EARUELETRIC EAPDX Series Adjustable Voltage & Current Protector User Manual

Model: EAPDX-40, EAPDX-63, EAPDX-63VAE-RGB

This manual provides detailed instructions for the installation, operation, and maintenance of your EARUELETRIC EAPDX Series Adjustable Voltage & Current Protector.

1. Introduction

The EARUELETRIC EAPDX Series is a range of adjustable digital voltage and current protectors designed to safeguard electrical appliances and circuits from over-voltage, under-voltage, and over-current conditions. Some models also include kWh energy metering functionality. These devices are suitable for DIN rail mounting and offer customizable protection parameters to suit various applications.

2. Safety Information

  • Installation and maintenance should only be performed by qualified electricians.
  • Ensure the power supply is completely disconnected before installation or any wiring changes.
  • Do not operate the device in wet or damp conditions.
  • Verify all connections are secure and correctly wired according to the diagram.
  • Do not exceed the rated voltage and current specifications of the device.
  • This device is designed for indoor use only.

3. Product Overview

The EAPDX series offers different models with varying functionalities:

  • Voltage Current Models (EAPDX-40, EAPDX-63): Display real-time voltage and current.
  • Voltage Current kWh Models (EAPDX-63VAE-RGB): Display real-time voltage, current, and accumulated kWh energy consumption.
Two models of EARUELETRIC EAPDX protectors, one displaying voltage and current, the other displaying voltage, current, and kWh.
Figure 3.1: EAPDX Voltage Current (left) and Voltage Current kWh (right) models.

Watch this video for a demonstration of the product's features and basic operation:

Video 3.1: Demonstration of EAPDX protector settings and display.

4. Specifications

General Specifications

ParameterValue
Pole No.1P+N
Rated Supply VoltageAC 220V / 230V
Operating Frequency50/60Hz
Output Contact1NO
Insulation Voltage400V
Altitude≤2000m
Operating Temperature-50°C - 55°C
Humidity≤50% at 40°C (without condensation)
Power Consumption<2W
Installation35mm symmetrical DIN rail
Diagram showing dimensions of the EAPDX protector: 36mm width, 84mm depth, 65mm height.
Figure 4.1: EAPDX Protector Dimensions.

Model-Specific Protection Ranges

Model NumberOvercurrent Protection RangeOvervoltage Protection RangeUndervoltage Protection RangeStart/Reset DelayDisplay Parameter
EAPDX-401-40A240-300V140-200V1s-300sVoltage Current
EAPDX-631-63A240-300V140-200V1s-300sVoltage Current
EAPDX-63VAE-RGB1-63A230-300V80-210V1s-600sVoltage Current kWh
Table detailing model numbers and their respective overcurrent, overvoltage, undervoltage protection ranges, start/reset delays, and display parameters.
Figure 4.2: Model-Specific Protection Ranges.

5. Installation

The EAPDX Series protectors are designed for easy installation on a 35mm symmetrical DIN rail. Follow the wiring diagrams carefully. Professional installation is highly recommended.

Wiring Diagram (EAPDX-40/63)

Wiring diagram for EAPDX-40/63 showing input (IN) and output (OUT) terminals for Neutral (N) and Live (L) wires. The diagram also shows the device dimensions.
Figure 5.1: Wiring Diagram for EAPDX-40/63 models.

Wiring Diagram (EAPDX-63VAE-RGB)

Wiring diagram for EAPDX-63VAE-RGB showing input (IN) and output (OUT) terminals for Neutral (N) and Live (L) wires. The diagram also shows the device dimensions.
Figure 5.2: Wiring Diagram for EAPDX-63VAE-RGB model.

General Wiring Steps:

  1. Mount the protector securely on a 35mm DIN rail.
  2. Connect the incoming Neutral (N) and Live (L) wires to the 'IN' terminals at the top of the device.
  3. Connect the outgoing Neutral (N) and Live (L) wires to the 'OUT' terminals at the bottom of the device.
  4. Ensure all terminal screws are tightened securely to prevent loose connections and overheating.

6. Setup and Configuration

The EAPDX series allows users to adjust various protection parameters. The display shows current settings or real-time values.

Entering Settings Mode

To enter the setting state, press and hold the SET button for more than 3 seconds.

Adjusting Parameters (EAPDX-40/63)

Once in settings mode, use the UP (▲) and DOWN (▼) buttons to navigate through the parameters (P-1 to P-6) and adjust their values. Short press SET to confirm a value and move to the next parameter. The display will show the parameter code (e.g., P-1) and its current setting.

Diagram showing the setting menu for EAPDX-40/63 models, including parameters for overvoltage, undervoltage, overcurrent, reset/start delay, and relay recovery delay.
Figure 6.1: EAPDX-40/63 Setting Menu.

Parameters for EAPDX-40/63:

  • P-1: Overvoltage setting (240-300V) - Default: 270V
  • P-2: Undervoltage setting (140-200V) - Default: 170V
  • P-3: Overcurrent setting (1A-40A/63A) - Default: 40A/63A
  • P-4: Reset/start delay (1s-300s) - Default: 5s
  • P-5: Relay recovery delay (1s-300s) - Default: 30s
  • P-6: Overcurrent Recovery Delay (1s-300s) - Default: 30s

Adjusting Parameters (EAPDX-63VAE-RGB)

The EAPDX-63VAE-RGB model has a more extensive settings menu. Use the UP (▲) and DOWN (▼) buttons to navigate and adjust values. Short press SET to confirm and move to the next parameter.

Detailed setting menu for EAPDX-63VAE-RGB, including power-on delay, protection recovery delay, over-voltage settings, undervoltage settings, over-under-voltage action delay, calibration, overcurrent settings, and reset modes.
Figure 6.2: EAPDX-63VAE-RGB Setting Menu.

Key Parameters for EAPDX-63VAE-RGB:

  • Pt: Power-on delay time (1s-600s)
  • rt: Protection recovery delay (1s-600s)
  • oU: Over-voltage protection setting (230-300V)
  • oUr: Over-voltage recovery setting (225-295V)
  • uU: Undervoltage protection setting (80-210V)
  • uUr: Undervoltage recovery setting (85-215V)
  • ULt: Over-under-voltage protection action delay time (0.1s-10s)
  • Urd: Calibration Voltage Value (-9.9V~9.9V)
  • oL: Over current protection value (1-63A)
  • CLt: Overcurrent protection action time (0.1s-60s)
  • CC: Overcurrent continuous times (0-20)
  • Crd: Current Calibration (-9.9A~9.9A)
  • PC: Power range setting (1-999)
  • CLP: Reset mode (CLP 000: Reset setting, CLP 008: Reset power level, CLP 009: Restore Factory Settings)

7. Operating Instructions

Once installed and configured, the device will continuously monitor the voltage and current of the circuit. The digital display will show the real-time values.

  • Normal Operation: The display shows the current voltage and current (and kWh for relevant models). The green indicator light (R/T) will be on.
  • Protection Trigger: If the voltage or current exceeds the set limits, the device will automatically cut off the power supply to protect connected equipment. The display may show an error code or flash the relevant parameter (e.g., >U for overvoltage).
  • Recovery: After the fault condition returns to normal and the set recovery delay time has passed, the device will automatically restore power.
  • Manual On/Off: A short press of the R/T button can manually turn the power output on or off.
  • Factory Reset: To restore factory settings, press and hold the UP (▲) and DOWN (▼) buttons simultaneously for a few seconds while in settings mode, or use the CLP 009 option in the EAPDX-63VAE-RGB settings menu.

8. Troubleshooting

  • Device does not power on: Check wiring connections (IN/OUT, N/L). Ensure the main power supply is active.
  • Voltage/Current readings are inaccurate: The device has calibration settings (Urd for voltage, Crd for current in EAPDX-63VAE-RGB models). Access the settings menu and adjust the calibration value if you have a known accurate reference meter. Some users have reported slight discrepancies (e.g., 10-12V difference) which might require manual calibration.
  • Device trips frequently: Review your set over-voltage, under-voltage, and over-current protection limits (P-1, P-2, P-3). Ensure they are appropriate for your connected load and power supply stability.
  • Device does not reset after protection: Check the relay recovery delay settings (P-5 for EAPDX-40/63, rt for EAPDX-63VAE-RGB). Ensure the delay time is sufficient. If the issue persists, try a factory reset.
  • Device does not turn on automatically or with power button after undervoltage trip (EAPDX-40/63): Some users have reported this behavior. Ensure recovery delay settings (P-5) are correctly configured. If the issue persists, a complete power cycle (disconnecting and reconnecting the main power) might be necessary, or it could indicate a specific unit issue.

9. User Tips

  • The EAPDX series is generally well-made, easy to read, and offers useful, simple functions.
  • The devices are programmable, allowing for customization to specific electrical needs.
  • For critical applications, it is advisable to verify the voltage and current readings with a calibrated multimeter and adjust the device's calibration settings if necessary.
  • Ensure the chosen model's current rating (40A or 63A) matches or exceeds your circuit's maximum expected load.

10. Maintenance

The EARUELETRIC EAPDX Series protector requires minimal maintenance.

  • Periodically check all wiring connections for tightness and signs of wear or corrosion.
  • Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning.
  • Do not use abrasive cleaners or solvents.