LEFOO LF20-V Vacuum Pressure Switch Instruction Manual

Model: LF20-V

1. Introduction

The LEFOO LF20-V Vacuum Pressure Switch is designed to sense vacuum pressure within a system. It is widely utilized in various applications requiring precise vacuum control. Featuring a fluororubber pressure sensing diaphragm, this switch offers compatibility with a diverse range of media. The LF20-V series provides multiple pressure interfaces and wiring options to suit specific customer needs.

Two LF20-V Vacuum Pressure Switches
Figure 1: Two LF20-V Vacuum Pressure Switches, showcasing different terminal types.

2. Specifications

Below are the detailed technical specifications for the LF20-V Vacuum Pressure Switch.

LF20-V Vacuum Pressure Switch English Specification and Diagram
Figure 2: Detailed specifications and dimensional diagram of the LF20-V Pressure Switch.

2.1 Basic Parameters

ParameterValue
MediaAir, water, refrigerants and other similar hydrocarbons
Pressure Setting Range1.1 inHg - 22 inHg
Max Working PressureVacuum pressure 30 inHg
Pressure Resistance45 psi
Burst Pressure150 psi
Operating Temperature-40°C to +120°C
Diaphragm MaterialEPDM or fluoro rubber
Electrical ParametersSPST-NO (NO-C) / SPST-NC (NC-C) / SPDT-NO (Adjustable) / SPDT-NO-C-NC (Adjustable)
Terminal Blocks#8-32 screw or 1/4" plug or welding wire harness
Interface MaterialBrass/Q235/stainless steel
Interface ThreadNPT1/8, G1/8, R1/8, NPT1/4, G1/4, R1/4"
Protective CoverTriangular sheath or round sheath
EU LVD VoltageHigh voltage: Above 50Vac or 75Vdc

2.2 Electrical Rating

RatingValue
Resistive15AMP-6VDC, 8AMP-12VDC, 4AMP-24VDC
Inductive15AMP-120VAC, 0.5AMP-240VAC

2.3 Product Variants

ModelInterface ThreadCircuitryPressure Set PointAdditional Details
LF20-V1G1/8NO-55 kPa
LF20-V2G1/4NC-60 kPa
LF20-V3G1/4NC-26 kPa
LF20-V4NPT 1/8NO-4 kPa
LF20-V5NPT 1/8NO-75 kPa
LF20-V6NPT 1/4NO-60 kPaWith wire
LF20-V7NPT 1/4NO-20 kPaWith wire
LF20-V8G1/8NO-30 kPaStainless steel
LF20-V9G1/8NC-30 kPaStainless steel
LF20-V10G1/4NO-4 kPaStainless steel
LF20-V11G1/8NC-75 kPa
LF20-V12NPT1/8NO-6 kPa

3. Setup

3.1 Installation and Disassembly

  1. Use a suitable O-ring or thread-wrap PTFE tape for sealing the pressure switch to the system.
  2. Utilize an open-end wrench (complying with DIN894 or similar standards) to install and disassemble the pressure switch.
  3. Ensure that there is no steam pressure in the equipment during the installation and disassembly process to prevent burns.
LF20-V Pressure Switch with connected wiring
Figure 3: Example of LF20-V Pressure Switch with connected wiring.

3.2 Electrical Connections

The LF20-V supports various terminal types. Refer to the diagrams below for common terminal block configurations.

Terminal Block Diagrams for LF20-V Pressure Switch
Figure 4: Terminal block configurations (NO-C, NC-C, NO-C-NC, NO-C-NC (Adjust)).
  • Connect the electrical connections using a continuity tester to verify proper wiring.
  • If using a test lamp as a continuity tester, observe the maximum permissible switch capacity (refer to technical data).
  • Ensure all connections are secure and insulated as required by local electrical codes.

4. Operating Instructions

4.1 Pressure Adjustment

To adjust the pressure set point of the LF20-V switch:

  1. Use a flat-blade screwdriver to turn the pressure adjusting screw.
  2. Turn clockwise to increase the pressure set point.
  3. Turn counter-clockwise to reduce the pressure set point.
  4. When debugging the pressure switch, always pay attention to safety regulations and use a test pressure gauge to accurately set the required driving pressure.
Close-up of LF20-V Pressure Switch showing adjustment screw
Figure 5: Close-up view of the pressure adjusting screw on the LF20-V switch.

5. Maintenance

  • Regular Inspection: Periodically check the pressure switch for any signs of wear, damage, or corrosion. Ensure all connections are tight and secure.
  • Cleaning: Keep the exterior of the switch clean and free from dust, dirt, and debris. Use a soft, dry cloth for cleaning. Avoid using harsh chemicals or abrasive materials.
  • Diaphragm Check: While the fluororubber diaphragm is durable, inspect it for any cracks or punctures if the switch's performance degrades. Replacement should be done by qualified personnel.
  • Environmental Conditions: Ensure the operating environment remains within the specified temperature range (-40°C to +120°C) to prevent damage to internal components.
  • Professional Service: For any complex issues or internal repairs, it is recommended to seek assistance from a qualified technician or contact LEFOO customer support.

6. Troubleshooting

ProblemPossible CauseSolution
Switch not activating/deactivating at set pressureIncorrect pressure setting; Clogged pressure port; Faulty wiring; Damaged diaphragm.Verify and adjust pressure setting with a gauge; Check and clear pressure port; Inspect wiring for loose connections or damage; Replace switch if diaphragm is damaged.
Erratic switch behaviorPressure fluctuations in the system; Electrical interference; Loose internal components.Stabilize system pressure; Check for proper grounding and shielding; Contact support for internal inspection.
Leakage at connection pointImproper sealing (O-ring/PTFE tape); Damaged threads; Overtightening.Reapply O-ring or PTFE tape correctly; Inspect threads for damage; Ensure proper torque during installation.
No electrical continuityBroken wire; Corroded terminals; Internal switch failure.Check and repair wiring; Clean terminals; Replace switch if internal failure is confirmed.

7. User Tips

  • Verify Compatibility: Always ensure the selected LF20-V model (e.g., LF20-V1, LF20-V6) matches your system's pressure range, media, and electrical requirements (NO/NC, voltage).
  • Use Proper Sealing: For reliable operation and to prevent leaks, always use appropriate sealing materials like PTFE tape or O-rings on the threaded connections.
  • Calibrate Carefully: When adjusting the pressure set point, use a calibrated pressure gauge to ensure accuracy. Small adjustments can make a significant difference.
  • Protective Covers: If your model includes a protective cover (triangular or round sheath), ensure it is properly installed to shield the terminals from environmental factors.
  • Safety First: Always disconnect power before performing any installation, adjustment, or maintenance on the pressure switch to prevent electrical shock.

8. Warranty and Support

LEFOO products are manufactured to high-quality standards. For warranty information, technical support, or service inquiries, please contact your local distributor or refer to the official LEFOO website. Keep your purchase receipt as proof of purchase for warranty claims.