ComWinTop CWT-TM-8PT

Contents

ComWinTop CWT-TM-8PT Temperature Acquisition Module User Manual

8-Channel PT100/PT1000 RS485 Modbus Output

1. Introduction

The ComWinTop CWT-TM-8PT is an 8-channel temperature acquisition module designed for industrial applications. It supports PT100 and PT1000 RTD sensors and communicates via RS485 using the Modbus RTU protocol. This manual provides essential information for the proper installation, operation, and maintenance of the module.

Front view of ComWinTop CWT-TM-8PT Temperature Acquisition Module

Figure 1: Front view of the CWT-TM-8PT Module, showing terminal blocks and labels.

Video 1: Product overview of the CWT-TM-8PT module.

2. Setup

2.1. Physical Installation

The CWT-TM-8PT module is designed for 35mm DIN-rail mounting.

Bottom view of the module with DIN-rail mounting clips

Figure 2: Bottom view showing the red DIN-rail mounting clips.

Side view of the module with ventilation slots

Figure 3: Side view of the module, highlighting ventilation slots.

2.2. Power Supply

The module requires a DC power supply within the range of 8V to 30V.

2.3. Terminal Connections

Refer to the table below for detailed terminal descriptions:

Table of terminal descriptions for CWT-TM-8PT

Figure 4: Terminal description table.

2.4. PT100/PT1000 Sensor Wiring

The module supports both two-wire and three-wire connections for PT100/PT1000 sensors. Ensure correct wiring as shown in the diagrams below.

PT100/PT1000 two-wire and three-wire connection diagrams

Figure 5: PT100/PT1000 wiring diagrams. For two-wire connections, short RTD(n)- and GND.

3. Operating Instructions

3.1. RS485 Modbus RTU Communication

The module communicates using the Modbus RTU protocol over RS485. The default communication parameters are:

  • Baud Rate: 9600 bps
  • Parity: None (n)
  • Data Bits: 8
  • Stop Bits: 1
  • Default Device Address: 1

3.2. Modbus Register Maps

The module uses specific Modbus registers for configuration and data acquisition.

3.2.1. Parameter Register Map (Function Code: 03H Read, 06H Write)

Modbus parameter register map table

Figure 6: Modbus parameter register map for communication settings and device address.

3.2.2. Data Register Map (Function Code: 03H Read)

Modbus data register map table

Figure 7: Modbus data register map for reading temperature values from channels.

3.3. Configuration Tool

A dedicated configuration tool is provided to simplify the setup and testing of the module. This tool allows you to set communication parameters, device address, and read sensor data.

Screenshot of the CWT-TM-8PT configuration tool

Figure 8: Screenshot of the module's configuration tool interface.

4. Maintenance

The CWT-TM-8PT module is designed for robust operation with minimal maintenance. To ensure optimal performance:

  • Keep the module clean and free from dust and debris.
  • Periodically check all wiring connections for tightness and integrity.
  • Ensure the operating environment remains within specified temperature and humidity ranges.

5. Troubleshooting

  • Module not responding after changing ID: If the module stops responding after changing its Modbus ID, ensure the new ID is valid (1-250) and that your communication software is configured to use the new ID. If issues persist, try resetting the module if a reset procedure is available (refer to the PDF manual if provided) or contact support.
  • Communication issues: Verify RS485 wiring (A to A, B to B). Ensure a 120-ohm termination resistor is added to both ends of the RS485 bus, as the module does not have one built-in. Check baud rate, parity, and stop bits match the module's settings.
  • Incorrect temperature readings: Double-check PT100/PT1000 sensor wiring. For two-wire connections, ensure RTD- is properly shorted to the nearest GND pin. Verify sensor type (PT100 or PT1000) matches module configuration.
  • No power: Check power supply connections and ensure voltage is within the 8V-30V DC range.

6. Specifications

Table of basic parameters and specifications for CWT-TM-8PT

Figure 9: Basic parameters and specifications of the CWT-TM-8PT module.

6.1. Dimensions

Diagram showing physical dimensions of the CWT-TM-8PT module

Figure 10: Physical dimensions: 14.5cm (L) x 8.9cm (W) x 4cm (H).

7. User Tips

  • Termination Resistor: Always add a 120-ohm termination resistor at both ends of your RS485 bus, as this module does not have one built-in. This is crucial for stable communication.
  • Wiring RTD-: For two-wire PT100/PT1000 connections, ensure the RTD- terminal is connected to the nearest GND pin for accurate readings.
  • Software Tool: For scanning and configuration, tools like OpenModScan can be very versatile and helpful.
  • PDF Manual: A detailed user manual in PDF format may be available for further reference. Please check the product page or contact the seller for the PDF document: User Manual (PDF).

8. Warranty and Support

For warranty information, technical support, or any issues not covered in this manual, please contact the seller directly. Provide your order details and a clear description of the problem for efficient assistance.

© 2024 ComWinTop. All rights reserved.