2-Channel PT100/PT1000 RS485 Modbus Temperature Acquisition Module User Manual

Model: CWT-TM-2PT

1. Introduction

This manual provides detailed instructions for the installation, operation, and maintenance of your ComWinTop 2-Channel PT100/PT1000 RS485 Modbus Output Temperature Acquisition Module. This device is designed for precise temperature measurement using PT100 or PT1000 sensors and communicates data via the RS485 Modbus RTU protocol.

Front view of the 2-channel PT100/PT1000 RS485 Transmitter module.

Figure 1: ComWinTop 2-Channel PT100/PT1000 RS485 Transmitter Module

Video 1: Product Overview

2. Specifications

The following table outlines the key technical specifications of the module:

Table 1: Basic Parameters
ParameterDescription
Power SupplyDC8-30V
Power Consumption9mA@30V, 12mA@24V, 23mA@12V, 33mA@8V
Input Sensor TypePT100 or PT1000
Measure Range-180°C ~ +650°C
Resolution0.1°C
Accuracy0.25°C
Input ConnectionsSupports two and three wire connections
Input FeaturesSupports disconnection and short circuit detection
OutputRS485 (Modbus RTU protocol), isolation design
Working Environment-30 ~ +55°C / 0-95%RH
MaterialABS
Mounting Type35mm Din-rail
Dimensions88*72*59mm

Figure 2: Basic Parameters Table

3. Setup

3.1 Terminal Description

Understand the function of each terminal before wiring:

Table 2: Terminal Description
TerminalDescription
+VPower +
GNDPower -
RTDx+PT100/1000 +
RTDx-PT100/1000 -
GND (Sensor)PT100/1000 GND
A (D+)RS485 +
B (D-)RS485 -

Figure 3: Terminal Description Table

3.2 PT100/PT1000 Wiring

The module supports both three-wire and two-wire connections for PT100/PT1000 sensors. Refer to the diagram below for correct wiring:

Wiring diagrams for PT100/PT1000 sensors, showing three-wire and two-wire connections.

Figure 4: PT100/PT1000 Wiring Diagram

  • Three-wire connection: Connect RTD1+, RTD2+, RTD3+, RTD4+, PGND, and RTD1- as shown.
  • Two-wire connection: Connect RTD1+, RTD2+, RTD3+, RTD4+, PGND, and RTD1-. For two-wire connections, you need to short RTD(n)- and GND.

3.3 Mounting

The module is designed for 35mm Din-rail mounting.

4. Operating Instructions

4.1 RS485 Communication (Modbus RTU Protocol)

The module communicates using the Modbus RTU protocol over RS485. The default communication parameters are:

  • Baud Rate: 9600 bps
  • Parity: None (n)
  • Data Bits: 8
  • Stop Bits: 1
  • Default Device Address: 1

4.1.1 Modbus Register Map - Parameter Register (Function Code: 03H Read, 06H Write)

This register allows configuration of communication parameters and device address.

Table 3: Parameter Register Map
Address (hex)Byte OrderMeaningDescriptionProperty
10LOCommunication parametersBIT<7:5> reserve
BIT<4:3> 00=none, 01=even, 10=odd, 11=odd
BIT<2:0> Baud Rate: 000=9600, 001=1200, 010=2400, 011=4800, 100=9600, 101=14400, 110=19200
Initial Value: 00
RW
HiAddress1-250
Initial Value: 01
RW

Figure 5: Modbus Parameter Register Map

4.1.2 Modbus Register Map - Data Register (Function Code: 03H Read)

This register provides the measured temperature data from each channel.

Table 4: Data Register Map
Address (hex)DescriptionFormatNumber of bytesProperty
40HChannel 1Float4R
42HChannel 2Float4R
20HChannel 1UINT (Scale: 0.1)2R
21HChannel 2UINT (Scale: 0.1)2R

Figure 6: Modbus Data Register Map

4.2 Configuration Tool

A dedicated configuration tool is provided to easily set up the module's parameters, such as slave address, baud rate, and to read sensor data. The tool offers a user-friendly interface for managing the device.

Screenshot of the configuration tool software interface.

Figure 7: Configuration Tool Interface

5. Maintenance

  • Keep the module clean and free from dust and moisture.
  • Ensure proper ventilation around the device to prevent overheating.
  • Avoid exposing the module to extreme temperatures or corrosive environments.
  • Regularly check wiring connections for tightness and integrity.

6. Troubleshooting

  • No communication: Verify RS485 wiring (A/B lines), power supply, and ensure communication parameters (baud rate, parity, address) match between the module and your master device.
  • Incorrect temperature readings: Check sensor wiring (two-wire vs. three-wire), ensure the correct sensor type (PT100/PT1000) is selected in your system, and inspect the sensor for damage.
  • Module not powering on: Confirm the DC8-30V power supply is connected correctly and providing the specified voltage.

7. User Tips

  • For stable readings, ensure your PT100/PT1000 sensors are properly insulated and protected from environmental interference.
  • When using the configuration tool, always verify the COM port settings match your PC's serial port connection.
  • If experiencing issues, consult the full user manual PDF for more in-depth information: Download User Manual (PDF).

8. Support

For technical assistance or further inquiries, please contact your seller or refer to the official product documentation.

© 2024 ComWinTop. All rights reserved.