1. Safety Information
⚠ Warning: To avoid danger of suffocation, keep this bag away from babies and children. Do not use this bag in cribs, beds, carriages, or play pens. This bag is not a toy.
General Precautions
- Always have an electrical professional perform the operation and installation of this product.
- Do not place the device near flammable materials.
- Ensure adequate ventilation during operation.
- Disconnect from power and store properly when not in use for extended periods.
- Always follow local electrical codes and regulations.
2. Product Overview
The TOMZN TOB1Z-63 Series DC Miniature Circuit Breaker (MCB) is designed for reliable overload and short circuit protection in DC distribution systems and electrical equipment. It is suitable for applications with a rated current of 63A or less and a direct current rated voltage of 125V. This MCB is widely used in various fields including electric, post, traffic, mining enterprises, and photovoltaic (PV) systems.
The TOB1Z-63 DC circuit breaker features a unique design structure with a strong permanent magnetism arc system, providing a 6KA short circuit capability. It boasts a long mechanical life of over 20,000 operations.
3. Specifications
The following table details the technical specifications of the TOMZN TOB1Z-63 DC Miniature Circuit Breaker:
| Attribute | Value |
|---|---|
| Model Number | TOB1Z-63 |
| Type | Miniature Circuit Breaker |
| Poles Number | 1P (also available in 2P, 3P, 4P) |
| Rated Voltage Ue | 1P: DC 125V; 2P: DC 440V |
| Insulation Voltage Ui | 1000V |
| Rated Current (In) | 3A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A |
| Rated Breaking Capacity (Ics=Icu) | 6000A |
| Rated Impulse Withstand Voltage (Uimp) | 6KV |
| Thermo-magnetic Release Characteristic | B: 6In ± 20%; C: 12In ± 20% |
| Mechanical Life | 20,000 operations |
| Electrical Life | Not less than 8000 times |
| Protection Degree | IP20 |
| Reference Temperature for Thermal Element Setting | 30°C |
| Ambient Operating Temperature | -5°C to +40°C (daily average ≤35°C) |
| Storage Temperature | -25°C to +70°C |
| Terminal Connection Type | Cable/U-type busbar/Pin-type busbar |
| Terminal Size (top/bottom for cable) | 25mm² 18-3 |
| Tightening Torque | 3.0N·m |
| Mounting | 35mm DIN Rail (FN 60715) by fast clip device |
| Connection | Top and bottom |
| EU LVD Voltage | High voltage: Above 50Vac or 75Vdc |
4. Installation
General Installation Guidelines
- Upon receiving the product, it is highly recommended to have an electrical professional perform the installation and initial operation.
- Connect the equipment strictly in accordance with the provided wiring diagram specifications.
- The circuit breaker is designed for mounting on a 35mm DIN rail (FN 60715 standard) using its fast clip device.
- When connecting, pay close attention to the '+' and '-' poles to ensure correct polarity.
- Power should enter from the top terminals and exit from the bottom terminals. This configuration is designed for convenient installation and cable management.
5. Operating Instructions
The TOB1Z-63 DC MCB functions as an automatic control transfer switch for dual power supply systems, offering quick and millisecond switching capabilities, making it ideal for solar systems.
Basic Operation
- Once installed by a qualified professional, the circuit breaker is ready for operation.
- The operating handle on the front of the device allows for manual switching (ON/OFF).
- In the event of a short circuit or overload condition, the equipment will immediately cut off the power supply to protect the circuit.
- After a trip, investigate and resolve the fault in the circuit before resetting the breaker.
Tripping Characteristics
The circuit breaker offers different tripping characteristics to suit various load types:
- B Curve (3-5In): Provides protection for people and long cables in TN and IT systems.
- C Curve (5-10In): Offers protection for resistive and inductive loads with low inrush current.
- D Curve (10-14In): Designed for circuits supplying loads with high inrush current at circuit closing (e.g., LV/LV transformers, breakdown lamps).
6. Maintenance
The TOMZN TOB1Z-63 DC MCB is designed for durability and requires minimal maintenance. However, regular checks and proper handling will ensure its longevity and reliable performance.
- Periodic Inspection: Visually inspect the circuit breaker and its connections periodically for any signs of damage, overheating, or loose wiring.
- Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.
- Storage: When not in use for extended periods, disconnect the device from power and store it in a dry, cool environment, away from direct sunlight and corrosive substances.
- Professional Check: For any suspected malfunction or after a significant electrical event (e.g., severe short circuit), have the device inspected by a qualified electrical professional.
7. Troubleshooting
This section provides basic troubleshooting steps for common issues. For complex problems, always consult a qualified electrician.
Circuit Breaker Trips Frequently
- Cause: Frequent tripping usually indicates an overload or a short circuit in the protected circuit.
- Solution:
- Disconnect all loads from the circuit.
- Reset the circuit breaker. If it trips immediately, there might be a short circuit in the wiring itself.
- Reconnect loads one by one to identify the faulty appliance or section of the circuit.
- Ensure the total current drawn by connected devices does not exceed the rated current of the MCB. If it does, redistribute loads or consider a higher-rated MCB (after consulting a professional and ensuring wiring can handle it).
- Check for loose connections at the terminals, which can cause overheating and tripping.
Circuit Breaker Does Not Reset
- Cause: A persistent fault (short circuit or severe overload) is still present, or the breaker itself is damaged.
- Solution:
- Ensure all loads are disconnected and the fault has been cleared.
- Attempt to reset the breaker firmly.
- If it still does not reset, the breaker might be internally damaged and needs replacement by a qualified professional.
8. User Tips
- Professional Installation: Always prioritize professional installation to ensure safety and compliance with electrical standards.
- Correct Sizing: Ensure the chosen amperage (3A to 63A) matches the requirements of your circuit to prevent nuisance tripping or inadequate protection.
- Polarity: Double-check the '+' and '-' connections during installation, especially in DC systems like PV setups, as incorrect polarity can cause damage.
- Ventilation: Maintain good ventilation around the circuit breaker to prevent overheating, especially in enclosed spaces.
- Regular Checks: Periodically inspect the breaker for any signs of wear, damage, or loose connections.
9. Frequently Asked Questions (FAQ)
- Q: What is the primary function of the TOMZN TOB1Z-63 DC MCB?
- A: Its primary function is to provide overload and short circuit protection for DC distribution systems and electrical equipment, particularly in applications like solar PV systems.
- Q: What does '1P 125V DC' mean?
- A: '1P' refers to a single pole, meaning it protects one conductor. '125V DC' indicates that it is designed for direct current circuits with a maximum rated voltage of 125 Volts.
- Q: What is the 'Breaking Capacity' of this circuit breaker?
- A: The breaking capacity (6000A or 6kA) is the maximum fault current that the circuit breaker can safely interrupt without being damaged. This is a critical safety rating.
- Q: Can I install this circuit breaker myself?
- A: Installation of electrical components, especially circuit breakers, should always be performed by a qualified electrical professional to ensure safety, proper function, and compliance with electrical codes.
10. Standards and Certifications
The TOMZN TOB1Z-63 DC Miniature Circuit Breaker complies with the following international standards and directives:
- Certification: CE
- Standards: IEC60947, IEC60898, GB14048.2
- Low Voltage Directive: 2014/35/EU
- Electromagnetic Compatibility Directive: 2014/30/EU
- Restriction of Hazardous Substances (RoHS) Directive: 2011/65/EU
11. Support
For further detailed information, technical diagrams, or specific inquiries, please refer to the official user manual PDF or contact TOMZN customer support.
Official User Manual (PDF): Download PDF Manual