SINOTIMER STVP-932 Three-phase Multifunctional Adjustable Voltage Protector User Manual

Model: STVP-932 | Brand: SINOTIMER

1. Introduction

The SINOTIMER STVP-932 is a three-phase four-wire adjustable automatic recovery overvoltage and undervoltage multi-function protector. This device is designed to safeguard electrical equipment from damage caused by voltage fluctuations, including overvoltage, undervoltage, phase loss, neutral wire break, and phase sequence errors. It features a digital display for real-time voltage monitoring and adjustable protection parameters for customized operation.

SINOTIMER STVP-932 Voltage Protector front view

Figure 1: Front view of the SINOTIMER STVP-932 Voltage Protector, showing the digital display and control buttons.

2. Safety Information

Please read and understand all safety instructions before installing or operating this device. Failure to follow these instructions may result in electric shock, fire, or serious injury.

  • Installation and maintenance should only be performed by qualified electricians.
  • Ensure the power supply is disconnected before any installation or wiring work.
  • Do not operate the device if it is damaged or malfunctioning.
  • This device does not provide overload or short-circuit protection. It must be used in conjunction with appropriate circuit breakers (e.g., C45, C65 mini circuit breakers).
  • Verify correct wiring connections (Phase L1, L2, L3, and Neutral N) to prevent damage to the device and connected equipment.

3. Product Features

  • **Three-phase Four-wire Protection**: Designed for 3-phase AC 230V/400V, 50/60Hz systems.
  • **Adjustable Overvoltage Protection**: User-configurable upper voltage limit (221V to 300V).
  • **Adjustable Undervoltage Protection**: User-configurable lower voltage limit (150V to 219V).
  • **Automatic Recovery**: Automatically restores power once voltage returns to safe levels after a set recovery time (2s to 600s).
  • **Phase Loss Protection**: Detects and protects against loss of any phase.
  • **Neutral Wire Break Protection**: Safeguards against neutral wire disconnection.
  • **Phase Sequence Protection**: Protects against incorrect phase sequence (reverse phase protection).
  • **Phase Unbalance Protection**: Adjustable protection for voltage imbalance across phases.
  • **Digital Display**: LCD shows real-time voltage for each phase.
  • **Fault History**: Stores up to 5 fault records for diagnostic purposes.
  • **DIN Rail Installation**: Easy mounting on a 35mm DIN rail.

Video 1: Product demonstration showcasing real-time voltage display, over/under voltage protection, phase loss, neutral wire break, phase sequence protection, and adjustable parameters.

4. Specifications

Parameter Value
Brand NameSINOTIMER
Model NumberSTVP-932
TypeVoltage relay, Mini
Rated VoltageAC 230/400V 50/60Hz
PhaseThree phase
Max Load Current40A, 50A, 63A, 80A (selectable)
Over Voltage Protection Range221V to 300V (adjustable)
Under Voltage Protection Range150V to 219V (adjustable)
Recovery Time2s to 600s (adjustable)
LCD DisplayReal voltage for each phase
Amperage MeasurementNot supported
Dimensions72mm * 65mm * 80mm (L*W*H)
Installation35mm DIN Rail
CertificationCE, RoHS
Is Smart DeviceNo
Dimensions of the STVP-932 Voltage Protector

Figure 2: Dimensions of the STVP-932 Voltage Protector: 72mm (length), 65mm (width), 80mm (height).

5. Installation

5.1 Physical Installation

The STVP-932 is designed for 35mm DIN rail mounting. Ensure sufficient space for ventilation and wiring connections. Mount the device securely on the DIN rail.

5.2 Wiring Diagram

Connect the voltage protector according to the following diagram. Ensure all connections are tight and correctly phased (L1, L2, L3, N). This device should be installed after the main power switch and before the load, in conjunction with an appropriate air circuit breaker for overload and short-circuit protection.

Wiring diagram for SINOTIMER STVP-932 Voltage Protector

Figure 3: Wiring diagram showing the connection of the Voltage Protector between a Power Switch and an Air Circuit Breaker. L1, L2, L3, and N inputs are connected to the 'IN' terminals, and outputs to the 'OUT' terminals.

6. Operation

6.1 Display Information

The LCD displays real-time voltage for each phase (A, B, C) and the neutral (N). It also indicates protection status and fault codes.

6.2 Setting Parameters

To adjust parameters, press and hold the SET button for 3 seconds. Then, repeatedly press SET to cycle through the parameters (P01-P14). Use the ▲ (Up) or ▼ (Down) buttons to adjust the value of the selected parameter. Once adjustments are complete, press SET again when "ENd" is displayed to save the settings. If no operation is performed within 10 seconds during setting, the device will exit the setting mode, and unsaved changes will be lost.

The adjustable parameters (P01-P14) include:

  1. Over-voltage protection value (Uvo)
  2. Over-voltage recovery value (Uvr)
  3. Over-voltage protection action time (Uvt)
  4. Under-voltage protection value (Uvu)
  5. Under-voltage recovery value (Uvr)
  6. Under-voltage protection action time (Uvt)
  7. 3-phase volt unbalance protection value (Ubu)
  8. 3-phase volt unbalance protection action time (Ubt)
  9. Phase sequence protection (ON/OFF)
  10. Power-on delay time (Pon)
  11. Fault recovery delay time (Frt)
  12. Reset mode selection (AU/HA) - AU for automatic reset, HA for manual reset (requires power cycle).
  13. Fault inquiry (P13)
  14. Factory data reset (P14)

6.3 Protection Functions

  • **Over-voltage Protection**: If any phase voltage exceeds the set Uvo, the device will trip within the set Uvt time.
  • **Under-voltage Protection**: If any phase voltage drops below the set Uvu, the device will trip within the set Uvt time.
  • **Phase Loss Protection**: Detects the absence of a phase and trips.
  • **Neutral Wire Break Protection**: Detects a break in the neutral wire and trips.
  • **Phase Sequence Protection**: If the phase sequence is incorrect (e.g., ABC vs. ACB), the device will trip. If "ABC" is displayed on the LCD, arbitrarily reverse two phase lines (fire lines) to correct.
  • **Automatic Recovery**: After a trip, once the voltage returns to the set recovery value (Uvr for overvoltage, Uvr for undervoltage) and the Fault Recovery Delay Time (Frt) has elapsed, the device will automatically restore power.

7. Maintenance

The STVP-932 is designed for low maintenance. Periodically check wiring connections for tightness and inspect the device for any signs of physical damage or overheating. Ensure the environment is free from excessive dust, moisture, and corrosive gases.

8. Troubleshooting

8.1 Fault Inquiry (P13)

The device stores the last 5 fault records. To view them, navigate to parameter P13 in the setting mode and use the ▲ or ▼ buttons to scroll through the fault codes (E1-E5). ">U" indicates overvoltage, and "<U" indicates undervoltage.

8.2 Common Issues

  • **Device trips frequently**:
    • Check if voltage fluctuations are within normal operating range. Adjust over/under voltage protection values if necessary.
    • Verify all phase and neutral connections are secure.
    • Check for phase loss or incorrect phase sequence.
  • **Device does not reset after a trip**:
    • Ensure the voltage has returned to the safe recovery range.
    • Check the "Fault recovery delay time" (Frt) setting.
    • If the reset mode (P12) is set to "HA" (manual reset), you may need to power cycle the device.
  • **"ABC" displayed on LCD**: This indicates an incorrect phase sequence. Arbitrarily reverse two phase lines (fire lines) to correct the sequence.
  • **Humming sound under load**: Some users reported a humming sound under load. This might be normal for certain loads or indicate loose connections. Ensure all connections are tight.

8.3 Important Remarks

  • The zero-phase protection is ineffective when a three-phase motor is running, as it cannot be distinguished by back-EMF.
  • This device does not have overload and short-circuit protection. Always use it with appropriate mini circuit breakers (e.g., C45, C65).

9. User Tips

  • **Voltage Compatibility**: This device is designed for AC 230/400V systems. It is not suitable for 127V phase systems. Please verify your system's voltage before installation.
  • **Amperage Measurement**: The STVP-932 displays voltage for each phase but does not measure amperage. If current monitoring is required, a separate ammeter or a different model (e.g., STVP-936) would be needed.
  • **Generator Compatibility**: The device saves settings even without network power. It can be suitable for use with Automatic Transfer Switches (ATS) from a generator, but specific generator compatibility should be verified.
  • **Phase Unbalance**: If you have significant voltage unbalance, the device will trip. Ensure your electrical system is balanced to prevent unnecessary trips.
  • **Installation Quality**: Ensure all wiring is done professionally and connections are secure to prevent issues like humming or intermittent protection.

10. Warranty and Support

For technical support, inquiries, or to access the full user manual in PDF format, please refer to the contact information below. The PDF manual provides detailed instructions and diagrams.

A PDF version of the user manual is available: View User Manual (PDF)

Distributor Contact Information:

**XNY INTERNATIONAL LIMITED**
Address: Room 20A, Kiu Fu Commercial Building, 300 Lockhart Road, Wanchai, Hong Kong.
Tel: 0086 577 6173 3853
Fax: 0086 577 8973 6991
WhatsApp: 0086 156 5857 3377
Wechat: sinotimer
Skype: sinotimer
Web: www.sinotimer.com
Email: info@sinotimer.com

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.