid, battery, generator, inverter status, home load, communication, energy flow direction, and battery SOC/load power levels. Refer to the full manual for a complete list of icons and their meanings.

4.3 Viewing Real-time Data

From the main screen, use the UP/DOWN keys to navigate and view real-time data such as PV input voltage/current/power, battery voltage/current, AC input/output data, and general system information.

4.4 System Settings

The inverter offers extensive settings to customize its operation. Access the setup menu using the touchable keys. Key settings include:

  • AC Output Source Priority: Configure whether utility, solar, or battery has priority for powering loads.
  • AC Output Frequency: Set to 50.0Hz or 60.0Hz.
  • AC Input Voltage Range: Define the acceptable AC input voltage range (e.g., 90-140V for 120/110V output).
  • Battery to Mains/Mains to Battery Voltage Threshold: Set voltage levels for switching between battery and mains power.
  • Battery Charging Mode: Select from Hybrid Charging (SNU default), Utility Priority Charging (CUB), Solar Priority Charging (CSO), or Only Solar Charging (OSO).
  • Battery Charging Current: Adjust the maximum charging current (e.g., 0-200A for 10KW model).
  • Battery Type: Select your battery type (Sealed Lead-Acid, Flooded Lead-Acid, Gel Lead-Acid, Li-ion, or User-defined).
  • Time-Slot Charging/Discharging: Configure specific time periods for charging and discharging based on energy tariffs.
  • Power Saving Mode: Enable to reduce no-load energy losses.
  • Communication Settings: Configure RS485 communication address and BMS communication protocol.
  • AC Output Phase Mode: Set for single-phase or split-phase operation.

For a complete list of parameters and their detailed descriptions, refer to the Parameter Table in Section 9 of the full user manual.

5. Maintenance

To ensure optimum and long-lasting performance, we recommend checking the following items twice a year:

  • Ensure the airflow around the inverter is not blocked and remove any dirt or debris from the radiator.
  • Check all exposed conductors for damage (sunlight, friction, dry rot, insect/rodent damage). Repair or replace if necessary.
  • Verify that indications and displays are consistent with equipment operation. Note any faults or incorrect displays and take corrective action.
  • Check all terminals for signs of corrosion, insulation damage, high temperatures, or burning/discoloration. Tighten terminal screws.
  • Check for dirt, nesting insects, and corrosion. Clean the insect screen regularly.
  • If the lightning arrester has failed, replace it promptly to prevent damage.

DANGER: Before any inspection or operation, ensure the inverter is disconnected from all power sources and capacitors are fully discharged to avoid electric shock.

6. Troubleshooting

This section provides guidance on common fault codes and troubleshooting steps. For a comprehensive list of fault codes and their remedies, please refer to Section 7 of the full user manual.

6.1 Common Faults and Remedies

Fault CodeMeaningCausalityRemedy
/No screen displayNo power input, or device switch is off.Check battery/PV air-switch, ensure switch is ON, press any button to exit sleep mode.
01BatVoltLowBattery voltage is lower than set value [14].Charge battery until voltage is above set value [14].
03Disconnected batteryBattery not connected, or BMS in discharge protection.Check battery connection, circuit breaker, and BMS communication.
14OverloadInverterInverter output power or current overload.Reduce load power and restart. Inverter will attempt restart after 3 mins, 5 consecutive overloads will switch off output until restart.
19OverTemperMpptMPPT heat sink over-temperature.Resume normal charge/discharge when heat sink temperature cools below recovery temp.
21FanFailFan failure detected by hardware.Manually toggle fan to check for blockage. Power off/restart. If fault persists, contact service.

NOTICE: If you encounter product faults that cannot be solved by the methods listed, please contact our after-sales service department for technical support. Do not disassemble the device yourself.

7. Specifications

The PowMr POW-SunSmart 10K Hybrid Solar Inverter offers robust performance for various solar energy applications. Below are key specifications:

7.1 General Specifications (POW-SunSmart 10K)

FeatureSpecification
Rated Output Power10,000W
Max. Peak Power20,000W
Rated Output Voltage120/240Vac (split phase/single phase)
Rated AC Frequency50/60Hz
WaveformPure Sine Wave
Battery TypeLi-ion / Lead-Acid / User Defined
Rated Battery Voltage48Vdc
Max. MPPT Charging Current200A
Max. Mains/Generator Charging Current120A
Max. Hybrid Charging Current200A
Number of MPPT Trackers2
Max. PV array power5,500W/5,500W
Max. Voltage of Open Circuit500Vdc/500Vdc
MPPT Tracking Efficiency99.9%
Dimensions620*445*130mm (2*1.5*0.4ft)
Weight27kg (59.5lb)
Protection LevelIP20, Indoor Only
Operating Temperature Range-10~55°C, >45°C derated (14~131°F, >113°F derated)
Cooling MethodInternal Fan
Embedded InterfacesRS485 / CAN / USB / Dry contact
External Modules (Optional)Wi-Fi / GPRS
CertificationsCE, FCC, RoHS, IEC62109-1, IEC62109-2, UL1741, EN61000-6-1, EN61000-6-3, FCC 15 class B

For detailed specifications of POW-SunSmart 8K, POW-SunSmart 8KP, and POW-SunSmart 10KP models, please refer to the full user manual.

8. User Tips

  • Parallel Operation: When connecting multiple inverters in parallel, ensure all communication cables are securely fastened and settings for parallel mode (e.g., PAL, 0°, 120°, 180° for phase difference) are correctly configured. Incorrect settings can lead to system malfunction.
  • Battery Management: The inverter supports various battery types and offers detailed settings for charging and discharging. For Li-ion batteries, ensure the BMS communication is properly established for optimal performance and protection.
  • Voltage Configuration: For split-phase systems, verify the voltage between L1 and N, L2 and N, and L1 and L2 to match your load requirements (e.g., 120V between L1/N and L2/N, and 240V between L1/L2).
  • Monitoring: Utilize the Wi-Fi/GPRS data acquisition module (purchased separately) and the mobile APP to monitor the inverter's operation status and parameters remotely.
  • Cleanliness: Regularly check and clean the demountable insect screen and ensure adequate ventilation to prevent overheating, especially in dusty environments.

9. Warranty and Support

The PowMr Dual MPPT Hybrid Solar Inverter comes with a 24 Months Warranty.

For technical support, inquiries, or warranty claims, please contact:

SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD
Tel/Fax: +86 755-28219903
Email: support@powmr.com
Web: www.powmr.com
Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China

For the most up-to-date user manual and software, please visit the official PowMr website.

This manual is intended for informational purposes only. Specifications and features are subject to change without notice. Always refer to the latest version of the manual provided by the manufacturer.