1. Introduction
This manual describes in detail the requirements and procedures for safe installation and operation of the DATOUBOSS 51.2V 100Ah LiFePO4 Lithium Battery. This battery, model DT-3U-48100, is a lithium iron phosphate battery designed with a standard 3U rack-mount form factor. It features A-grade cells, a rated energy of 5.12 kWh, and a maximum charge/discharge current of 100 A. The unit includes a built-in smart Battery Management System (BMS) and supports RS485, CAN, and RS232 communication interfaces, as well as Bluetooth and WiFi for app monitoring. Its modular design allows for flexible expansion, supporting up to 15 units connected in parallel to achieve a total capacity of 76.8 kWh. With a cycle life exceeding 15,000 cycles, it offers high safety and a long service life, making it suitable for various applications including home energy storage, off-grid backup power, RVs, and light electric vehicles.
Please read this manual carefully before installation, operation, and maintenance. Only qualified persons are permitted to install, operate, and maintain the system to prevent product damage or personal safety risks.
2. Safety Information
2.1 General Safety Precautions
- Do not impact the battery with heavy objects.
- Do not squeeze or pierce the battery pack.
- Do not throw the battery pack into fire.
- Do not connect the battery in series.
- Do not expose the battery pack to conditions over 80°C.
- Do not place the battery near a heat source, such as a fireplace.
- Do not expose the battery pack to direct sunlight or rain.
- Do not allow non-qualified persons to disassemble the battery pack.
- Do not touch the battery pack with wet hands.
- Do not expose the battery pack to moisture or liquid environments.
- Do not short-circuit or reverse connect the battery.
- Do not use chargers or charging devices unapproved by the manufacturer to charge the battery.
- Do not mix batteries from different manufacturers or different types or brands.
- For safety, it is not recommended to use the battery near the ocean.
2.2 Safety Instructions
The battery has been designed and tested in accordance with international safety requirements (UL, IEC, UN38.3, etc.). However, due to various factors during its lifetime, DATOUBOSS cannot guarantee absolute safety. To prevent personal and property damage and ensure long-term operation, please read and follow the instructions carefully.
2.3 Safety Gear
When installing and handling the battery pack, it is required to wear the following safety gear:

Insulated Gloves

Safety Glasses

Safety Shoes
2.4 Emergency Safety Measures
Water Invasion: Cut off the AC power supply of the system first, then disconnect all switches under the premise of ensuring safety.
Electrolyte or Gas Leakage: If the battery pack leaks electrolyte, avoid contact with the liquid or gas. If exposed, immediately perform the following actions:
- Gas Inhalation: Evacuate people from the contaminated area and seek medical aid immediately.
- Eye Contact: Flush eyes with clean, flowing water for 15 minutes, then seek medical aid immediately.
- Skin Contact: Thoroughly rinse the exposed area with soap and water to ensure no chemicals remain, then seek medical aid immediately.
- Ingestion: Induce vomiting and seek medical help immediately.
2.5 Other Tips
- All products are strictly inspected before shipment. Contact support for replacement if you notice any defects such as swelling.
- Do not disassemble batteries and components. Unauthorized disassembly or repair voids warranty and manufacturer responsibility for damage.
- Ensure the battery is safely grounded before use for safe and normal system operation.
- Verify that the electrical parameters of all connected devices are mutually compatible.
- Consider environmental factors carefully. The environment and storage methods impact the service life and reliability of this product.
3. Product Overview
3.1 General Schematic
The DATOUBOSS battery functions as a storage unit in photovoltaic systems. Below is a general schematic of an AC-coupled system:

Figure 1: General Schematic of an AC-Coupled System
3.2 Features
- High Safety: Made from LiFePO4 chemistry, complying with international safety and transport standards.
- Modular and Flexible: Supports connecting up to 15 batteries in parallel to expand system energy.
- Built-in Pre-charge Circuit: Avoids rush current when connecting with different inverters/chargers.
- Automatic Dynamic Addressing: For multiple batteries connected together.
- High DOD: Supports a maximum of 96% Depth of Discharge (DOD) under off-grid and backup applications.
- Smart BMS: Provides warning and protection functions including over-discharging, over-charging, over-current, short-circuit, and high/low temperature protection.
- Automatic Balancing: LiFePO4 is equipped with an automatic balancing function for long cycle life. New batteries require approximately 10 charge-discharge cycles to reach maximum capacity.
- Compact Size and Light Weight: For easy installation and maintenance.
- Communication Ports: CAN/RS485 port for external communication.
3.3 Specifications
3.3.1 Dimensions

Figure 2: Battery Dimensions
| Item | Value |
|---|---|
| Dimension | 22.09*19.02*5.24in / 56.1*48.3*13.3cm |
| Weight | 94.8lb / 43kg |
3.3.2 Electrical Parameters
| Item | Value |
|---|---|
| Rated voltage | 51.2V |
| Max. voltage range | 40.5~54.75V |
| Charge voltage | 58.4V |
| Low voltage cut-off | 40.0V |
| Nominal energy | 5.12kWh |
| Usable energy | 5.12kWh |
| Nominal capacity | 100Ah |
| Standard charge current | ≤50A |
| Max. charge current | 100A |
| Max. discharge current | 100A (initial temp. ≤35°C) |
| Communication port | RS485/CAN/RS232 |
| Max. parallel number | 15pcs |
| Operating temperature (Charge) | 0~55°C |
| Operating temperature (Discharge) | -20~55°C |
| Storage temperature (-20~25°C) | Less than 1 year |
| Storage temperature (20~40°C) | Less than 3 months |
| Environment at shipment state | 60±25% R.H. |
3.3.3 BMS Parameters
| Charge Parameter | Spec | Delay | Recovery |
|---|---|---|---|
| Cell Voltage Protection | 3600mV | 3000mS | 3400mV |
| Module Voltage Protection | 58.4V | 3000mS | 54.4V |
| Charge Over Current 1 | 105A | 2000mS | |
| Charge Over Current 2 | 120A | 2000mS | |
| Temperature Protection | <32°F/0°C or >149°F/65°C |
| Discharge Parameter | Spec | Delay | Recovery |
|---|---|---|---|
| Cell Voltage Protection | 2500mV | 3000mS | 3000mV |
| Module Voltage Protection | 40.0V | 3000mS | 48.0V |
| Discharge Over Current 1 | 105A | 2000mS | |
| Discharge Over Current 2 | 120A | 2000mS | |
| Short Circuit | 1200A | 400uS | |
| Temperature Protection | <-4°F/-20°C or >149°F/65°C |
| BMS Parameter | Parameter | Condition |
|---|---|---|
| PCB Temperature Protection | >221°F/105°C | |
| Cell Balance | 60mV charging equalization | |
| Temperature Accuracy | ±3°C | |
| Cell Voltage Accuracy | ±10mV | For Cells |
| Current Accuracy | ±2% | |
| SOC | 5% | |
| Power Consumption (Off Mode) | ≤20uA | Storage/Transport |
| Power Consumption (Sleep Mode) | ≤200uA | Sleeping |
| Power Consumption (Operating Mode) | ≤60mA | Charging/Discharging |
| Communication Ports | RS485, CAN, RS232 | |
| Bluetooth & WiFi Signal Distance | ≥49 feet/15m |
3.3.4 Panel Interface

Figure 3: Battery Panel Interface
| NO. | Item | Usage Description |
|---|---|---|
| A | Handles | For handling, installation and disassembly of battery |
| B | Grounding | Used to connect battery with ground |
| C | Negative terminal | Used to connect the inverter/charger |
| D | Positive terminal | Used to connect the inverter/charger |
| E | 125A breaker | Over-current protection |
| F | Power switch | Used to Power on/off battery |
| G | ON/OFF indicator | Indicates whether the battery is turned on or off |
| H | Reset | Used to reset the BMS |
| I | ADS | Used to set the address of the battery in the battery pack |
| J | RUN | Used to show battery is in running status when lighting or flashing |
| K | ALM | Used to show battery Alarm/Protection status |
| L | Dry contact | 2 channels output signal, 1 channel input signal (Pin1 on the left) |
| M | SOC | Used to show battery real-time SOC |
| N | RS485-1 | Connect to host computer/inverter |
| O | CAN | Connect to inverter |
| P | RS232 | Connect to host computer/inverter |
| Q | RS485 IN / RS485 OUT | For communication between batteries |
| R | Mounting ear | Used to fix with rack |
3.3.5 Communication Interface Pin Diagram

Figure 4: Communication Interface Pin Diagram
| Communication Port | Functional Description | PIN | Description |
|---|---|---|---|
| RS485-1 | Connect to host computer/inverter | 1,8 | RS485-B1 |
| 2,7 | RS485-A1 | ||
| 4 | NC | ||
| 5 | NC | ||
| CAN | Connect to host computer/inverter | 4 | CANH1 |
| 5 | CANL1 | ||
| 3,6 | GND | ||
| RS232 | Connect to host computer | 1,2,6 | NC |
| 3 | TX | ||
| 4 | RX | ||
| 5 | GND | ||
| RS485-2*2 | Parallel communication*2 | 1,8 | RS485-B2 |
| 2,7 | RS485-A2 | ||
| 4,5 | NC | ||
| 3 | N(L)/OUT(R) | ||
| 6 | GND |
3.3.6 Communication Protocols/Devices Supported by Each Port
| Port | Usage | Supported Protocols/Devices |
|---|---|---|
| RS485-1 | Connect to the inverter or upper computer | PYLON-LV RS485 V3.5 2019/08/07 (9600) |
| Growatt BMS-V1.09(1)-20201022 | ||
| VOLTRONIC-485-V1.0.3-200325 | ||
| LXP-485-V1.0.0-210625 | ||
| Deye-485 Modbus Protocol(4)-deye -V1.30-20160801 | ||
| SRNE WOW PACE BMS Modbus_Protocol for RS485 V1.3(2020-11-24) | ||
| CAN | Connect to the inverter | Pylon-CAN-V1.2-180408-lowVoltage |
| Growatt BMS CAN-Bus-protocol-low-voltage-V1.04 | ||
| Victron-CAN-V1.00-210107 | ||
| Luxpowertek Battery CAN Protocol-V1.0-20200211 | ||
| SMA-CAN-V1.0.0-210630-FSS-ConnectingBat-TIen--20W | ||
| Sofar-CAN-V1.00-211117-Rev6 | ||
| PV1800F-CAN communication Protocol1.04.04 | ||
| RS232 | Connect to the upper computer | JBD-UP |
| Solar Assistant | ||
| Overkill |
3.3.7 LED Indicator Light Description
| State of System | Event | MOS (LED9) | Run (LED8) | Alarm (LED7) | SOC (LED6-1) | Description |
|---|---|---|---|---|---|---|
| Power off | Sleep | OFF | OFF | OFF | OFF OFF OFF OFF OFF OFF | All LEDs turn off |
| Static state | Normal | OFF | Flash1 | OFF | Refer to table(4-11-2) | |
| Alarm | OFF | ON | Flash3 | The over voltage alarm does not flash | ||
| Charging | OV protect | ON | ON | ON | ON ON ON ON ON ON | |
| Temperature, Over-current, fail-safe | ON | OFF | ON | OFF OFF OFF OFF OFF OFF | ||
| Normal | OFF | Flash 3 | OFF | Refer to table(4-11-2) | ||
| Discharging | UV protect | ON | Flash2 | OFF | OFF OFF OFF OFF OFF OFF | |
| Over-current, short circuit, temperature, fail-safe | ON | OFF | ON | OFF OFF OFF OFF OFF OFF | ||
| Alarm | OFF | Flash 3 | Flash 3 |
3.3.8 LED Flash Description
| Flash Mode | ON Duration | OFF Duration |
|---|---|---|
| Flash1 | 0.25S | 3.75S |
| Flash2 | 0.5S | 0.5S |
| Flash3 | 0.5S | 1.5S |
3.3.9 Protection Mechanisms
| Item | Description | Remark |
|---|---|---|
| Charge End Cell/PACK high-voltage | BMS stops charging if any cell or PACK voltage reaches protection value. Auto-released when both Pack and cell voltage return to release range or efficient discharge current is present. | |
| Discharge End Cell/PACK low-voltage | BMS stops discharging if any cell or PACK voltage is under protection value. Auto-released when all cell voltages return to release range or efficient charge current is present. | Automatically recovers. Charge timely to avoid over-discharge into Low-power mode. |
| High temperature | BMS halts charging, discharging, or both if any cell, environment, or MOSFET temperature falls outside acceptable range. | Automatic recovery |
| Low temperature | BMS stops charging or discharging or both if any cell/environment/MOS temperature is under range. | Automatic recovery |
| Charge over-current | BMS stops charging when current is higher than protection value. Releases when system delay time is met. | Automatically recovers. If locked after three consecutive times, manual intervention is required. |
| Discharge over-current/Overload | BMS stops discharging when current is higher than protection value. Releases when system delay time is met. | Automatically recovers. If locked after three consecutive times, manual intervention is required. |
| Short-circuit/Reversed | Short-circuit and Reversed polarity protection occurred. | Charge to release Manual reset |
| Temperature, Voltage, Current sensor failure | Entering failure mode requires manual intervention; no charging and discharging. | Manual intervention |
| Dormancy mode | After reaching a certain condition, it enters dormancy mode. | Recoverable |
4. Installation
4.1 Preparation
4.1.1 Safety Compliance
The system installation must be performed by qualified person(s). During the entire installation process, strictly follow local safety regulations and related operating procedures.
4.1.2 Environment Requirements
| Category | Description |
|---|---|
| Working temperature | -20°C~55°C (maximum operating range) 15°C~30°C (optimal temperature) |
| Relative humidity | 5%~90%, No condensation |
| Altitude | <3000m |
| Safety requirement |
|
4.1.3 Tools Required
| Tool | Purpose |
|---|---|
| Screwdriver (slot, cross) | General fastening |
| Multi-meter | Electrical measurements |
| Wrench | Tightening fasteners |
| Clamp meters | Measuring current |
| Diagonal pliers | Cutting wires |
| Insulating tape | Insulating connections |
| Needle nose pliers | Holding and bending wires |
| Thermometer | Observing installation environment temperature |
| Clamping pliers | Securing components |
| Anti-static bracelet | Preventing electrostatic discharge |
| Wire stripper | Stripping wire insulation |
| Cable ties | Organizing cables |
4.2 Inspection
4.2.1 Unpack Precautions
- Load and unload the equipment according to specified requirements to prevent sun and rain damage.
- Check and confirm the goods (quantity, appearance, etc.) against the 'scope of delivery' before unpacking.
- Handle with care during unpacking to protect the surface coating.
- Record and contact the manufacturer if the inner packing is damaged after unpacking.

Figure 5: General Materials Included
4.2.2 External Cable Kits (Optional, not included)
Cables connected to the inverter or junction box are external cable kits and are NOT included in the battery carton. Customers need to purchase them separately. Information is provided below:
| Type | Detail | Qty. |
|---|---|---|
| Battery to Battery Communication Cable | Standard communication cable (200mm length) | 1PCS |
| Parallel Cables | Battery to Battery positive cable (2AWG 2000mm RED) | 1PCS |
| Battery to Battery negative cable (2AWG 2000mm BLACK) | 1PCS | |
| Grounding Cable | Grounding cable (0T1.5-5, 200mm length) | 1PCS |
| Cables (Inverter Connection) | Battery to Inverter positive cable (2/0AWG 2000mm RED) | 1PCS |
| Battery to Inverter negative cable (2/0AWG 2000mm BLACK) | 1PCS |
4.3 Installation Procedures
4.3.1 Pre-installation Reminders
Before installation, re-check the following conditions and equipment:
- Sufficient space for installation, and that the bracket or cabinet's load-bearing capacity meets weight requirements.
- Power cable pair(s) meet the maximum current requirement for operation.
- Overall layout of power supply equipment and batteries at the construction site is reasonable.
- Installer is wearing an anti-static wristband.
- Two people are present for installation work.
- No potential risks at the installation site, such as flooding, sun exposure, corrosion, or salt spray.
4.3.2 Install the Battery into the Rack Slot
Carefully insert the battery into the designated rack slot.

Figure 6: Inserting Battery into Rack Slot
4.3.3 Set the Inverter Communication Protocol
To set up communication with your inverter:
- Turn on the battery:
- Open the 125A Circuit Breaker.
- Press the POWER button.
- Use the mobile app to set the communication protocol:
- Scan the QR code below to download the software.
- Open the software and search for nearby devices (ensure Bluetooth is on and permissions are granted).
- Modify the Inverter Protocol on the Parameter page (refer to APP-Quick Start for detailed information).

Figure 7: Communication with Inverter and App Monitoring
4.3.4 Connect the Battery to the Inverter
- Battery-inverter power connection:
Note: Turn off the POWER button and the breaker before connecting cables. Use the cables required by the inverter to connect the battery pack to the BAT input terminal of the inverter. - Battery-inverter communication connection:
Use a standard Ethernet cable to connect the battery's RS485-1 or CAN port to the BMS communication port of the inverter.

Figure 8: Connecting Battery to Inverter
4.3.5 Important Notes for Connection
5. Operation
5.1 Turning On/Off
To turn on the battery, ensure the 125A circuit breaker is open, then press the POWER button on the front panel. To turn off, press the POWER button again and close the 125A circuit breaker.
5.2 LED Indicators
The front panel features LED indicators (MOS, Run, Alarm, SOC) that provide real-time status information. Refer to Table 9: LED Indicator Light Description and Table 10: LED Flash Description in the Specifications section for detailed interpretation of these indicators during various states (Power off, Static state, Charging, Discharging).
5.3 Communication
The battery supports RS485, CAN, and RS232 ports for communication with inverters and upper computer systems. Bluetooth and WiFi capabilities allow for wireless monitoring via a mobile application. Ensure proper cable connections and protocol settings as detailed in the Installation section.
5.4 Parallel Operation
The DATOUBOSS battery supports connecting up to 15 units in parallel for increased capacity. When operating in parallel, the system can use either automatic addressing or manual DIP switch settings. If all DIP switches are dialed to OFF, the manual DIP address function is enabled. Otherwise, the default automatic addressing function is used. Refer to the 'ADS' section in the Product Overview for detailed DIP switch configurations.
6. Maintenance
6.1 Storage Guidelines
- Store the battery in a dry, clean, dark, and well-ventilated indoor environment.
- The recommended long-term storage temperature range is 15°C to 30°C.
- Ensure no harmful gases, flammable and explosive products, or corrosive chemical substances are present in the storage location.
- Batteries should be stored and transported at approximately 50% State of Charge (SOC). Do not store over 80% SOC for extended periods.
- If the battery is not used for a long time, it needs to be charged every 6 months.
- Do not drop the battery, pile it up over 6 layers, and always keep it face up.
6.2 Optimal Operating Temperature
The optimal operating temperature range for the battery is 15°C to 30°C. Frequent exposure to extreme temperatures outside this range may negatively impact the battery's performance and shorten its cycle life.
7. Troubleshooting
| Item | Solution | Measure |
|---|---|---|
| Unable to start | 1. Switch on battery and press RESET for 6s to observe whether the battery can be started. 2. Charge the battery with a charger or inverter to provide 54-57.6V voltage and observe whether it can be started. | |
| Unable to charge | 1. Check whether the cable connection between the battery and the inverter/charger is correct. 2. Check whether the inverter/charger setting is correct. 3. Check whether the battery is in charge protection mode; if yes, try to discharge the battery. | If the abnormal status is still present after these steps, please contact your supplier. |
| Unable to discharge | 1. Check whether the cable connection between the battery and the inverter/charger is correct. 2. Check whether the battery occurs short circuit, reverse connection, pre-charge failure during connection inverter etc. 3. Check whether the battery is in discharge protection mode; if yes, try to charge the battery. | |
| High/Low temperature | 1. Stop the battery system for a while, and check whether the installation location temperature meets the requirement. 2. Avoid continuous full charging and discharging. | |
| High current | Check whether the configuration and parameters setting on the inverter/charger is correct. | If there is any other situation(s) not listed in this table, turn off the faulty battery, and contact your supplier. |
| ALM ON | Turn off all the batteries, and remove the fault battery from the system. | |
| Communication fail | 1. Check whether the communication cable type is correct and is contacted well. 2. Check whether the DIP switch setting is correct. 3. Check whether the inverter protocol related setting is correct. 4. Check whether both battery and inverter are working properly. |
8. User Tips
- Familiarize yourself with LiFePO4 battery characteristics and system integration before installation for a smoother setup.
- Always double-check all connections and settings, especially communication protocols, to ensure proper functionality and avoid issues.
9. Disposal of Battery