LILYTECH ZL-7801A

Contents

LILYTECH ZL-7801A Temperature Humidity Controller

User Manual

1. Introduction

The ZL-7801A is a versatile temperature and humidity controller designed for precise environmental management. It features IP65 level front panel protection, ensuring durability and ease of operation and installation. This controller is suitable for a wide range of applications including incubators, climate chambers, greenhouses, and warehouses.

For a comprehensive PDF version of this manual, please refer to the official document: ZL-7801A User Manual (PDF)

LILYTECH ZL-7801A Temperature Humidity Controller with sensor
Figure 1: LILYTECH ZL-7801A Temperature Humidity Controller with its sensor.

2. Specifications

FeatureDescription
Power Supply100-240Vac, 50/60Hz
Input SignalOne humidity and temperature sensor (wire length 2.0 meters, extendable up to 5 meters)
Output Load (Resistive)R1 load: 5A/250Vac
R4 and R5 load: 3A/250Vac
R2 and R3 load: 16A/250Vac
Setting RangeHumidity: 5.0-95.0% RH
Temperature: -20.0~60.0°C
Sensor AccuracyHumidity: ±3%
Temperature: ±2%
0.1 absolute accuracy after calibration
Working EnvironmentHumidity: 10-90% RH (without dew)
Temperature: -20-45°C
Device DimensionW78 * H34.5 * D71 mm
Drilling SizeW71 * H29 mm
Case MaterialsPC + ABS, fireproof
Protection LevelIP65 (front panel only)
Front view of ZL-7801A controller
Figure 2: Front panel display and buttons.
Back view of ZL-7801A controller with wiring terminals
Figure 3: Rear view showing wiring terminals.
ZL-SHr05A and ZL-SHr05B sensor options
Figure 4: Available sensor options (ZL-SHr05A and ZL-SHr05B) with their respective humidity ranges.

3. Installation

The ZL-7801A controller is designed for easy panel mounting.

  1. Insert the controller into the pre-cut hole in your panel.
  2. Slide the provided brackets to fix the device securely in place.
Installation steps for ZL-7801A controller
Figure 5: Step-by-step guide for installing the controller into a panel.

4. Electrical Wiring Diagram

WARNING: Electrical wiring must be performed by a certified electrician. Incorrect wiring can damage the device, system, and pose a safety risk.

Carefully follow the wiring diagram below. Ensure all security and protection devices for the equipment are in place.

Detailed electrical wiring diagram for ZL-7801A
Figure 6: Electrical wiring diagram for the ZL-7801A. Connect power (100-240Vac) to L and N. Outputs R1 (Aux), R2 (Humidity), R3 (Temperature), R4/R5 (Timer) are clearly marked. The humidity/temperature sensor connects to terminals 9-12.

Output Connections:

  • R1: Aux Output (5A/250V~) - Can be used for egg turning, bells, or other auxiliary functions.
  • R2: Humidity Output (16A/250V~) - Connects to a humidifier or dehumidifier.
  • R3: Temperature Output (16A/250V~) - Connects to a heater.
  • R4/R5: Timer Output (3A/250V~) - Used for timed operations, such as egg turning.

The sensor connects to terminals 9 (O), 10 (B), 11 (R), 12 (Y).

Important Safety Note:

  • Ensure proper grounding.
  • Avoid mixing sensor/switch lines with inductive load/power supply lines in the same conduit.
  • Reduce sensor wiring length if possible and avoid spiral shapes near power devices.
  • Do not directly contact internal electronic components.

5. Key Operation

The controller features a digital display and four buttons: P (Program), S (Set/Save), ▲ (Up), and ▼ (Down).

Video 1: A 13-second demonstration of the ZL-7801A controller rotating, showing its physical design and terminal layout.

5.1. Temperature and Humidity Setting

  1. Press and hold the S button for 3 seconds to enter temperature and humidity setting mode. The display will show the set temperature.
  2. Press the P button to switch between humidity and temperature settings.
  3. Use the ▲ or ▼ buttons to adjust the value. Holding the button will allow for faster adjustment.
  4. Press and hold the S button for 3 seconds to exit and save the settings. If no key operation occurs for 30 seconds, the settings will automatically save and exit.

5.2. System Parameters Setting

  1. Press and hold the P button for 3 seconds to enter parameter setting mode.
  2. If a password is set (not 0000), the display will show "---0". Use ▲/▼ to select the digit and P to set the value (0-9). Press S to confirm.
  3. If the password is correct (or if it's 0000), the controller will show the parameter code.
  4. Use ▲ or ▼ to select the desired parameter code (refer to the table below).
  5. Press S to enter the code setting.
  6. Use ▲ or ▼ to adjust the value. Press S to return to the parameter code selection.
  7. Press and hold the P button for 3 seconds to exit and save. If no key operation occurs for 30 seconds, the settings will automatically save and exit.
CodeFunctionRangeRemarkFactory Set
U10Temp. control modeH/CH: Heat mode, C: Cool modeC
U11Temp. hysteresis0.1~20.0°C5.0
U12Time delay protection for temp. load0~30 min3
U13Temp. calibration-9.9~+9.9°C0.0
U14Sensor selection0~10: SHr03A, 1: SHr05A/SHr05B1
U20Humidity control modeH/PH: Humidify mode, P: Dehumidify modeP
U21Humidity hysteresis0.1~20.0%RH5.0
U22Time delay protection for humidity load0~30 min3
U23Humidity calibration-9.9~+9.9%0.0
U30Dewing warning modeC/UC: Dewing warning, U: No dewing warningU
U31Dewing warning delay0-30 sec6
U40Timer 1, period 1, time unit0-20: sec, 1: min, 2: hour1
U41Timer 1, period 1, time1-9999R5 on, R4 off120
U42Timer 1, period 2, time unit0-20: sec, 1: min, 2: hour1
U43Timer 1, period 2, time1-9999R4 on, R5 off120
U50Temp. and humidity value display alternating time1-30 secOnly when no warning2
U99Password0000-99990000: skip password0000

6. Control Functions

6.1. Temperature Control (U10)

Heat Mode (U10 = H):

  • The temperature load (R3) will turn ON when the room temperature is less than or equal to the set temperature minus the temperature hysteresis (U11), and the time delay protection (U12) has elapsed.
  • The temperature load (R3) will turn OFF when the room temperature is greater than or equal to the set temperature.

Cool Mode (U10 = C):

  • The temperature load (R3) will turn ON when the room temperature is greater than or equal to the set temperature plus the temperature hysteresis (U11), and the time delay protection (U12) has elapsed.
  • The temperature load (R3) will turn OFF when the room temperature is less than or equal to the set temperature.

Load Delay Protection:

  • After power is supplied, the temperature load (R3) will only activate after the time delay protection (U12) has elapsed.

6.2. Humidity Control (U20)

Humidify Mode (U20 = H):

  • The humidity load (R2) will turn ON when the room humidity is less than or equal to the set humidity minus the humidity hysteresis (U21), and the time delay protection (U22) has elapsed.
  • The humidity load (R2) will turn OFF when the room humidity is greater than or equal to the set humidity.

Dehumidify Mode (U20 = P):

  • The humidity load (R2) will turn ON when the room humidity is greater than or equal to the set humidity plus the humidity hysteresis (U21), and the time delay protection (U22) has elapsed.
  • The humidity load (R2) will turn OFF when the room humidity is less than or equal to the set humidity.

Load Delay Protection:

  • After power is supplied, the humidity load (R2) will only activate after the time delay protection (U22) has elapsed.

6.3. Dewing Warning

When the humidity reaches the dew point for the duration of the dewing warning delay (U31), the controller will enter a dewing warning state.

  • If the Dewing warning mode (U30) is set to 'C' (Dewing warning), the display will show "E2", loads (R2, R3) will turn OFF, and the alarm output (R1) will activate.
  • If the Dewing warning mode (U30) is set to 'U' (No dewing warning), the display will show "99.9%", humidity control continues, and no alarm output.

6.4. Timer 1 Control (R4, R5)

This function controls outputs R4 and R5 for timed operations.

  • During Period 1: R5 is ON, R4 is OFF.
  • During Period 2: R4 is ON, R5 is OFF.
  • If the repeat times (U70) is set to 0, the timer will repeat infinitely. Otherwise, it will stop after the set number of full periods (U70).

7. Sensor Information

The ZL-7801A uses a combined temperature and humidity sensor.

  • If the sensor is broken, the controller will display "E1", loads (R2, R3) will turn OFF, and the alarm output R1 will turn ON.
  • Temperature and humidity calibration (U13 and U23) allow for fine-tuning the sensor readings to achieve 0.1 absolute accuracy.
  • WARNING: Do not plug in or unplug the sensor while the power is supplied to the controller.
ZL-7801A controller with ZL-SHr05A sensor
Figure 7: ZL-7801A controller shown with the ZL-SHr05A sensor.

8. Factory Settings Reset

To restore the controller to its factory default settings:

  1. Press and hold the P and ▲ buttons simultaneously for 5 seconds.
  2. The device will display "UnL".
  3. Press the ▼ button twice.
  4. The controller will reset all parameters to factory default settings, including the password.

9. Troubleshooting

  • Display shows "E1": Indicates a broken sensor. Loads R2 and R3 will turn off, and R1 (alarm) will turn on. Replace the sensor.
  • Display shows "E2": Indicates a dewing warning (if U30 is set to 'C'). Loads R2 and R3 will turn off, and R1 (alarm) will turn on.
  • Controller not powering on or erratic behavior: Double-check all electrical wiring for correct connections and ensure the power supply is within the specified 100-240Vac range.
  • Inaccurate temperature/humidity readings: Perform sensor calibration using parameters U13 (temperature) and U23 (humidity).
  • Settings not saving: Ensure you press and hold the 'S' button for 3 seconds to save settings, or wait for 30 seconds of inactivity for automatic save.
  • Rattling sound inside the unit: If a rattling sound is heard, especially from a blue square component (likely a relay), it might indicate a loose or faulty component. This typically requires professional inspection or replacement.

10. User Tips

  • This controller is highly effective for automating humidity in incubators, as reported by users.
  • All temperature and humidity settings are retained even after power is disconnected.
  • The sensor wire can be extended up to 5 meters if needed for your application.
  • The default password for accessing system parameters is '0000'.
  • For connecting a cooler for ventilation (humidity or temperature control), ensure the current consumption is small or use an external relay to handle higher loads.
  • The controller works with 100-240V AC input.

11. Warranty and Support

For any issues, technical support, or warranty claims, please contact your retailer or the manufacturer directly. Keep your purchase receipt as proof of purchase.

Additional resources, including the full PDF manual, can be found on the manufacturer's website: https://www.suzhoulily.com.cn/doc/ZL-7801A/V3.0/

12. Safety Warnings

FAILURE TO FOLLOW THESE SAFETY INSTRUCTIONS COULD RESULT IN FIRE, ELECTRIC SHOCK, OR OTHER INJURY OR DAMAGE.

  • Professional Installation: All electrical wiring must be manipulated by a certified electrician.
  • Power Supply: Using the wrong power supply voltage may severely damage the device and the entire system. Ensure the power supply is 100-240Vac.
  • Wiring Separation: Always try to lay out sensor and switch lines separately from inductive load lines and power supply lines. Do not run them in the same pipeline or near contactors/breakers.
  • Sensor Handling: Reduce the length of sensor wiring if possible. Avoid forming spiral shapes near power devices. Do not plug or unplug the sensor when power is supplied.
  • Internal Components: Avoid direct contact with the internal electronic components of the controller.
  • Pre-Power Check: After finishing and checking the electrical wiring, thoroughly inspect all connections before applying power to the device. Incorrect connections can damage the device and system, and may be dangerous.

© 2023 LILYTECH. All rights reserved.