1. Product Description
The TAIYEDQ HB011 is a data acquisition module designed for real-time measurement of eight-channel AC current. It utilizes high-precision current transformers for signal isolation and sensing. The module incorporates a special true RMS measurement chip, enabling accurate measurement of various waveform currents. It offers high precision and good stability, communicating via a standard RS-485 bus interface using the MODBUS-RTU protocol.
Key Features:
- Eight channels of simultaneous sampling, each independent.
- High precision and excellent stability.
- Current perforation input for easy installation and use.
- Measures true RMS values.
- Default Modbus-RTU standard protocol, RS485 communication output.
- Supports integration with PLCs, configuration software, touch screens, wireless DTU modules, and serial communication.
2. Setup and Installation
2.1. Wiring Diagram
Ensure all power is disconnected before performing any wiring. Follow the diagram below for correct connections.

This diagram illustrates the connections for AC power supply (L, N), the load under test (passing through the current transformers), DC power supply (9-30V to 24V/0V terminals), and RS485 output (A/B terminals) to a serial converter, PLC, or touch screen.
Connection Steps:
- AC Power Supply: Connect your AC power lines (L and N) to the circuits you intend to monitor. These lines will pass through the current transformers (channels 1-8).
- Load Under Test: Ensure the current-carrying wire of the load passes through the center of each respective current transformer on the module.
- DC Power Supply: Connect a DC power source (9-30V) to the green terminal block. Connect the positive (+) lead to the '24V' terminal and the negative (-) lead to the '0V' terminal.
- RS485 Output: Connect your RS485 communication device (e.g., PLC, serial converter, touch screen) to the 'A' and 'B' terminals on the green terminal block.
2.2. DIP Switch Configuration (HB-CT8-JC)
The module features four DIP switches for configuration:
- Switches 1, 2, and 3 (Station Number Configuration): These switches, in conjunction with the basic station number (W100, default = 30), determine the module's communication station number. The address selection uses an 8421 code: switch 1 corresponds to 1, switch 2 to 2, and switch 3 to 4. Setting a switch to 'ON' makes its value valid. Sum the valid numbers and add 30 to get the communication address.
Example: If switch 1 is ON, switch 2 is OFF, and switch 3 is ON, the calculation is (1 + 0 + 4) + 30 = 35. The module's address will be 35. - Switch 4 (System Initialization): To initialize system parameters, first power off the module. Set switch 4 to the 'ON' position. Power on the module and wait for the work light to illuminate. Immediately after, power off the module again and set switch 4 back to the 'OFF' position. Power on the module again. This process will reset parameters to their default values.
3. Operating Instructions
3.1. Communication Protocol
The module operates using the Modbus RTU protocol in slave mode, connected via RS485. Parameter modifications (except for the communication station number) require a power cycle to take effect. The maximum baud rate is 115200bps, and the module automatically adapts to the host computer's baud rate.
Communication Parameters:
| Address (Decimal) | Name | Range (Default) | Function Description |
|---|---|---|---|
| W100 | Communication Station Number | 1-220 (30) | Forms the station number with DIP switches 1, 2, 3. |
| W101 | Communication Station Number Parity | 0-2 (2) | 0=None, 1=Odd, 2=Even |
| W102 | Communication Baud Rate | 0-4 (3) | Automatically adapts to host baud rate. |
| W103 | Communication Stop Bit | 0-3 (1) | 0=0.5 bits, 1=1 bit, 2=2 bits, 3=1.5 bits |
| W104 | Communication Data Length | 7-8 (8) | 7-bit or 8-bit data |
Basic Data Description:
| Name | Meaning | Read/Write | Address (Decimal) | Illustration |
|---|---|---|---|---|
| T | Measurement Period | Read Only | W1 | Cannot be set |
| AH1~AH8 | Upper Limit Alarm Value | Read and Write | W2~W9 | See example description |
| AL1~AL8 | Lower Limit Alarm Value | Read and Write | W10~W17 | See example description |
| VER | Program Version | Read Only | W59 | Module version (numbers) |
| ALM | Alarm Status | Read Only | W61 | See Note 1 for details |
| PV1~PV8 | Current Measurement | Read Only | W86~W93 | Unit 0.1A |
Note 1: Bit Interpretation of Alarm Status (W61) provides detailed status for each channel's upper and lower limit alarms.
3.2. Serial Communication Example
To read 8 channel current values (8 registers starting from W86):
- Send (Hexadecimal):
1E 03 00 56 00 08 A6 73
(Address: 1E, Function Code: 03, Initial Address: 0056, Number of Registers: 0008, CRC Check: A673) - Receive (Hexadecimal):
1E 03 10 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 2D 86
Receive Data Description:
- 1st byte (1E): Device address
- 2nd byte (03): Read register function code
- 3rd byte (10): Number of data bytes (8 registers * 2 bytes/register = 16 bytes, represented as 10h)
- Bytes 4-19: Values of channels 1 to 8 (each value is 2 bytes)
- Bytes 20 and 21: CRC check value

The module can be integrated with various PLCs, touch screens, configuration systems, industrial computers, laptops, and instrumentation via serial connection.
4. Maintenance
The TAIYEDQ HB011 module is designed for reliable operation with minimal maintenance. To ensure optimal performance and longevity:
- Keep Clean: Periodically clean the module and its surroundings to prevent dust accumulation, which can affect performance and heat dissipation.
- Ensure Ventilation: Ensure the module is installed in an area with adequate ventilation to prevent overheating.
- Check Connections: Periodically inspect all wiring connections (power, load, RS485) to ensure they are secure and free from corrosion or damage.
- Environmental Conditions: Operate the module within the specified environmental conditions (temperature and humidity) to prevent damage.
5. Troubleshooting
If you encounter issues with the module, refer to the following troubleshooting steps:
5.1. LED Indicators
- POW Light (Power Indicator): If the POW light is always on, the module is powered normally. If it is off, check the DC power supply connection.
- COM Light (Communication Indicator): If the COM light flashes, communication is normal. If the COM light is off, communication is not successful.
5.2. Communication Issues
- Check RS485 Wiring: Ensure the 'A' and 'B' terminals are correctly connected to your communication device.
- Verify Modbus Settings: Confirm that the station number, baud rate, parity, data bits, and stop bits configured in your host device match the module's settings (or defaults).
- DIP Switch Settings: Double-check the DIP switch settings for the station number.
- Host Device: Ensure your host communication device (PLC, PC, etc.) is functioning correctly and its Modbus master settings are accurate.
5.3. Inaccurate Readings
- Load Connection: Ensure the current-carrying wire of the load passes correctly through the center of the current transformer.
- Current Range: Verify that the measured current is within the module's specified range (0-50A).
- Module Integrity: If issues persist, inspect the module for any visible damage.
6. Specifications
| Parameter | Value |
|---|---|
| Brand Name | TAIYEDQ |
| Model Number | HB011 |
| Rated Voltage | DC 24V (Max. allowable ripple voltage 5%) |
| Max. Power Consumption | 100mA |
| Working Temperature | -20°C to 50°C |
| Relative Humidity | 35%~85% (non-condensing) |
| Current Range | 0~50A AC |
| Precision | 0.1A |
| Basic Error | ±1%FS |
| Sampling Period | 0.1S |
| Output Interface | RS485 (Modbus-RTU Standard Protocol) |
| Default Communication Parameters | Station 30, 9600bps, Even Parity, 8 Data Bits, 1 Stop Bit |
| Dimensions (8-Channel) | 145mm x 90mm x 40mm |
| Dimensions (4-Channel) | 114mm x 42mm x 30mm |
| Installation Method | 35mm DIN Rail or Screw Installation |
| Origin | Mainland China |
| Certification | NONE |
| Wireless Functionality | No |
| Battery Included | No |
| EU LVD Voltage | Low voltage: Below 50Vac or 75Vdc |
Dimensions:

Dimensions: 114mm (length) x 42mm (width) x 30mm (height).

Dimensions: 145mm (length) x 90mm (width) x 40mm (height).
7. User Tips
- Modbus Protocol Details: For advanced Modbus integration or if you require a more in-depth understanding of the protocol, refer to the official Modbus RTU specification for detailed register maps and function codes beyond what is covered in this manual.
- Power Supply Stability: Ensure a stable DC 24V power supply is used, as voltage fluctuations can affect measurement accuracy and communication reliability.
8. Warranty and Support
For any warranty claims, technical support, or further inquiries regarding the TAIYEDQ HB011 module, please contact your seller or the manufacturer directly.
For comprehensive documentation and additional details, please refer to the official user manual PDF available at: User Manual (PDF)