1. Safety Information
⚠ Warning:
- To avoid danger of suffocation, keep product packaging away from babies and children. Do not use this packaging in cribs, beds, carriages, or playpens. This bag is not a toy.
- Always ensure the power supply is disconnected before installation or maintenance.
- Installation and maintenance should only be performed by a qualified electrical professional.
This device complies with CE standards. Packaging materials should be separated and disposed of according to local recycling guidelines. For more information on waste disposal, refer to local waste management resources.
2. Product Overview
The TOMZN AC Surge Protective Device (SPD) series, including models TOV1-B, TOV1-C, and TOV1-D, is designed to protect electrical appliances and systems from transient overvoltages caused by lightning strikes or other switching events in the power grid. These devices are suitable for three-phase four-wire systems.
2.1 Function Overview
When a surge occurs in the circuit, the equipment will immediately cut off the power to protect other electrical appliances. Under normal operating conditions, the protector remains in a high resistance state. Upon detecting a surge overvoltage, it rapidly conducts within nanoseconds, diverting the surge current to the earth and protecting connected electrical equipment. Once the surge voltage dissipates, the protector automatically reverts to its high resistance state, allowing normal power grid operation.
2.2 Product Models
The TOV1 series offers different maximum discharge current capacities:
- TOV1-B: Max. Discharge Current (Imax) 60kA
- TOV1-C: Max. Discharge Current (Imax) 40kA
- TOV1-D: Max. Discharge Current (Imax) 20kA




3. Specifications
The following tables detail the technical specifications for the TOMZN TOV1 series Surge Protective Devices.
3.1 General Specifications
| Attribute | Value |
|---|---|
| Brand Name | TOMZN |
| Model Number | TOV1-B/C/D |
| Type | Other (Surge Protective Device) |
| Origin | Mainland China |
| Certification | CE |
| EU LVD Voltage | High voltage: Above 50Vac or 75Vdc |
| High-concerned chemical | None |
| Is Smart Device | No |
| is_customized | Yes |
3.2 Electrical Specifications (Type 2: 8/20µs)
| Parameter | TOV1-B | TOV1-C | TOV1-D |
|---|---|---|---|
| Rated voltage (V) | 220/380 | ||
| Input voltage (AC) | 275V, 385V, 420V | ||
| Uc | 385-420V | ||
| Nominal Discharge Current In (8/20µs) | 30kA | 20kA | 10kA |
| Max. Discharge Current Imax (8/20µs) | 60kA | 40kA | 20kA |
| Voltage Protection Level Up (kV) | ≤2.0kV | ≤1.8kV | ≤1.5kV |
| Response time (ns) | ≤25 | ||
| Ambient temperature | -40°C ~ +80°C | ||
| Shell Color | Red | Gray | Yellow |
| Module Base | Gray | ||
| Maximum wire diameter (mm²) | 35 hard wire or stranded wire | ||
| Recommended wiring (mm²) | 4-25 | ||
| Circuit breaker selection | 32A | 40-63A | 25A |
| Installation | 35mm electrical guide rail | ||
3.3 Electrical Specifications (Type 1: 10/350µs)
| Parameter | Value |
|---|---|
| Model | TOV1 |
| Applicable power supply | 220/385V-50Hz |
| Uc | 385V- |
| Iimp (10/350µs) | 15KA, 25KA, 50KA |
| In (8/20µs) | 15KA, 25KA, 50KA |
| Imax (8/20µs) | 100KA, 150KA, 200KA |
| Voltage protection level | ≤1.8V, ≤3.0KV |
| Response Time (nS) | ≤100ns |
| Operating temperature | -40°C ~ +80°C |
| Shell material | Flame retardant nylon |
| Protection level | IP20 |
| Equipped with front fuse | 125A |
| Connecting conductor cross section | 6-35mm² |
4. Installation
Important: Installation must be performed by a qualified electrical professional. Ensure the power supply is disconnected before beginning installation.
4.1 Wiring Diagram Overview
The surge protective device is designed for connection in three-phase four-wire systems, typically between the three phase lines and one neutral line to ground. The electrical schematic diagram illustrates how the protector is integrated into the circuit. For detailed wiring diagrams, including TN-S and TT systems, please refer to the complete user manual PDF.
Download the full user manual (PDF) for detailed wiring diagrams: TOMZN TOV1-B/C/D User Manual PDF
4.2 Installation Steps and Precautions
- Wire Connection: The connecting wire should have the same capacity as or larger than the power line. The total length of the connecting wire should be controlled within 0.5 meters; shorter wire length is preferable for optimal performance.
- Circuit Breaker/Fuse: A corresponding air switch or fuse must be connected in series at the front end of the surge protector.
- Power Disconnection: The power supply must be disconnected during installation to prevent electrical shock.
- Mounting: The device is designed for installation on a TH35mm wide guide rail.
- Environmental Conditions:
- Ambient temperature: -40°C to +80°C.
- Altitude: Does not exceed 2000m.
- Relative humidity: Not more than 90% (at 25°C).
- Installation location should be free from significant impact, vibration, or shaking.
- Install in a medium with no risk of explosion.
5. Operation
Once installed by a professional and connected according to wiring specifications, the surge protective device operates automatically. It continuously monitors the electrical circuit for transient overvoltages.
- Normal Operation: In the absence of surges, the device remains in a high-impedance state, allowing electricity to flow normally without interference.
- Surge Protection: Upon detecting an overvoltage event (e.g., lightning strike, switching surge), the device rapidly switches to a low-impedance state, diverting the excess current to the ground. This action protects downstream electrical equipment from damage.
- Automatic Reset: After the surge event passes, the device automatically reverts to its high-impedance state, restoring normal circuit operation.
- Parameter Adjustment: According to the instructions, adjust the equipment parameters as needed.
6. Maintenance
Regular inspection and proper storage are crucial for the longevity and effective operation of your surge protective device.
6.1 Routine Checks
- Visual Inspection: Periodically check the indicator window on the module.
- Green Indicator: Indicates normal operation.
- Red Indicator: Indicates that the module has deteriorated or failed and must be replaced immediately.
- Air Switch/Fuse: Frequently check the air switch or fuse connected in series on the line for proper function.

6.2 Storage and General Precautions
- Flammable Materials: Do not place the device near flammable materials.
- Ventilation: Ensure adequate ventilation during operation to prevent overheating.
- Extended Storage: Disconnect the device from power and store it properly when not in use for extended periods.
7. Troubleshooting
This section outlines common issues and their resolutions for the TOMZN AC Surge Protective Device.
| Problem | Possible Cause | Solution |
|---|---|---|
| Red indicator visible in module window | The surge protective module has deteriorated or failed due to a surge event. | Replace the affected module immediately. Ensure power is disconnected before replacement. |
| No power to protected equipment | The series-connected air switch or fuse has tripped/blown. | Check and reset the air switch or replace the fuse. Investigate for potential overcurrent issues. |
| Device feels excessively hot during operation | Inadequate ventilation or device operating under abnormal conditions. | Ensure sufficient airflow around the device. Verify operating parameters are within specifications. If overheating persists, consult a professional. |
If issues persist or you encounter problems not listed here, please consult a qualified electrician.
8. User Tips
- For optimal protection, ensure the grounding system is robust and correctly installed.
- Consider periodic professional inspection of your entire electrical system, including surge protection devices, especially after severe electrical storms.
- Always use the recommended wire gauges and circuit breaker ratings as specified in the installation section to ensure safety and performance.
9. Applicable Regulations and Harmonized Standards
This product conforms to the following regulations and standards:
- Low Voltage Directive (LVD) 2014/35/EU
- EN IEC 60947-1:2021
- EN IEC 60947-3:2021
10. Warranty and Support