1. Introduction
This is a multi-function inverter/charger, combining functions of inverter, MPPT solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
1.1 Features
- Pure sine wave inverter
- Maximizes solar energy harvest through advanced MPPT technology.
- Supports flexible charging from PV, utility, and generator sources.
- Supports flexible power supply from PV, battery, utility, and generator.
- Supports load operation without battery connection.
- Provides a wide input voltage and frequency range for unstable grids.
- Features a lightweight design for easy installation and maintenance.
- Provides a large LCD display for clear system monitoring.
- Supports both lithium and lead-acid batteries.
- Supports remote monitoring via WiFi mobile APP.
1.2 Basic System Architecture
The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system: Generator or Utility, PV modules (option). Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.

2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
- CAUTION - To reduce the risk of injury, only rechargeable batteries such as deep cycle lead-acid or lithium batteries can be charged. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION - Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. Installation
3.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:
- The unit x 1
- User manual x 1 (Refer to this document)
- Fixed bracket x 2
- Screws x 4
- WIFI module x 1
3.2 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall.
- Be sure to keep other objects and surfaces as shown in the figure below to ensure sufficient heat dissipation and adequate space for cable removal.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing four screws. It's recommended to use M4 or M5 screws.

3.3 Wiring
3.3.1 Preparation
Before connecting all wirings, please take off the bottom cover by removing four screws as shown below.

3.3.2 Grounding
Before making any electrical connections, connect the inverter grounding terminal to a reliable protective earth (PE) conductor in accordance with local electrical regulations. The grounding terminal is located on the side panel of the inverter. Ensure that the grounding connection is completed before connecting photovoltaic modules, batteries, utility power, or loads.
WARNING: Failure to properly ground the inverter may result in electric shock, equipment damage, or improper system operation.
3.3.3 Battery Connection
For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to the table for the recommended fuse or circuit breaker size.
| Model | Wire Size | Cable (mm²) | Torque value | Recommended Circuit Breaker Size |
|---|---|---|---|---|
| 7KW | 1*2AWG | 38 | 5 Nm | 200A |
WARNING:
- All wiring must be performed by qualified personnel.
- It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size.
Please follow below steps to implement battery connection:
- Assemble battery ring terminal based on recommended battery cable and terminal size.
- The 7KW model supports a 48V battery system. The connection is shown in the diagram below.

- Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals.

WARNING: Shock Hazard - Installation must be performed with care due to high battery voltage in series.
CAUTION: Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
3.3.4 AC Input/Output Connection
Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
| Model | Gauge | Torque Value | Recommended Circuit Breaker Size |
|---|---|---|---|
| 7KW | 10 AWG | 1.4~1.6 Nm | 63A |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10 mm for six conductors. And shorten phase L and N 3 mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. (L→LINE (brown or black); N→Neutral (blue))

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
- Insert AC output wires according to polarities indicated on terminal block and tighten the terminal screws. (L→LINE (brown or black); N→Neutral (blue))
- Make sure the wires are securely connected.

CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
3.3.5 PV Connection
Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
| Model | Gauge | Torque Value | Recommended Circuit Breaker Size |
|---|---|---|---|
| 7KW | 12 AWG | 1.4~1.6 Nm | 32A |
PV module selection:
Before selecting a suitable solar module, please refer to the following requirements:
- The open circuit voltage (Voc) of the solar module shall not exceed the maximum open circuit voltage of the inverter (<450VDC).
- The open circuit voltage (Voc) of the solar module should be higher than the minimum input voltage of the inverter PV (>150VDC).
The following is an example of a 380Wp solar panel configuration system. After considering the above two parameters, the recommended configuration is shown in the table below. For other specifications of components, the number of series and parallel connections is determined based on the open circuit voltage not exceeding 450V and the optimal working voltage of 360V.
| Panel Power | Rated Voltage/Rated Current | Open-Circuit Voltage / Short-Circuit Current | Number | Total rated power / Total rated voltage |
|---|---|---|---|---|
| 380Wp | 40.10V/9.49A | 48.82V/9.99A | 8 pieces in series and 2 pieces in parallel | 6080Wp/321V |
| 500Wp | 40.08V/12.48A | 47.28V/12.18A | 9 pieces in series | 4500Wp/361V |
| 550Wp | 40.05V/13.73A | 46.30V/13.50A | 9 pieces in series | 4950Wp/360V |
| 590Wp | 39.09V/15.09A | 47.30V/15.85A | 9 pieces in series | 5310Wp/352V |
| 615Wp | 39.96V/15.39A | 48.30V/16.10A | 9 pieces in series | 5535Wp/360V |
| 660Wp | 38.10V/17.33A | 45.70V/18.42A | 9 pieces in series | 5940Wp/343V |
| 710Wp | 40.69/17.45 | 48.94V/18.45A | 9 pieces in series | 6390Wp/366V |
Please follow below steps to implement PV modules connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Insert PV input wires according to polarities indicated on terminal block and tighten the terminal screws.
- Check correct polarity of wire from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector.

3.4 Final Assembly
After connecting all wirings, please put the bottom cover back by screwing four screws.
4. Operation
4.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected, follow the power-on sequence below to start the inverter safely:
- Close the battery circuit breaker.
- Press the On/Off switch (located on the bottom of the case) to turn on the unit. Wait until the inverter starts up and enters normal operation (inverting).
- Close the PV, AC input and AC output circuit breaker.
To shut down the system, turn off the circuit breakers in the reverse order.

4.2 Operation and Display Panel
The inverter features an LCD display and buttons for operation and monitoring.

4.2.1 Function Keys
| Function Key | Description |
|---|---|
| PRG/ESC | To enter setting mode or exit setting mode |
| UP | To go to next selection |
| DOWN | To go to previous selection |
| ENTER | To confirm the selection in setting mode |
4.2.2 LED Indicator
| LED Indicator | Messages | |
|---|---|---|
| CHG | Green Solid On | Battery is fully charged. |
| Flashing | Battery is charging. | |
| AC/INV | Green Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by battery or PV in battery. |
Note: When a fault occurs, the device displays only the fault code and does not indicate a fault via an LED indicator. For detailed descriptions of fault codes, please refer to Section 5.
4.2.3 LCD Display Icons
The LCD display uses various icons to convey system status and information.

| Icon | Function description |
|---|---|
| Indicates the PV input | |
| Indicates the AC input | |
| 8.8.8VCA% | Indicate input voltage, input current, PV voltage, battery voltage and charger current. When "dxx" is displayed, it indicates that the system has entered the settings mode. |
| 8.8 | Indicates the fault codes |
| 8.8.8VHzAKW | Indicate output voltage, output frequency, load in Watt. |
| Battery charging label | |
| OVER LOAD | Indicates overload |
| Indicates the load (with percentage segments) | |
| Indicates unit connects to the PV panel. | |
| Indicates the utility /MPPT charger circuit is working. | |
| Indicates the DC/AC inverter circuit is working. |
4.2.4 LCD Settings (d01-d25)
After pressing and holding the PRG button for 1 second, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit.
| NO. | Setting Page | Selection Information |
|---|---|---|
| d01 | Output Source Priority | SUB (default): Solar → Utility → Battery Mode: Solar power is prioritized for load supply. When PV power is insufficient, utility power supplements the loads. If utility power is unavailable, the loads are powered by PV and the battery. With utility available, the inverter enters battery discharge mode after the battery voltage reaches the d12 setting for 10 minutes, and returns to charging mode when the battery voltage drops 2 V below d12. Without utility power, the inverter supplies the loads from PV and the battery and stops AC output when the battery voltage falls below the d11 setting. When sufficient PV power is available, the battery charging voltage can reach the maximum value set by d15. UFI: Utility First Mode: Utility power is prioritized to supply the loads, while PV power or utility power keeps the battery fully charged at all times. In the event of a utility power failure, the inverter immediately switches to inverter mode to supply the loads. When utility power is available, the inverter enters battery discharge mode after the battery voltage reaches the value set by parameter d15 for 10 minutes; when the battery voltage falls 2 V below the d15 setting, the inverter switches to battery charging mode. ONI: Inverter Priority Mode: The inverter enters battery discharge mode after the battery voltage reaches the value set by parameter d15 and remains at this level for 10 minutes. When the battery voltage falls below the value set by parameter d11, the inverter switches to battery charging mode. NBU: Battery-Free AC-Coupling Mode: In this mode, the inverter can operate without a battery. The load is powered by both the PV array and the utility grid. For example, if the PV array generates 1 kW while the load requires 2 kW, the remaining 1 kW is supplied by the utility grid. If the load decreases to 500 W, the utility grid will no longer supply power, and the load will be powered entirely by the PV array. Any excess PV power (500 W in this example) will not be exported to the utility grid, ensuring zero-export operation. |
| d02 | Utility Input Voltage Range | WID: Wide input voltage range: 90-270VAC NOR (default): Normal input voltage range: 160-240VAC |
| d03 | AC Output Voltage | 220V (default), 230V, 240V: AC output voltage: adjustable 220/230/240V. |
| d04 | AC Output Frequency | 50Hz (default), 60Hz: AC output frequency: 50 Hz or 60 Hz. |
| d05 | SOC Charge/Discharge Control Enable | OFF (default): Disable SOC Charge/Discharge Control ON: Enable SOC Charge/Discharge Control (Note: This parameter must be enabled for d19 and d20 to take effect.) |
| d06 | Charging Source Priority | CSO: Solar priority charging CUT: Utility priority charging SNU (default): Solar and utility charge the battery together OSO: Solar only charges the battery |
| d07 | Battery Type | Pb: Operate with lead-acid batteries (this setting enables float charging mode) Li (default): Operate with lithium batteries (this setting disables float charging mode, and the maximum battery cutoff voltage is limited by parameter d15) |
| d08 | Maximum Inverter Output Power | 7KW (default): This parameter is factory-set according to the 7 kW unit specification and is not user-adjustable. |
| d09 | Rated Battery Voltage | 48V (default): This parameter is factory-set according to the 48V system specification and is not user-adjustable. |
| d10 | Restore Factory Default Settings | OFF (default): Do not restore factory default settings ON: Restore factory default settings |
| d11 | Utility Mode Voltage Point Setting | 46.0V (default): When the inverter is operating in inverter mode, if the battery voltage falls below the set threshold, the system will automatically switch to grid mode. In this case, the load is supplied by the utility grid, and the inverter enters standby mode. The battery will no longer discharge energy to external loads. Setting range: 44-52V, with 0.1V increment per adjustment. |
| d12 | Battery Mode Voltage Point Setting | 53.0V (default): When the inverter is in standby mode, although the load is supplied by the grid, if solar MPPT charging or grid charging raises the battery voltage above the set threshold, the system will automatically switch back to inverter mode. In this case, the load is powered by the inverter, and both the battery and solar energy will supply power to the load. Any excess solar energy will be stored in the battery. Setting range: 48-56V, with 0.1V increment per adjustment. (Note: Parameters d11 and d12 are linked to the Output Source Priority settings. The SUB and SBU modes selected in parameter d01 operate according to the values of d11 and d12. To prevent improper configuration, the inverter verifies these parameter settings automatically. The voltage difference between d11 and d12 must be maintained at 4-5 V; otherwise, the inverter may switch repeatedly between inverter power and utility power.) |
| d13 | Utility Charging Current for Battery | 30A (default): Setting range: 0.5-60A, with 1A increment per adjustment. Note: Must be lower than the inverter's rated current. |
| d14 | Solar Charging Current for Battery | 80A (default): Setting range: 0-100A, with 1A increment per adjustment. Note: Must be lower than the inverter's rated current. |
| d15 | Bulk Charging Voltage | 56.0V (default): This parameter defines the final constant voltage level after the battery is fully charged. It is used to control the voltage maintenance level during the constant-voltage charging stage and is applicable to both lithium and lead-acid batteries. When parameter d07 is set to lead-acid battery mode, this value serves as the equalization charging voltage. The float charging voltage will follow a preset value of 13.8V per cell and operate automatically (the float voltage can be adjusted separately via the app). When parameter d07 is set to lithium battery mode, this value serves as the final equalization charging voltage. The battery voltage will be maintained at this set level to ensure cell balancing management. This parameter can be adjusted according to different battery specifications to meet actual system requirements. Setting range: 51-59V, with 0.1V increment per adjustment. |
| d16 | Zero Export Mode (Anti-backflow) | ON (default): When Zero-Export Mode is enabled, the inverter supplies only the power required by the load. If the load demand exceeds the inverter's output capacity, the utility grid supplies the remaining power. OFF: When Zero-Export Mode is disabled, surplus PV power can be exported to the utility grid. |
| d17 | System Power ON/OFF Status | ON (default): The system is currently powered ON. OFF: The system is currently powered OFF. |
| d18 | Maximum Output Current | 15.0A (default): This parameter defines the maximum AC output current of the inverter and must be set below the inverter's rated output current. For example, if the maximum output current is set to 15A at 220V, the corresponding maximum output power is approximately 3.3 kW (15A × 220V). In grid-connected anti-backflow (zero export) operation, this parameter is used to indirectly limit the inverter's output power by restricting the AC output current. |
| d19 | Charge SOC Threshold | 50% (default): When the battery SOC falls below the set threshold, the battery will start charging. The setting range is 0-100%, and the set value must be lower than the Discharge SOC. In general, it is recommended to set it 10% lower than the Discharge SOC. (Note: If the inverter is operating in discharge mode, battery discharging will stop when the battery SOC falls below this value.) |
| d20 | Discharge SOC Threshold | 100% (default): When the battery SOC exceeds the set threshold, the battery will start discharging. The setting range is 0-100%. |
| d21 | Battery Charge/Discharge Control | 0 (default): After the charging or discharging process is completed, this parameter will automatically reset to zero. 1: The system enters charging mode. 2: The system enters discharging mode. |
| d22 | Factory Test Mode Switch | OFF (default): This setting is reserved for factory use and cannot be changed by the user. |
| d23 | Zero-Export Activation Threshold | 70W (default): When the inverter detects that the load power exceeds 70W, the zero-export function is activated. If the load power is below 70W, the zero-export function remains inactive. In other words, zero-export control is applied only when the load power exceeds the configured activation threshold. Purpose: Allows users to adjust the zero-export activation threshold to compensate for sensor accuracy errors, thereby minimizing unintended power export to the utility grid. |
| d24 | External CT Zero-Export Switch | OFF (default): This model does not support an external CT. The load connected to the backup (off-grid) output must not exceed the inverter's rated output power. The built-in CT monitors the load power, allowing the inverter to regulate its output and provide hybrid power from both the utility grid and the inverter at the backup (off-grid) output. Setting range: 20-200W, with 10W increment per adjustment. |
| d25 | Parallel Power Balancing Parameter | 50 (default): When operating in parallel, if the output power among the inverters is unbalanced, this parameter can be adjusted to achieve more even load sharing. |
4.2.5 Main Display Screen
Press the "Up" or "Down" buttons to preview the main display screens.


Additional display screens show:
- Page 2: Current inverter temperature (e.g., 31.3°C), inverter output frequency (e.g., 50Hz), and indication of load supplied by battery power.
- Page 3: Current battery voltage (e.g., 28.2V), battery DC current, and indication of constant-voltage equalization charging mode.
- Page 4: Current PV voltage (e.g., 58.2V), displayed PV current value (e.g., 1.1A), and indication of constant-voltage equalization charging mode.
- Page 5: Current MPPT temperature (e.g., 29.3°C), current solar power generation (e.g., 33.3Wh), and indication of constant-voltage equalization charging mode.
- Page 6: Current internal high voltage of the inverter (e.g., 419V), accumulated power generation (e.g., 20.3Wh, switches to kWh if >1kWh), and indication of float charging mode.
- Page 7: Current battery SOC display, current battery SOH display, and indication of float charging mode.
4.3 Communication Wiring Between the Inverter and BMS
The inverter supports communication with a Battery Management System (BMS).
4.3.1 Inverter Communication Port Pin Definition (RJ45)
| RJ45 Pin | Definition |
|---|---|
| Pin 1 | / |
| Pin 2 | / |
| Pin 3 | / |
| Pin 4 | CAN-H (Internal BMS Communication) |
| Pin 5 | CAN-L (Internal BMS Communication) |
| Pin 6 | / |
| Pin 7 | / |
| Pin 8 | / |
4.3.2 Communication Wiring Between the Inverter and BMS
- Inverter communication board network port pin4 (CAN-H) connects to network interface board BMS port pin x (CAN-H);
- Inverter communication board network port pin5 (CAN-L) connects to network interface board BMS port pin x (CAN-L);

5. Fault Codes and Troubleshooting
When a fault occurs, the device displays a fault code. Refer to the table below for detailed descriptions of fault codes, their causes, and recommended solutions.
| Fault Code | Fault Status | Cause and Description | Solution |
|---|---|---|---|
| E0 | Input undervoltage protection | Utility input voltage is too low. | If a wider utility voltage range is required, set d02 to WID. If the problem still cannot be resolved after setting d02 to WID, check whether the input voltage is too low. |
| E1 | Input overvoltage protection | Utility input voltage is too high. | If a wider utility voltage range is required, set d02 to WID. If the problem still cannot be resolved after setting d02 to WID, check whether the input voltage is too high. |
| E2 | Input over-frequency protection | Input frequency exceeds the preset frequency range. | For 50Hz systems, the acceptable input frequency range is 45Hz-55Hz. For 60Hz systems, the acceptable input frequency range is 55Hz-65Hz. If the system frequency exceeds 65Hz, an over-frequency fault will be triggered. Check the utility grid frequency. |
| E3 | Input Underfrequency Protection | The input frequency is outside the preset operating range. | For 50Hz systems, the acceptable input frequency range is 45Hz-55Hz. For 60Hz systems, the acceptable input frequency range is 55Hz-65Hz. If the system frequency falls below 45Hz, an over-frequency fault alarm will be triggered. Please check the utility grid frequency. |
| E4 | Frequent Grid Switching | Excessive switching between utility mode and inverter mode is one of the most common issues encountered in energy storage applications. The root cause is usually poor battery performance. | 1. Battery-related causes: When the battery is supplying a heavy load and the battery voltage drops below the d11 setting, the inverter automatically transfers to utility mode. If PV charging continues, the battery voltage may recover quickly and exceed the d12 setting, causing the inverter to switch back to inverter mode. This repeated transition can result in more than 8 switching events within one hour. 2. Poor battery performance: If the battery has limited performance (such as a lead-acid battery) while supplying a high load, it is recommended to use SBU/SUB mode, set d11 to the lowest value, and set d12 to the highest value in order to reduce the switching frequency. 3. Use a higher-performance battery: Replacing the battery with a higher-performance lithium battery can effectively resolve this issue. After this fault code is triggered, the inverter will lock the current operating state for one hour and then automatically recover. During this period, the inverter may stop operating. 4. Battery voltage rebound effect: Users often assume the battery still has sufficient capacity because the displayed voltage appears normal. However, this may only be a temporarily elevated voltage with little actual capacity available. When a load is applied, the battery voltage can drop rapidly and trigger inverter protection. |
| E5 | Inverter Short Circuit | The inverter has detected a short-circuit fault. | Please disconnect the load from the inverter and carefully inspect the load for any short-circuit points. It is recommended to connect the inverter output to the load through a circuit breaker, as the circuit breaker also provides protection. |
| E6 | Inverter Overload | The inverter has encountered an overcurrent/overload fault. | 1. When the inverter is operating in off-grid mode, please check whether the load is overloaded or whether the load current is too high. 2. When the inverter is operating in charging mode, please check whether the charging current is set too high, or whether a short-circuit condition exists on the battery side. 3. When the inverter is operating in grid-tied mode, please check whether the grid-tied current setting is too high. |
| E7 | Inverter Bus Overvoltage | Abnormal utility grid voltage. | Please check the external AC input voltage. Excessively high utility voltage may cause inverter faults. Disconnect the inverter from the external AC power source if the utility voltage is abnormal. |
| E8 | PV1 Input Overvoltage | The operating voltage of the solar panels connected to the PV1 terminal is too high. | Please check the operating voltage of the solar panels. A recommended open-circuit voltage of approximately 400V is considered optimal. |
| E9 | PV2 Input Overvoltage | The operating voltage of the solar panels connected to the PV2 terminal is too high. | Please check the operating voltage of the solar panels. A recommended open-circuit voltage of approximately 400V is considered optimal. |
| EA | PV1 Overcurrent Protection | An overcurrent condition has occurred at the PV1 input terminal. | Please check the operating voltage of the solar panels. A recommended open-circuit voltage of approximately 400V is considered optimal. Also check whether the PV terminals have been incorrectly connected or damaged. |
| EB | PV2 Overcurrent Protection | An overcurrent condition has occurred at the PV2 input terminal. | Please check the operating voltage of the solar panels. A recommended open-circuit voltage of approximately 400V is considered optimal. Also check whether the PV terminals have been incorrectly connected or damaged. |
| EC | Charging Overcurrent Protection | During charging, the battery current exceeds the inverter's rated current. | Please check whether the battery is damaged or whether a short circuit exists at the battery terminals. |
| ED | Charging Overvoltage Protection | The battery terminal voltage is too high. | Please check whether parameter D15 is set too high, or whether the battery terminal voltage is excessively high. |
| EE | Battery Voltage Protection | The battery voltage has exceeded the preset parameter value, or the battery is fully discharged. | 1. The battery may have been disconnected from the inverter. Please check the battery wiring and grounding connections. For lithium batteries, the BMS may have disconnected the battery. 2. The battery may already be fully discharged or unable to support heavy loads. In this case, it is recommended to replace it with a higher-performance battery. |
| EF | INV Overtemperature Protection | The inverter temperature has exceeded 85°C. | Please ensure proper ventilation and heat dissipation, use the correct installation method, and wait for the inverter to cool down and recover automatically. |
| EG | MPPT1 Overtemperature Protection | The MPPT1 temperature has exceeded 85°C. | Please ensure proper ventilation and heat dissipation, use the correct installation method, and wait for the inverter to cool down and recover automatically. |
| EH | MPPT2 Overtemperature Protection | The MPPT2 temperature has exceeded 85°C. | Please ensure proper ventilation and heat dissipation, use the correct installation method, and wait for the inverter to cool down and recover automatically. |
| EI | BMS Fault | A fault has occurred in the battery BMS. | The BMS connection has been disconnected. Please reconnect it. |
Note: Displaying "99" indicates normal status.
6. Maintenance
To maintain optimum and long-lasting working performance, we recommend that the following items are checked twice a year.
- Ensure that the airflow around the inverter is not blocked and remove any dirt or debris from the radiator.
- Check that all exposed conductors are not damaged by sunlight, friction with other surrounding objects, dry rot, insect or rodent damage, etc. The conductors need to be repaired or replaced if necessary.
- Verify that the indications and displays are consistent with the operation of the equipment, note any faults or incorrect displays and take corrective action if necessary.
- Check all terminals for signs of corrosion, insulation damage, high temperatures or burning/discoloration and tighten terminal screws.
- Check for dirt, nesting insects and corrosion, clean as required, Clean the insect screen regularly.
- If the lightning arrester has failed, replace the failed arrester in time to prevent lightning damage to the inverter or other equipment of the user.
DANGER: Before conducting any inspection or operation, please ensure that the inverter is disconnected from all power sources and that the capacitor is fully discharged to avoid the risk of electric shock.
6.1 Paid Repair Services
Paid repair services will be provided under the following circumstances:
- The product is beyond the warranty period.
- Damage caused by installation that does not comply with the product requirements, standards, or applicable regulations.
- Damage caused by related accessories in the installation environment that do not comply with the product requirements, standards, or applicable regulations.
- Quality issues resulting from improper use, improper storage, unauthorized repair, modification, disassembly, or other abnormal operations by the user.
- Damage caused by natural disasters (such as earthquakes, floods, or lightning strikes) or external events (such as fires or building collapses).
- Malfunctions or damage caused by relocation, transportation, or improper storage after the installation site has been changed.
7. Specifications
| Category | Parameter | Value |
|---|---|---|
| AC Input | Rated voltage | 230Vac |
| Voltage range | 170-270Vac (UPS); 90-280Vac (APL) | |
| Maximum input voltage | 280VAC | |
| Rated input frequency | 50Hz/60Hz (Adaptive) | |
| Frequency range | 40-65Hz | |
| Transfer range | 10ms (UPS); 20ms (APL) | |
| Maximum AC charging current | 60A | |
| AC Output | Rated output capacity | 7KW |
| Rated output voltage | 220/230/240Vac | |
| Voltage accuracy | ±5% | |
| Rated output frequency | 50Hz/60Hz | |
| Frequency accuracy | ±2% | |
| Output waveform distortion (THD) | ≤3% (100% linear load) | |
| Power factor | 1 | |
| Maximum conversion efficiency | 94.2% | |
| Grid-connected output overload current | 50A | |
| Off-grid Load Capacity | 110% < Load < 150% (±10%) | Alarm and shutdown after 10 seconds |
| 150% < Load < 200% (±10%) | Alarm and shutdown after 5 seconds | |
| Load > 200% (±10%) | Immediate alarm and shutdown | |
| Battery | Battery type | Lead-acid / Lithium battery |
| Rated input voltage | 48VDC | |
| Battery voltage range | 46.4-58.8V | |
| Maximum charging current | 135A | |
| Float charging voltage | 53.5V (Lead-acid); User-defined for Lithium Battery | |
| Equalization charging voltage | 56.5V (Lead-acid); User-defined for Lithium Battery | |
| PV Input | Maximum PV input power | 7000W |
| Maximum PV input current | 25A | |
| Nominal operating voltage | 360Vdc | |
| PV input voltage range | 100-450VDC | |
| Maximum PV input voltage | 450VDC | |
| Maximum PV charging current | 120A | |
| General Parameters | Dimensions | 385*320*105mm |
| Net Weight | 7.7kg | |
| Noise | ≤48dB | |
| Operating temperature range | -20°C~+50°C | |
| Storage temperature | -15°C~+65°C | |
| Operating humidity range | 0~90% (Non-condensing) | |
| Operating altitude | ≤6000m | |
| Protection | Battery overvoltage protection | Yes |
| Overload protection | Yes | |
| Output short-circuit protection | Yes | |
| Over-temperature protection | Yes |
8. Appendix: Parallel Connection
The inverter supports up to 6 units of single-phase parallel connection for expanded output power, without the need for external parallel communication cables.
8.1 Cautions for Parallel Connection
- PV wiring: In parallel connection, the PV array of each inverter must be independent.
- Battery wiring: In a parallel system, all solar inverters may be connected to a common battery bank or to separate battery banks. Ensure that the battery polarity is connected correctly (BAT+ to BAT+ and BAT- to BAT- where applicable). Before power-on and start-up, verify that all battery connections, cable lengths, and cable sizes are correct and properly matched to prevent abnormal operation of the parallel system.
- AC OUT wiring: In single-phase parallel connection, all solar inverters must be connected in the manner of L-to-L, N-to-N, and PE-to-PE, and before power on and start-up, it is necessary to check and ensure correct connection, wiring length, and cable size, so as to avoid the abnormal operation of parallel system output caused by wrong connection.
- AC IN wiring: In single-phase parallel connection, all solar inverters must be connected in the manner of L-to-L, N-to-N, and PE-to-PE, and before power on and start-up, it is necessary to check and ensure correct connection, wiring length, and cable size, so as to avoid the abnormal operation of parallel system output caused by wrong connection. Meanwhile, it is not allowed to have multiple different AC source inputs to avoid damage to the external equipment of the inverter. The AC source input shall be consistent and unique.
- Before and after connecting the system, please carefully refer to the following system wiring diagrams to ensure that all wiring is correct and reliable before power on.
- After the system is correctly wired, powered on, and in normal operation, if a new inverter needs to be connected, make sure to disconnect the battery input, PV input, AC input and AC output, and that all solar inverters are powered off before reconnecting into the system.
8.2 Single-Phase Parallel System Diagram
Two inverters in parallel:

Three inverters in parallel:

Four inverters in parallel:

Five inverters in parallel:

Six inverters in parallel:

9. User Tips
- Check Package Contents: Some users noted that cables might not be included, so verify all necessary components upon arrival.
- Wi-Fi Module: The Wi-Fi functionality is provided via a separate module, not built-in. Ensure it is properly connected if remote monitoring is desired.
- Battery Compatibility: The inverter supports both 12V, 24V, and 48V battery systems depending on the model (e.g., 2.5KW 12V, 3.5KW 24V, 7KW 48V, 13.2KW 48V). Ensure your battery voltage matches the inverter model.
- Charging Options: The inverter supports charging from solar, utility grid, and generators. Configure the charging source priority (d06 setting) according to your needs.
- System Sizing: When considering solar panels, ensure the open circuit voltage (Voc) does not exceed 450VDC and is above 150VDC for optimal performance.
10. Warranty and Support
For technical support, warranty claims, or further assistance, please contact PowMr customer service:
- Email: support@powmr.com
- Website: www.powmr.com
- Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China
- Phone/Fax: +86 755-28219903
Please refer to the "Maintenance" section for conditions under which paid repair services may be provided.