1. Introduction
The Meterek D52-2066 is a rail-type digital display multifunction electricity meter designed for household and industrial applications. It accurately measures and displays six key electrical parameters simultaneously: AC voltage, AC current, active power, power factor, frequency, and electric energy. Its full-view color LCD screen presents data intuitively with different parameters displayed in distinct colors for easy readability.
This meter features a robust ABS insulating material housing, offering high impact resistance and durability across a wide range of temperatures. It supports one-button zeroing for power measurement and includes an automatic data saving function that retains test data during power failures, ensuring continuous accumulation upon reconnection.
2. Safety Information
- Ensure all power is disconnected before installation or maintenance to prevent electric shock.
- Installation should be performed by qualified personnel in accordance with local electrical codes and regulations.
- Do not operate the meter if it appears damaged.
- The meter is designed for AC voltage within the specified range (AC40.0-300.0V). Using it outside this range may cause damage or inaccurate readings.
- Keep the device dry and clean.
3. Package Contents
- 1 x Meterek D52-2066 Single-phase Electricity Meter
4. Installation and Wiring
4.1 Mounting
The D52-2066 meter is designed for guide rail installation. Mount the meter securely onto a standard DIN rail in your electrical panel.
4.2 Wiring Diagram
Refer to the diagram below for correct wiring. Ensure that the AC measurement input is properly connected to your circuit breakers and the load. The meter is intended to measure the electricity consumption of the entire house or a specific circuit.
4.3 External Transformer Leads
The secondary leads of an external transformer (if used) can be extended by 0.5 to 3 meters using thin wire or other suitable wires without affecting measurement accuracy.
5. Operation
5.1 Display Overview
The meter features a full-view color LCD screen that displays the following parameters simultaneously:
- AC Voltage (V)
- AC Current (A)
- Active Power (W)
- Frequency (Hz)
- Electric Energy (kWh)
- Power Factor (PF)
Each parameter is displayed in a different color for quick and easy identification.
5.2 Power Measurement Reset
The meter includes a "RESET" button (typically a small blue button on the front panel, as seen in Figure 2) for power measurement reset. Press this button to clear the accumulated electric energy (kWh) reading. This is useful for monitoring consumption over specific periods.
5.3 Data Saving Function
The D52-2066 meter is equipped with an automatic data saving function. In the event of a power failure or disconnection of the measurement voltage, the meter will automatically save the current test data. When power is reconnected, the meter will continue to accumulate data from the previously saved point, ensuring no loss of historical energy consumption records.
6. Maintenance
The meter's housing is constructed from durable ABS insulating material, providing high impact resistance and stability across various temperatures. This design minimizes the need for extensive maintenance.
- Cleaning: Use a soft, dry cloth to clean the meter's exterior. Do not use abrasive cleaners or solvents.
- Environment: Ensure the meter is installed in a dry environment, free from excessive dust, moisture, and corrosive gases.
- Inspection: Periodically check the wiring connections to ensure they are secure and free from corrosion.
7. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| No display or meter not powering on | No power supply; Loose wiring connection; Damaged meter. | Check power supply to the circuit; Verify all wiring connections are secure (refer to Section 4.2); If connections are correct and power is present, the meter may be faulty and require replacement. |
| Inaccurate readings | Incorrect wiring; External transformer issues; Meter malfunction. | Double-check wiring against the diagram (Section 4.2); Ensure external transformer (if used) is correctly rated and connected; If issues persist, contact support. |
| Electric energy (kWh) reading does not reset | Reset button not pressed correctly; Meter malfunction. | Ensure the "RESET" button is pressed firmly; If it still doesn't reset, the meter may be faulty. |
8. Specifications
| Parameter | Value |
|---|---|
| Model | D52-2066 |
| Name | Electricity Meter |
| Material | ABS |
| Measurement Accuracy | 1% ± 2 words |
| AC Voltage Measurement Range | AC40.0-300.0V |
| AC Current Measurement Range | AC0-99.9A |
| Current Display Resolution | 0.01A |
| Industrial Frequency Range | 45.0Hz-65.0Hz |
| Power Factor Range | 0.00-1.00PF |
| Active Power Range | 0-30000W |
| Active Power Display Resolution | 0.1W to 0-9999.9W |
| Electric Power Range | 0-99999kwh |
| Electric Power Display Resolution (0-999.99kwh) | 0.01kwh |
| Electric Power Display Resolution (1000.0-9999.9kwh) | 0.1kwh |
| Electric Power Display Resolution (10000-99999kwh) | 1kwh |
| Measuring Speed | Approx. 2 times per second |
| Installation Method | Guide Rail |
| Item Size | 54 * 80 * 60mm (2.13 * 3.15 * 2.36in) |
| Package Size | 85 * 65 * 60mm (3.35 * 2.56 * 2.36in) |
| Package Weight | 150g / 5.29oz |
9. User Tips
- Voltage Compatibility: The meter is compatible with 120V AC systems, falling within its specified AC40.0-300.0V range.
- Two-Phase Systems: Users have successfully employed two of these meters to monitor two-phase powered systems, such as solar installations, indicating versatility.
- Durability: The meter has been reported to function reliably for extended periods (e.g., 3 years), suggesting good long-term performance.
10. Warranty and Support
For detailed warranty information and technical support, please refer to the official product documentation or contact your retailer.
A comprehensive user manual in PDF format is available for download: View User Manual (PDF)
For further assistance, please contact Meterek customer service.