TOMZN TOB1Z-63 DC Miniature Circuit Breaker User Manual

Model: TOB1Z-63

1. Safety Information

⚠ Warning: To avoid danger of suffocation, keep this bag away from babies and children. Do not use this bag in cribs, beds, carriages, or play pens. This bag is not a toy.

General Precautions

  • Always have an electrical professional perform the operation and installation of this product.
  • Do not place the device near flammable materials.
  • Ensure adequate ventilation during operation.
  • Disconnect from power and store properly when not in use for extended periods.
  • Always follow local electrical codes and regulations.

2. Product Overview

The TOMZN TOB1Z-63 Series DC Miniature Circuit Breaker (MCB) is designed for reliable overload and short circuit protection in DC distribution systems and electrical equipment. It is suitable for applications with a rated current of 63A or less and a direct current rated voltage of 125V. This MCB is widely used in various fields including electric, post, traffic, mining enterprises, and photovoltaic (PV) systems.

The TOB1Z-63 DC circuit breaker features a unique design structure with a strong permanent magnetism arc system, providing a 6KA short circuit capability. It boasts a long mechanical life of over 20,000 operations.

Front view of TOMZN TOB1Z-63 DC MCB with labeled components
Figure 2.1: Product Appearance Display of TOB1Z-63 DC MCB, highlighting input, brand, model number, DC voltage, breaking capacity, rated current, wiring diagram, operating handle, and fastening screws.

3. Specifications

The following table details the technical specifications of the TOMZN TOB1Z-63 DC Miniature Circuit Breaker:

Attribute Value
Model NumberTOB1Z-63
TypeMiniature Circuit Breaker
Poles Number1P (also available in 2P, 3P, 4P)
Rated Voltage Ue1P: DC 125V; 2P: DC 440V
Insulation Voltage Ui1000V
Rated Current (In)3A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
Rated Breaking Capacity (Ics=Icu)6000A
Rated Impulse Withstand Voltage (Uimp)6KV
Thermo-magnetic Release CharacteristicB: 6In ± 20%; C: 12In ± 20%
Mechanical Life20,000 operations
Electrical LifeNot less than 8000 times
Protection DegreeIP20
Reference Temperature for Thermal Element Setting30°C
Ambient Operating Temperature-5°C to +40°C (daily average ≤35°C)
Storage Temperature-25°C to +70°C
Terminal Connection TypeCable/U-type busbar/Pin-type busbar
Terminal Size (top/bottom for cable)25mm² 18-3
Tightening Torque3.0N·m
Mounting35mm DIN Rail (FN 60715) by fast clip device
ConnectionTop and bottom
EU LVD VoltageHigh voltage: Above 50Vac or 75Vdc
Table of detailed specifications for TOB1Z-63 DC MCB
Figure 3.1: Detailed specifications including crust grade rating current, pole configuration, rating voltage, rating current, breaking current, trip time, and instantaneous trip type.
Table of TOB7Z-63 DC MCB specifications
Figure 3.2: Additional specifications for TOB7Z-63 DC MCB, including standards, characteristic curves, ambient conditions, and life cycles.
Dimension diagram of the TOB1Z-63 circuit breaker
Figure 3.3: Dimension Diagram showing height (A, C), length (B, D, E), and width (F) measurements. All dimensions are in millimeters and are for reference only.

4. Installation

General Installation Guidelines

  1. Upon receiving the product, it is highly recommended to have an electrical professional perform the installation and initial operation.
  2. Connect the equipment strictly in accordance with the provided wiring diagram specifications.
  3. The circuit breaker is designed for mounting on a 35mm DIN rail (FN 60715 standard) using its fast clip device.
  4. When connecting, pay close attention to the '+' and '-' poles to ensure correct polarity.
  5. Power should enter from the top terminals and exit from the bottom terminals. This configuration is designed for convenient installation and cable management.
TOMZN TOB1Z-63 DC MCB mounted on a DIN rail
Figure 4.1: The TOB1Z-63 DC MCB securely mounted on a standard DIN rail.
Easy wiring diagram for TOB1Z-63 DC MCB showing input and output connections
Figure 4.2: Wiring Diagram illustrating the +Input and +Output connections. Ensure to screw down to penetrate the insulating layer of the power lines.
Side view of the circuit breaker showing auxiliary connections and mounting mechanism
Figure 4.3: Side view indicating how to tilt out for auxiliaries and lift for installation.

5. Operating Instructions

The TOB1Z-63 DC MCB functions as an automatic control transfer switch for dual power supply systems, offering quick and millisecond switching capabilities, making it ideal for solar systems.

Basic Operation

  • Once installed by a qualified professional, the circuit breaker is ready for operation.
  • The operating handle on the front of the device allows for manual switching (ON/OFF).
  • In the event of a short circuit or overload condition, the equipment will immediately cut off the power supply to protect the circuit.
  • After a trip, investigate and resolve the fault in the circuit before resetting the breaker.

Tripping Characteristics

The circuit breaker offers different tripping characteristics to suit various load types:

  • B Curve (3-5In): Provides protection for people and long cables in TN and IT systems.
  • C Curve (5-10In): Offers protection for resistive and inductive loads with low inrush current.
  • D Curve (10-14In): Designed for circuits supplying loads with high inrush current at circuit closing (e.g., LV/LV transformers, breakdown lamps).
Image showing the circuit breaker operating in extreme temperatures
Figure 5.1: The TOB1Z-63 MCB is designed to operate normally in harsh environments, from temperatures not higher than 40°C to not lower than -10°C.

6. Maintenance

The TOMZN TOB1Z-63 DC MCB is designed for durability and requires minimal maintenance. However, regular checks and proper handling will ensure its longevity and reliable performance.

  • Periodic Inspection: Visually inspect the circuit breaker and its connections periodically for any signs of damage, overheating, or loose wiring.
  • Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.
  • Storage: When not in use for extended periods, disconnect the device from power and store it in a dry, cool environment, away from direct sunlight and corrosive substances.
  • Professional Check: For any suspected malfunction or after a significant electrical event (e.g., severe short circuit), have the device inspected by a qualified electrical professional.

7. Troubleshooting

This section provides basic troubleshooting steps for common issues. For complex problems, always consult a qualified electrician.

Circuit Breaker Trips Frequently

  • Cause: Frequent tripping usually indicates an overload or a short circuit in the protected circuit.
  • Solution:
    1. Disconnect all loads from the circuit.
    2. Reset the circuit breaker. If it trips immediately, there might be a short circuit in the wiring itself.
    3. Reconnect loads one by one to identify the faulty appliance or section of the circuit.
    4. Ensure the total current drawn by connected devices does not exceed the rated current of the MCB. If it does, redistribute loads or consider a higher-rated MCB (after consulting a professional and ensuring wiring can handle it).
    5. Check for loose connections at the terminals, which can cause overheating and tripping.

Circuit Breaker Does Not Reset

  • Cause: A persistent fault (short circuit or severe overload) is still present, or the breaker itself is damaged.
  • Solution:
    1. Ensure all loads are disconnected and the fault has been cleared.
    2. Attempt to reset the breaker firmly.
    3. If it still does not reset, the breaker might be internally damaged and needs replacement by a qualified professional.

8. User Tips

  • Professional Installation: Always prioritize professional installation to ensure safety and compliance with electrical standards.
  • Correct Sizing: Ensure the chosen amperage (3A to 63A) matches the requirements of your circuit to prevent nuisance tripping or inadequate protection.
  • Polarity: Double-check the '+' and '-' connections during installation, especially in DC systems like PV setups, as incorrect polarity can cause damage.
  • Ventilation: Maintain good ventilation around the circuit breaker to prevent overheating, especially in enclosed spaces.
  • Regular Checks: Periodically inspect the breaker for any signs of wear, damage, or loose connections.

9. Frequently Asked Questions (FAQ)

Q: What is the primary function of the TOMZN TOB1Z-63 DC MCB?
A: Its primary function is to provide overload and short circuit protection for DC distribution systems and electrical equipment, particularly in applications like solar PV systems.
Q: What does '1P 125V DC' mean?
A: '1P' refers to a single pole, meaning it protects one conductor. '125V DC' indicates that it is designed for direct current circuits with a maximum rated voltage of 125 Volts.
Q: What is the 'Breaking Capacity' of this circuit breaker?
A: The breaking capacity (6000A or 6kA) is the maximum fault current that the circuit breaker can safely interrupt without being damaged. This is a critical safety rating.
Q: Can I install this circuit breaker myself?
A: Installation of electrical components, especially circuit breakers, should always be performed by a qualified electrical professional to ensure safety, proper function, and compliance with electrical codes.

10. Standards and Certifications

The TOMZN TOB1Z-63 DC Miniature Circuit Breaker complies with the following international standards and directives:

  • Certification: CE
  • Standards: IEC60947, IEC60898, GB14048.2
  • Low Voltage Directive: 2014/35/EU
  • Electromagnetic Compatibility Directive: 2014/30/EU
  • Restriction of Hazardous Substances (RoHS) Directive: 2011/65/EU

11. Support

For further detailed information, technical diagrams, or specific inquiries, please refer to the official user manual PDF or contact TOMZN customer support.

Official User Manual (PDF): Download PDF Manual

© 2024 TOMZN. All rights reserved.