1. Introduction
The TAIYEDQ BH-0.66-30 Current Transformer (CT) is designed for indoor use in AC circuits with a rated voltage of 0.66kV and below, and a rated frequency of 50/60Hz. It is primarily used for current electric energy measurement and relay protection applications.
This product features a new shell type design, allowing for flexible installation using either busbar or fixed plate mounting methods. It is suitable for installation in any direction and can accommodate wires for busbars or cables.
2. Safety Information
- Always ensure power is disconnected before installation, wiring, or maintenance.
- Installation should only be performed by qualified personnel familiar with electrical systems and safety procedures.
- Do not exceed the rated primary current, secondary current, or voltage specifications.
- Ensure proper grounding where applicable.
- Avoid touching live terminals.
- Inspect the CT for any physical damage before installation.
3. Product Overview
The BH-0.66-30 series current transformer is a toroidal type device designed for accurate current measurement. It features primary (P1) and secondary (S1, S2) terminals, and a central opening for the primary conductor.
Figure 1: Front view of the BH-0.66-30 Current Transformer. The label shows primary current, VA rating, class, secondary current, frequency, and voltage.
Figure 2: Detailed view of the product label, indicating specifications such as Primary 150A, 5/3.75VA, Class 0.5, Secondary 5A, 50/60Hz, 660V.
Video 1: A 360-degree view of the BH-0.66-30 Current Transformer, showcasing its physical design and included mounting accessories.
4. Setup and Installation
Before installation, ensure the power supply to the circuit where the CT will be installed is completely disconnected.
4.1 Mounting
The BH-0.66-30 CT can be mounted using either a busbar or a fixed plate. Mounting accessories (screws and brackets) are typically included.
- Busbar Mounting: Slide the CT onto the busbar. Secure it using the provided brackets and screws if necessary.
- Fixed Plate Mounting: Use the mounting holes on the CT base to secure it to a panel or plate with appropriate screws.
4.2 Wiring
Refer to the following diagram for wiring connections. Ensure all connections are tight and secure.
Figure 3: Dimensional drawing and terminal markings. P1 indicates the primary side where the main current flows, and S1/S2 are the secondary terminals for connection to measuring instruments.
- Primary Connection (P1): The main conductor (busbar or cable) carrying the current to be measured must pass through the central hole of the CT. Ensure the direction of current flow is consistent with the markings (P1).
- Secondary Connection (S1, S2): Connect the S1 and S2 terminals to the input terminals of your measuring instrument (e.g., ammeter, energy meter, relay).
- Polarity: Observe polarity markings (P1, S1, S2) to ensure correct measurement and protection operation.
5. Operating Instructions
Once installed and wired correctly, the current transformer operates passively by inducing a proportional current in its secondary winding. The secondary current (typically 5A) can then be safely measured by connected instruments.
- Ensure the primary current does not exceed the rated primary current of the CT.
- The secondary circuit of the CT should always be connected to a load (e.g., ammeter) or short-circuited when not in use. Never operate a CT with an open secondary circuit, as this can lead to dangerously high voltages across the secondary terminals.
6. Maintenance
The TAIYEDQ BH-0.66-30 Current Transformer is designed for long-term, maintenance-free operation under normal conditions.
- Periodically inspect the CT for any signs of physical damage, overheating, or loose connections.
- Keep the CT clean and free from dust and moisture. Use a dry, soft cloth for cleaning.
- Ensure the primary conductor passing through the CT is free from insulation damage.
7. Troubleshooting
7.1 No Reading or Incorrect Reading on Measuring Instrument
- Check Connections: Ensure all primary and secondary wiring connections are secure and correct according to the wiring diagram.
- Check Polarity: Verify that the polarity of the CT (P1, S1, S2) matches the requirements of the measuring instrument.
- Check Primary Current: Confirm that there is actual current flowing through the primary conductor.
- Check Measuring Instrument: Test the measuring instrument with a known current source to ensure it is functioning correctly.
- CT Rating: Ensure the CT's primary current rating matches the expected maximum current of the circuit.
7.2 Overheating
- Overload: The primary current may be exceeding the CT's rated primary current. Reduce the load or replace the CT with one of a higher rating.
- Open Secondary: An open secondary circuit can cause dangerous voltage and overheating. Ensure the secondary circuit is always closed through a load or short-circuited.
- Loose Connections: Check for any loose connections that could cause resistance and heat generation.
8. Specifications
| Parameter | Value |
|---|---|
| Model Number | BH-0.66-30 |
| Primary Current Ratio | 100A, 150A, 200A, 250A, 300A, 400A (selectable) |
| Secondary Current | 5A |
| Rated Voltage | 0.66kV / 660V |
| Rated Frequency | 50/60Hz |
| Accuracy Class | 0.5 |
| Rated Output (VA) | Typically 3.75VA (may vary by specific model/ratio) |
| Window Size (Hole Diameter) | 30mm |
| Coil Structure | Toroidal |
| Phase | Single Phase |
| Dimensions (Approx.) | Height: 81mm, Length: 61mm, Width: 34mm |
Figure 4: The BH-0.66-30 series is available in various primary current ratings from 100A to 400A.
9. User Tips
No specific user tips were available from provided reviews or Q&A content for this product.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your retailer or the manufacturer directly. Please have your product model number and purchase details ready when contacting support.
A detailed user manual in PDF format may be available for download from the manufacturer's website or provided by your seller. (Reference: User Manual PDF)