1. Introduction
The GEYA GYL9 AC-S Type Time Delayed Residual Current Circuit Breaker (RCCB), also known as an Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD), is designed to provide protection against earth leakage faults. This device is specifically a 'Time Delayed' type, which means it is designed to trip after a short delay. This feature is crucial in installations with multiple RCCBs, allowing downstream devices to trip first and preventing nuisance tripping of the entire circuit.
This manual provides essential information for the safe and effective installation, operation, and maintenance of your GYL9 AC-S Type RCCB.
2. Safety Information
Please read and understand all safety instructions before installing, operating, or performing maintenance on this device. Failure to follow these instructions may result in electric shock, fire, or serious injury.
- Installation must be performed by a qualified electrician in accordance with all national and local electrical codes.
- Always disconnect power before working on the circuit breaker or associated wiring.
- Do not operate the device if it appears damaged or is not functioning correctly.
- Ensure proper grounding and wiring connections to prevent hazards.
- The device is designed for specific voltage and current ratings. Do not exceed these limits.
- This device is not a smart device and does not offer remote control capabilities.
3. Specifications
The GYL9 AC-S Type RCCB is designed to meet IEC61008-1 standards and is CE certified. Key technical specifications are detailed below:
| Attribute | Value |
|---|---|
| Brand Name | GEYA |
| Model Number | GYL9 AC-S Type RCCB |
| Type | Earth Leakage (RCD) |
| Poles | 2P, 4P |
| Rated Current (In) | 25A, 40A, 63A, 80A, 100A |
| Rated Voltage (Ue) | 2P: 240V, 4P: 415V |
| Rated Sensitivity (IΔn) | 100mA, 300mA |
| Action Time | <130-500mS (Selective) |
| Rated Insulating Voltage (Ui) | 500V |
| Rated Frequency | 50/60Hz |
| Breaking Capacity (Inc/IΔc) | 6KA / 10KA |
| Electrical Life | 4000 operations |
| Mechanical Life | 10000 operations |
| Certification | CE |
| Mounting | Din Rail (EN/IEC 60715) |
| Protection Degree | IP20 (Direct install), IP40 (Installed in distribution box) |
| Operating Temperature | -25°C ~ +40°C |
| Storage Temperature | -25°C ~ +70°C |
| Installation Altitude | <2000m |
| Pollution Degree | 2 |
| Max. Cable Size (Hard Wire) | 35mm² |
| Max. Cable Size (Flexible Wire) | 25mm² |
| Tightening Torque | 3.5Nm |
4. Setup and Installation
The GYL9 AC-S Type RCCB is designed for DIN rail mounting. Ensure the installation environment meets the specified temperature, altitude, and pollution degree requirements.
4.1. Mounting
- Securely attach the RCCB to a standard DIN rail (EN/IEC 60715) in your distribution board.
- Ensure adequate ventilation around the device.
4.2. Wiring Connections
Follow the wiring diagram carefully. Use appropriate cable sizes (max. 35mm² for hard wire, 25mm² for flexible wire) and ensure all connections are tightened to 3.5Nm to prevent loose contacts and overheating.
Wiring Diagram (4P GYL9 AC-S)
The wiring diagram for the GYL9 AC-S Type RCCB (4P version) typically involves connecting the incoming line (L1, L2, L3, N) to the top terminals and the outgoing load to the bottom terminals. Ensure correct phase and neutral connections as indicated on the device.
Note: A detailed wiring diagram is available in the official PDF manual.
5. Operation
5.1. Switching On/Off
- To switch on: Push the operating lever upwards to the 'ON' position.
- To switch off: Push the operating lever downwards to the 'OFF' position.
5.2. Earth Leakage Protection
The GYL9 AC-S Type RCCB continuously monitors the current balance between live and neutral conductors. If an earth leakage current exceeds the rated sensitivity (e.g., 100mA or 300mA) for the specified time delay, the device will automatically trip, disconnecting the circuit to prevent electric shock.
5.3. Time Delay Feature
The 'AC-S Type' designation indicates a time-delayed tripping characteristic. This is particularly useful in installations where multiple RCCBs are used in series. The upstream time-delayed RCCB allows a short circuit or earth fault to be cleared by a downstream, faster-acting RCCB or RCBO first, thereby localizing the fault and preventing a wider power outage.
6. Maintenance
6.1. Monthly Test
A 'Test Monthly' button is located on the front of the RCCB. It is essential to press this button monthly to verify the proper functioning of the earth leakage protection mechanism. When pressed, the RCCB should trip immediately. If it does not trip, the device may be faulty and should be replaced by a qualified electrician.
6.2. Cleaning
Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.
7. Troubleshooting
- RCCB does not trip on fault: Ensure the device is correctly wired and the 'Test Monthly' button functions. If not, the device may be faulty and requires replacement.
- Nuisance tripping: This can occur due to transient earth leakage currents or faulty appliances. The time-delayed nature of the AC-S type helps mitigate this for upstream devices. Check all connected appliances for faults.
- RCCB trips immediately on power-up: This indicates a persistent earth leakage fault in the circuit. Disconnect all loads and reconnect them one by one to identify the faulty appliance or wiring section.
8. User Tips
- For installations with multiple earth leakage protection devices, strategically place time-delayed (AC-S type) RCCBs upstream to ensure selective tripping and minimize disruption.
- Regularly check the 'Test Monthly' button to confirm the device's operational integrity.
- If you experience frequent tripping, consult a qualified electrician to diagnose and resolve underlying electrical issues.
9. Warranty and Support
For any issues or inquiries regarding your GEYA GYL9 AC-S Type RCCB, please refer to the official GEYA website or contact your local distributor for support. Keep your purchase records for warranty claims.
For additional documentation, including the full user manual in PDF format, please visit the official GEYA website or refer to the provided link: GEYA GYL9 User Manual (PDF).
10. GEYA Company Overview
GEYA Electric, established in 2007, is a private-owned enterprise specializing in the research, manufacturing, and sales of low-voltage electrical and automatic controlling products. The company is committed to top quality and constant innovation, holding numerous national patents and various international certifications (CCC, CE, CB, SAA, SEMKO, TUV, Rosh).