LEFOO LF32

Contents

LEFOO LF32 Series Differential Pressure Switch

User Manual

1. Introduction

The LEFOO LF32 series differential pressure switch is designed for precise monitoring of air flow in various ventilation systems. Its robust design makes it suitable for applications involving fans, filters, and ventilation ducts. Beyond air flow monitoring, it serves as a critical component for overheat protection in heating coils and frost protection in industrial cooling circuits. The switch allows for visual adjustment to suit specific operational requirements.

1.1. Applications

  • Monitoring air filters and ventilation systems.
  • Fan heater overheat protection.
  • Controlling air and fire-protection flaps.
  • Monitoring industrial cooling-air circuits.
  • Monitoring flows in ventilation ducts.
  • Clean room and intelligent building applications.

2. Safety Information

Please read and understand all safety instructions before installing, operating, or maintaining this device. Failure to follow these instructions may result in property damage, injury, or death.

  • Electrical Safety: This device operates at high voltage (above 50Vac or 75Vdc). Installation and wiring should only be performed by qualified personnel in accordance with local electrical codes and regulations. Always disconnect power before performing any work on the switch.
  • Pressure Limits: The maximum operating pressure for all LF32 models is 10kPa. Operating the switch under overpressure may cause abnormal performance and damage the device.
  • Hose Connections: It is strictly prohibited to connect the pressure hoses and interfaces in reverse. Incorrect connection will prevent the switch from functioning properly.
  • Physical Handling: Avoid dropping or impacting the switch, as this may damage its internal structure and affect its performance.
  • Environmental Conditions: Ensure the device is installed within the specified temperature range to prevent malfunction.

3. Packing List

Verify that all items listed below are included in your package:

  • LF32 series differential pressure switch (1 PCS)
  • LF32 instruction manual (1 PCS)
  • Plastic tube (2 PCS) and Mounting screw (4 PCS)
  • 1.5m PVC hose
  • L-type metal bracket (1 PCS) (optional)
  • Bracket screw (4 PCS) (optional)
  • Female quick plug terminal (3 PCS)
Image showing the contents of the LF32 series differential pressure switch package, including the switch, tubes, screws, and terminals.
Figure 3.1: Standard Accessories Included

This image displays the various components typically found in the product package, such as the main switch unit, connection tubes, mounting hardware, and electrical terminals.

4. Specifications

Feature Detail
Max. Operating Pressure 10kPa (all models)
Medium Air, non-combustible and non-aggressive gases
Weight With cover: 139g; Without cover: 100g
Mechanical Life 1,000,000 cycles
Wire Clip Nut PG11 or M20
IP Grade IP54 with cover; IP00 without cover
Temperature Range Medium ambient: -20°C ~ +85°C; Storage: -40°C ~ +85°C
Electrical Rating Resistive (inductive) load: 1.5A (0.4A) /250VAC; 0.1A/24VDC
Electrical Connections 6.35x0.8 Amp standard flat plug or screw terminal
Pressure Connections External diameter 6 mm, P1 (marked +) is higher connection, P2 (marked -) is lower connection

4.1. Model Specific Pressure Ranges

Model Pressure Range Differential (Diff) Setting Point Deviation
LF32-0220-200Pa10Pa≤±15%, min±10Pa
LF32-0330-300Pa10Pa≤±15%, min±10Pa
LF32-03A20-300Pa10Pa≤±15%, min±10Pa
LF32-0440-400Pa20Pa≤±15%, min±10Pa
LF32-0550-500Pa20Pa≤±15%, min±10Pa
LF32-05A30-500Pa20Pa≤±15%, min±10Pa
LF32-0660-600Pa20Pa≤±15%, min±10Pa
LF32-06A40-600Pa20Pa≤±15%, min±10Pa
LF32-10200-1000Pa100Pa≤±15%
LF32-11100-1000Pa50Pa≤±15%
LF32-15100-1500Pa50Pa≤±15%
LF32-20200-2000Pa100Pa≤±15%
LF32-25500-2500Pa150Pa≤±15%
LF32-45500-4500Pa250Pa≤±15%
LF32-501000-5000Pa250Pa≤±15%

Note: The pressures are accurate when the switch is vertically installed. If installed horizontally with the connection terminals upward, the pressure reading will be 20Pa higher. The switches are factory-set to the first gear, and the set point can be adjusted by rotating the knob.

5. Dimensions

Technical drawing showing the dimensions of the LF32 differential pressure switch from multiple views.
Figure 5.1: Product Dimensions

This diagram provides detailed measurements of the LF32 series differential pressure switch, essential for proper installation planning.

6. Installation Guide

6.1. Mounting

For optimal performance and longevity, vertical installation with the interface facing downwards is recommended. This orientation helps prevent dust and condensation from entering the switch. Installing the switch horizontally with the cover upward will result in a pressure reading that is 20Pa higher than actual. Horizontal installation with the cover facing downwards is NOT recommended.

Diagram illustrating recommended vertical installation and non-recommended horizontal installations for the pressure switch.
Figure 6.1: Recommended Installation Orientation

This image shows the correct (vertical, interface down) and incorrect (horizontal) mounting positions for the differential pressure switch.

6.2. Wiring

The LF32 series supports both AMP plug connections and screw terminal connections. Ensure proper force and torque are applied during wiring to prevent damage and ensure reliable operation.

  • AMP Plug Connection:
    • Inserting force: ≤ 76N
    • Recommended maximum torque: 0.7N-m
  • Screw Connection:
    • Use M4 OT terminals.
    • Recommended maximum torque: 1N-m
Wiring diagrams for AMP plug and screw terminal connections, showing proper insertion and torque specifications.
Figure 6.2: Electrical Connection Details

This diagram illustrates the correct methods for connecting electrical wires using either AMP plugs or screw terminals, including recommended force and torque values.

The recommended outer diameter of the cable is 5-10mm. The recommended torque for tightening the cover screw is 1N-m.

6.3. Pressure Connections

Connect the external diameter 6 mm hoses to the pressure ports. P1 (marked +) is for the higher pressure connection, and P2 (marked -) is for the lower pressure connection. The recommended length of the hose is within 2 meters, and it should not be knotted under any circumstances. Ensure the hoses are not connected in reverse.

7. Operation

The LF32 series differential pressure switch is factory-set to the first gear. The set point can be adjusted by rotating the knob located on the device.

  • To increase the pressure set point, rotate the knob clockwise.
  • To decrease the pressure set point, rotate the knob anticlockwise.
Image of the LF32 differential pressure switch showing the adjustment knob and its markings for setting pressure.
Figure 7.1: Adjustment Knob

This image highlights the adjustment knob used to set the desired pressure threshold for the switch, with indicators for increasing and decreasing the set point.

8. Maintenance

The LF32 series differential pressure switch requires minimal maintenance. Regular checks can ensure optimal performance and extend the product's lifespan:

  • Visual Inspection: Periodically inspect the switch for any signs of physical damage, loose connections, or accumulation of dust and debris.
  • Hose Integrity: Ensure that the pressure hoses are free from kinks, knots, or damage. Replace any compromised hoses immediately.
  • Cleanliness: Keep the switch and its connections clean. The recommended vertical, interface-down installation helps prevent dust and condensation buildup.
  • Connection Security: Verify that all electrical and pressure connections remain secure.

9. Troubleshooting

Problem Possible Cause Solution
Incorrect Pressure Reading Horizontal installation with terminals upward. Re-install vertically with interface facing downwards. Adjust set point if necessary.
Switch Not Actuating / Malfunctioning
  • Hoses knotted or too long (>2m).
  • Hoses or interfaces connected in reverse.
  • Operating under overpressure (>10kPa).
  • Physical damage from dropping/impact.
  • Ensure hoses are straight and within 2m length.
  • Verify correct P1 (+) and P2 (-) connections.
  • Ensure operating pressure is within specified limits.
  • Inspect for damage; replace if necessary.
Difficulty Adjusting Set Point Knob not rotated correctly or stiff. Rotate knob clockwise to increase, anticlockwise to decrease. Ensure no obstructions.

10. User Tips

No specific user tips were available from reviews or Q&A for this product. Always refer to the installation and operation guidelines for best results.

11. Warranty and Support

For detailed warranty information and technical support, please refer to the official LEFOO documentation. A comprehensive user manual in PDF format is available for download:

View User Manual (PDF)

12. Certifications

This product complies with the following standards and certifications:

  • C US (UL/CSA recognized component)
  • CE (Conformité Européenne)