1. Introduction
The LEFOO LF32 series differential pressure switch is designed for precise monitoring of air flow in various ventilation systems. Its robust design makes it suitable for applications involving fans, filters, and ventilation ducts. Beyond air flow monitoring, it serves as a critical component for overheat protection in heating coils and frost protection in industrial cooling circuits. The switch allows for visual adjustment to suit specific operational requirements.
1.1. Applications
- Monitoring air filters and ventilation systems.
- Fan heater overheat protection.
- Controlling air and fire-protection flaps.
- Monitoring industrial cooling-air circuits.
- Monitoring flows in ventilation ducts.
- Clean room and intelligent building applications.
2. Safety Information
Please read and understand all safety instructions before installing, operating, or maintaining this device. Failure to follow these instructions may result in property damage, injury, or death.
- Electrical Safety: This device operates at high voltage (above 50Vac or 75Vdc). Installation and wiring should only be performed by qualified personnel in accordance with local electrical codes and regulations. Always disconnect power before performing any work on the switch.
- Pressure Limits: The maximum operating pressure for all LF32 models is 10kPa. Operating the switch under overpressure may cause abnormal performance and damage the device.
- Hose Connections: It is strictly prohibited to connect the pressure hoses and interfaces in reverse. Incorrect connection will prevent the switch from functioning properly.
- Physical Handling: Avoid dropping or impacting the switch, as this may damage its internal structure and affect its performance.
- Environmental Conditions: Ensure the device is installed within the specified temperature range to prevent malfunction.
3. Packing List
Verify that all items listed below are included in your package:
- LF32 series differential pressure switch (1 PCS)
- LF32 instruction manual (1 PCS)
- Plastic tube (2 PCS) and Mounting screw (4 PCS)
- 1.5m PVC hose
- L-type metal bracket (1 PCS) (optional)
- Bracket screw (4 PCS) (optional)
- Female quick plug terminal (3 PCS)
This image displays the various components typically found in the product package, such as the main switch unit, connection tubes, mounting hardware, and electrical terminals.
4. Specifications
| Feature | Detail |
|---|---|
| Max. Operating Pressure | 10kPa (all models) |
| Medium | Air, non-combustible and non-aggressive gases |
| Weight | With cover: 139g; Without cover: 100g |
| Mechanical Life | 1,000,000 cycles |
| Wire Clip Nut | PG11 or M20 |
| IP Grade | IP54 with cover; IP00 without cover |
| Temperature Range | Medium ambient: -20°C ~ +85°C; Storage: -40°C ~ +85°C |
| Electrical Rating | Resistive (inductive) load: 1.5A (0.4A) /250VAC; 0.1A/24VDC |
| Electrical Connections | 6.35x0.8 Amp standard flat plug or screw terminal |
| Pressure Connections | External diameter 6 mm, P1 (marked +) is higher connection, P2 (marked -) is lower connection |
4.1. Model Specific Pressure Ranges
| Model | Pressure Range | Differential (Diff) | Setting Point Deviation |
|---|---|---|---|
| LF32-02 | 20-200Pa | 10Pa | ≤±15%, min±10Pa |
| LF32-03 | 30-300Pa | 10Pa | ≤±15%, min±10Pa |
| LF32-03A | 20-300Pa | 10Pa | ≤±15%, min±10Pa |
| LF32-04 | 40-400Pa | 20Pa | ≤±15%, min±10Pa |
| LF32-05 | 50-500Pa | 20Pa | ≤±15%, min±10Pa |
| LF32-05A | 30-500Pa | 20Pa | ≤±15%, min±10Pa |
| LF32-06 | 60-600Pa | 20Pa | ≤±15%, min±10Pa |
| LF32-06A | 40-600Pa | 20Pa | ≤±15%, min±10Pa |
| LF32-10 | 200-1000Pa | 100Pa | ≤±15% |
| LF32-11 | 100-1000Pa | 50Pa | ≤±15% |
| LF32-15 | 100-1500Pa | 50Pa | ≤±15% |
| LF32-20 | 200-2000Pa | 100Pa | ≤±15% |
| LF32-25 | 500-2500Pa | 150Pa | ≤±15% |
| LF32-45 | 500-4500Pa | 250Pa | ≤±15% |
| LF32-50 | 1000-5000Pa | 250Pa | ≤±15% |
Note: The pressures are accurate when the switch is vertically installed. If installed horizontally with the connection terminals upward, the pressure reading will be 20Pa higher. The switches are factory-set to the first gear, and the set point can be adjusted by rotating the knob.
5. Dimensions
This diagram provides detailed measurements of the LF32 series differential pressure switch, essential for proper installation planning.
6. Installation Guide
6.1. Mounting
For optimal performance and longevity, vertical installation with the interface facing downwards is recommended. This orientation helps prevent dust and condensation from entering the switch. Installing the switch horizontally with the cover upward will result in a pressure reading that is 20Pa higher than actual. Horizontal installation with the cover facing downwards is NOT recommended.
This image shows the correct (vertical, interface down) and incorrect (horizontal) mounting positions for the differential pressure switch.
6.2. Wiring
The LF32 series supports both AMP plug connections and screw terminal connections. Ensure proper force and torque are applied during wiring to prevent damage and ensure reliable operation.
- AMP Plug Connection:
- Inserting force: ≤ 76N
- Recommended maximum torque: 0.7N-m
- Screw Connection:
- Use M4 OT terminals.
- Recommended maximum torque: 1N-m
This diagram illustrates the correct methods for connecting electrical wires using either AMP plugs or screw terminals, including recommended force and torque values.
The recommended outer diameter of the cable is 5-10mm. The recommended torque for tightening the cover screw is 1N-m.
6.3. Pressure Connections
Connect the external diameter 6 mm hoses to the pressure ports. P1 (marked +) is for the higher pressure connection, and P2 (marked -) is for the lower pressure connection. The recommended length of the hose is within 2 meters, and it should not be knotted under any circumstances. Ensure the hoses are not connected in reverse.
7. Operation
The LF32 series differential pressure switch is factory-set to the first gear. The set point can be adjusted by rotating the knob located on the device.
- To increase the pressure set point, rotate the knob clockwise.
- To decrease the pressure set point, rotate the knob anticlockwise.
This image highlights the adjustment knob used to set the desired pressure threshold for the switch, with indicators for increasing and decreasing the set point.
8. Maintenance
The LF32 series differential pressure switch requires minimal maintenance. Regular checks can ensure optimal performance and extend the product's lifespan:
- Visual Inspection: Periodically inspect the switch for any signs of physical damage, loose connections, or accumulation of dust and debris.
- Hose Integrity: Ensure that the pressure hoses are free from kinks, knots, or damage. Replace any compromised hoses immediately.
- Cleanliness: Keep the switch and its connections clean. The recommended vertical, interface-down installation helps prevent dust and condensation buildup.
- Connection Security: Verify that all electrical and pressure connections remain secure.
9. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| Incorrect Pressure Reading | Horizontal installation with terminals upward. | Re-install vertically with interface facing downwards. Adjust set point if necessary. |
| Switch Not Actuating / Malfunctioning |
|
|
| Difficulty Adjusting Set Point | Knob not rotated correctly or stiff. | Rotate knob clockwise to increase, anticlockwise to decrease. Ensure no obstructions. |
10. User Tips
No specific user tips were available from reviews or Q&A for this product. Always refer to the installation and operation guidelines for best results.
11. Warranty and Support
For detailed warranty information and technical support, please refer to the official LEFOO documentation. A comprehensive user manual in PDF format is available for download:
12. Certifications
This product complies with the following standards and certifications:
- C US (UL/CSA recognized component)
- CE (Conformité Européenne)