SINOTIMER TM613-380V

Contents

SINOTIMER TM613 380V Three-Phase Digital Programmable Timer Switch User Manual

Model: TM613-380V

1. Introduction

The SINOTIMER TM613 is a stable, high-performance three-phase digital programmable timer switch designed for 7-day, 24-hour operation. This device features three FireWire inputs and three FireWire outputs, eliminating the need for a zero line, which can be convenient for certain installations. It allows for a total of 28 ON/OFF programs to be set from Monday to Sunday, with a minimum interval of one minute and a maximum of 168 hours (equivalent to one week). The timer supports temporary manual override while maintaining its programmed loop.

It is widely used in various applications such as controlling pumps, pond aerators, steaming machines, water heaters, billboards, neon signs, and exhaust fans. The TM613 is suitable for three-phase 350V-420VAC motors and other equipment, providing unmanned management with safe, reliable, and stable performance.

2. Safety Information

  • Electrical Hazard: Installation and maintenance should only be performed by qualified personnel. Ensure power is disconnected before any wiring or service.
  • Voltage Compatibility: This device is designed for 350-420VAC three-phase systems. Do not connect to single-phase or voltages outside this range.
  • Current Rating: The maximum current per phase is 16A. Do not exceed this rating to prevent damage or fire.
  • Proper Grounding: Ensure proper grounding according to local electrical codes.
  • Environmental Conditions: Avoid installing in areas with excessive moisture, dust, or extreme temperatures.

3. Product Overview

3.1 Key Features

  • Three-phase digital time switch for 7 days-24 hours programming.
  • Advanced pre-setting capability for up to one week.
  • 28 ON/OFF programs for daily and weekly scheduling.
  • One channel, voltage output.
  • Accurate-to-the-minute control.
  • LED power indicator and high contrast LCD display.
  • Reset function and manual override.
  • Battery backup for power failure.

3.2 Product Components

The timer switch features a clear LCD display, control buttons, and input/output terminals. Refer to the images below for visual identification.

Front view of the TM613 timer switch with input/output labels
Front view of the TM613 timer switch with input/output labels.
Angled view of the TM613 timer switch showing the display and buttons
Angled view of the TM613 timer switch.
Back view of the TM613 timer switch showing mounting points
Back view of the TM613 timer switch with mounting points.

4. Setup and Installation

4.1 Mounting

The TM613 timer switch can be installed on a DIN rail or panel mounted. Refer to the dimensions and mounting details below.

Diagram showing dimensions for DIN rail mount and panel mount, along with a wiring diagram
Dimensions for DIN rail mount (35mm) and panel mount. Overall dimensions: 52.5mm (width) x 116mm (height) x 106mm (depth).

4.2 Wiring

Connect the three-phase power supply to the 'INPUT' terminals (A, B, C) and the three-phase device (e.g., motor, pump) to the 'OUTPUT' terminals (A, B, C). The device is designed for 3x16A output. Ensure all connections are secure and comply with local electrical standards.

Wiring Diagram:

Wiring diagram for the TM613 three-phase timer switch, showing input A, B, C and output A, B, C connections to a 3-Phase Device
Wiring diagram for the TM613. Input A, B, C connect to the power source, and Output A, B, C connect to the 3-Phase Device.

5. Operating Instructions

5.1 Initial Setup and Unlocking

Upon initial power-up or after a reset, the display may be locked. To unlock the device, press the 'Clock' button 4 times consecutively.

5.2 Setting Current Time

  1. Press the 'Clock' button.
  2. Use 'Week', 'Hour', and 'Minute' buttons to set the current day, hour, and minute.
  3. Press 'Clock' again to save and exit.

5.3 Programming ON/OFF Cycles

The TM613 supports up to 28 ON/OFF programs. Follow these steps to set your desired schedule:

Table showing programming steps for the TM613 timer switch
Programming steps for setting ON/OFF times.
  1. Press the 'Program' button to enter programming mode. The display will show '1 ON'.
  2. Use 'Hour' and 'Minute' buttons to set the desired ON time for the first program.
  3. Press 'Week' to select the day(s) for this program (e.g., MO-FR, SA-SU, MO-SU, etc. If the same everyday, no need to press this key).
  4. Press 'Program' again. The display will show '1 OFF'.
  5. Use 'Hour' and 'Minute' buttons to set the desired OFF time for the first program.
  6. Press 'Week' to select the day(s) for this program (if different from ON time, or if same everyday, no need to press this key).
  7. Repeat steps 1-6 for programs 2 through 28.
  8. Press the 'C/R' button to save all programs and exit programming mode.

5.4 Manual Override

The 'Manual' button allows you to temporarily override the programmed schedule. Pressing it cycles through ON, AUTO, and OFF modes:

  • ON: The output is continuously ON, regardless of programs.
  • AUTO: The output follows the programmed schedule.
  • OFF: The output is continuously OFF, regardless of programs.

When in ON or OFF manual mode, the timer will remain in that state until manually changed or a program triggers a state change if it's set to AUTO.

5.5 Locking the Device

To prevent accidental changes to settings, you can lock the device by pressing the 'Clock' button 4 times consecutively.

5.6 Video Demonstration

Watch this video for a visual guide on programming and operating the timer switch:

Video demonstrating the programming and manual operation of the TM613 timer switch.

6. Maintenance

6.1 Battery Backup

The TM613 includes a built-in battery backup to retain programmed settings during power outages. No user maintenance is typically required for the internal battery.

6.2 Cleaning

Wipe the device with a soft, dry cloth. Do not use abrasive cleaners or solvents, as they may damage the casing or display.

7. Troubleshooting

  • Display is blank: Check power supply connections. Ensure the device is receiving 350-420VAC three-phase power.
  • Device not responding to button presses: The device might be locked. Press the 'Clock' button 4 times to unlock it.
  • Programs not executing: Ensure the current time is set correctly. Verify that the device is in 'AUTO' mode (not ON or OFF manual override). Double-check your programmed ON/OFF times and selected days.
  • Output not switching: Check wiring connections to the load. Ensure the load itself is functional.
  • Motor/device damage concerns: This timer switch controls power ON/OFF. It does not inherently provide phase loss protection. For critical applications where phase loss could damage equipment, consider installing an external phase failure relay in conjunction with this timer.

8. Specifications

FeatureSpecification
Model NumberTM613-380V
Brand NameSINOTIMER
TheoryDigital
UseTimer Switch
Operating Voltage350-420VAC ±15%
Frequency50-60Hz
Max. Current3 x 16A
Programs28 ON/OFF per day/week
Minimum Interval1 Minute
Maximum Interval168 Hours (1 Week)
InstallationDIN RAIL or panel mounted
Battery IncludedYes (for backup)
CertificationCE
Dimensions (approx.)52.5mm (W) x 116mm (H) x 106mm (D)

9. User Tips

  • Voltage Check: This device is specifically for 380V three-phase systems. If you require a 220V device, ensure you purchase the correct model, as this unit is not compatible with 220V.
  • Phase Loss Protection: While the timer provides stable performance, for applications where motor damage from phase loss is a concern, consider integrating an external phase failure protection relay into your system.

10. Warranty and Support

For warranty information, technical support, or service inquiries, please contact your retailer or the manufacturer directly. Keep your purchase receipt as proof of purchase.

Ask a question about this manual