1. Product Overview
The TAIYEDQ TY-80*40 is an open-type current transformer designed for indoor use. It features a pure copper coil, dual isolation, and a flame-retardant shell. This device is used in AC lines with a rated frequency of 50-60 Hz for precise current measurement, electrical energy metering, and relay protection.

2. Safety Information
WARNING: High Voltage Hazard! Failure to follow these instructions may result in serious injury or death.
- It is strictly prohibited to open the secondary terminal of the current transformer during operation, as this will cause extremely high voltage.
- It is prohibited to open a secondary circuit during the operation of the current transformer.
- Do not connect the transformer to a fuse for use.
- Always connect the load circuit at the output end of the transformer first. Failure to do so will generate high circuit voltage at the output, exceeding normal values and endangering personnel and equipment safety.
- For open-close type transformers, always connect the secondary circuit first, and then attach the transformer to the cable.
3. Package Contents
- 1 × TAIYEDQ TY-80*40 Current Transformer
4. Specifications
| Feature | Specification |
|---|---|
| Brand Name | TAIYEDQ |
| Model Number | TY-80*40 (also TY8242) |
| Working Frequency | 50-60Hz |
| Product Shell | Load PA/UL94-VO (Flame Retardant) |
| Rated Input | 400/5A, 500/5A, 600/5A, 800/5A, 1000/5A, 1500/5A, 2000/5A (Specific to model variant) |
| Rated Output | 5A |
| Product Core | Silicon Steel |
| Product Winding | Pure Copper |
| Voltage Level | 0.66/0.72KV |
| EU LVD Voltage | Low voltage: Below 50Vac or 75Vdc |
| Working Humidity | ≤ 85% |
| Insulation Strength | 2.5KV/1mA/min |
| Working Temperature | -25 ℃ to +75 ℃ |
| Insulation Resistance | DC500V/100M Ω min |
| Output Connections | Terminal Connections |
| Installation Method | Fixed with two buttons |
| Phase | SINGLE |
| Use | Current Measurement |
| Origin | Mainland China |
| Certification | NONE |
| Wireless Functionality | No |
| Battery Included | No |
| High-concerned chemical | None |
| Customizable | Yes |
4.1. Product Dimensions (TY-80*40 Model)

| Model | Overall Dimensions (mm) | Perforation Size (mm) | Input Range (A) | Output Range | |||
|---|---|---|---|---|---|---|---|
| W | H | D | a | e | |||
| TY-40*30 | 84 | 118 | 45 | 42 | 32 | 50-600 | 1A/5A |
| TY-60*40 | 104 | 126 | 45 | 62 | 42 | 100-1500 | 1A/5A |
| TY-80*40 | 124 | 136 | 40 | 82 | 42 | 100-2000 | 1A/5A |
| TY-100*40 | 144 | 146 | 50 | 102 | 42 | 400-4000 | 1A/5A |
| TY-120*50 | 164 | 158 | 50 | 122 | 52 | 400-5000 | 1A/5A |
5. Installation and Setup
Follow these steps for proper installation of your current transformer:
- Open the Transformer: Press and hold the red button(s) on the transformer and pull it up to separate the two halves.
- Connect Secondary Circuit: Before attaching the transformer to the primary cable, ensure the secondary circuit is properly connected.
- Install on Copper Bar: After positioning the copper bar (primary conductor) in the middle of the transformer, grasp both ends of the transformer halves and press them towards the middle until they securely click into place around the copper bar.
- Secure the Transformer: Install and fix the transformer onto the copper bar using the provided M5 screws and plastic pads.

6. Operation
6.1. Operating Conditions
The transformer is suitable for the following operating conditions:
- Altitude: Does not exceed 1000 meters.
- Surrounding Medium Temperature: -30°C to +40°C.
- Relative Humidity of Air: Greater than 85%.
- Environment: Places without explosion hazards, excessive dust, and chemically corrosive gases.
The transformer is designed for long-term use at 110% of its rated current state under rated secondary load.
6.2. Wiring Instructions
The following wiring methods are applicable to most instrument manufacturers. Always refer to your specific instrument's wiring diagram for detailed connections.
- S1 Connection: The blue/yellow/red wire connects to the S1 incoming line. This typically corresponds to the rail gauge/digital display instrument/pointer strap interface.
- S2 Connection: The black wire connects to the S2 outgoing line. This normally corresponds to instruments without a specific interface for guide rail/digital display instrument/pointer meter.
- Current Direction: Ensure the current flows in the same direction as the arrow indicated on the transformer label. For example, if labeled P1 in P2 out, P1 should be towards the power supply and P2 towards the load.
- P1, P2, S1, S2 Wiring: These wiring methods require one to three directions, with a set of three. If one direction is reversed, it will impact metering accuracy.
6.3. Withstand Voltage Test
During the withstand voltage test, the withstand voltage from the primary to the secondary and ground should be 3 kV. The secondary voltage to ground should also be 3 kV for one minute.
7. Maintenance
- Magnetic Core Cleaning: If dirt adheres to the two magnetic cores in the middle of the transformer, gently wipe them clean with a washed gauze. When opening the transformer, be careful not to let sand and dust get on the surface of the magnetic core, as this can cause poor product contact and affect performance.
8. Troubleshooting
8.1. Problem: Vibration Sound After Installation
If you hear a vibration sound after installing the open-close product, consider the following solutions:
- Check for Overload: Verify if the product is operating under overload. If the actual current exceeds 1.2 times the rated current of the transformer, replace it with a higher magnification transformer.
- Clean Magnetic Cores: Dirt on the magnetic cores can cause noise. Gently wipe them clean with a washed gauze.
- Check S1 and S2 Open Circuit: An open circuit in S1 and S2 will produce noise and generate a high voltage hazard. Ensure these circuits are closed.
- Check Fixing Screws: If the four fixing screws are tightened too tightly, it can cause the two opening and closing surfaces of the transformer to open slightly, leading to poor contact and noise. Adjust the tightness if necessary.
8.2. Problem: Inaccurate Measurement
If measurements are inaccurate, consider the following:
- Lead Configuration: Do not add or remove leads. The leads are adjusted according to the product's factory configuration. Altering them may affect accuracy.
- Current Discrepancy: If the difference between the actual current and the transformer's rated current is too large, accuracy may be affected. For example, a 200/5 transformer may not accurately measure very low currents. Accuracy improves as the actual current approaches the rated current.
- Poor Product Contact: Misaligned magnetic cores, dirt obstructing the opening, or noise can all impact measurement accuracy.