ECGSOLAX ECG-LVM8K-SP

Contents

ECGSOLAX 8KW Hybrid Solar Inverter User Manual

Model: ECG-LVM8K-SP

1. Introduction

This manual provides detailed instructions for the assembly, installation, operation, and maintenance of your ECGSOLAX 8KW Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference. This document is intended for both qualified personnel and end-users, ensuring safe and efficient use of the inverter.

1.1 Product Description

The ECGSOLAX Hybrid Solar Inverter series integrates and manages photovoltaic systems, storage batteries, the power grid, and connected loads. It delivers stable, safe, and clean electricity suitable for residential, commercial, and industrial applications, meeting diverse energy needs.

1.2 Key Features

  • Supports various energy storage batteries (lead-acid, lithium-ion).
  • Provides single-phase and split-phase pure sine wave output.
  • Adjustable voltage for each phase (100~130V).
  • Single-channel photovoltaic input with MPPT tracking (efficiency up to 99.9%, max 27A per channel).
  • Two output modes: mains bypass and inverter output, with uninterrupted power supply.
  • Four charging modes: PV only, Mains priority, PV priority, Mains & PV hybrid charging.
  • Timed battery charging and discharging.
  • Energy-saving mode to reduce no-load energy loss.
  • Multiple protection functions for photovoltaic panels, batteries, loads, and the controller.
  • Capacitive intelligent touch screen for intuitive parameter setting.
  • Stores 256 event records and 1024 days of historical data.
  • Built-in Bluetooth and Wi-Fi for cloud platform access and automatic time synchronization.

2. Important Safety Instructions

Please read all instructions and cautionary markings before using the unit.

  • Ensure correct battery system selection (lithium or lead-acid).
  • Do not disassemble the unit; refer to qualified service personnel for repairs.
  • All electrical operations and connections must be performed by a professional engineer and comply with local safety standards.
  • CAUTION: Charge only deep-cycle lead-acid or lithium rechargeable batteries. Other types may burst.
  • Disconnect all wirings before maintenance or cleaning to prevent electric shock.
  • Select appropriate cable sizes as per specifications for optimum operation.
  • GROUNDING: This inverter must be connected to a permanent grounded wiring system.
  • Never short-circuit AC output or DC input. Do not connect to mains with DC input short circuits.
  • Avoid installing in harsh environments (moist, oily, flammable, explosive, dusty).
  • Only qualified personnel should repair this equipment.
  • Do not reverse battery input polarity to prevent damage.
  • Ensure the inverter is fully assembled before operation.
  • Confirm the inverter AC output is the sole input device for the load; do not parallel with other AC power sources.
  • Attach proper fuses or circuit breakers externally.

3. Setup and Installation

3.1 System Components

A complete system typically consists of:

  • Photovoltaic Modules: Convert light into DC electricity, charge batteries, or supply AC power to loads.
  • Mains Power or Generator: Supplies power to loads and charges batteries via AC input.
  • Battery: Ensures power supply to loads when PV power is insufficient or mains are unavailable.
  • Loads: Various household and office appliances (refrigerators, lights, TVs, AC units, etc.).
  • Inverter: The central energy conversion device.
Split-phase mode wiring diagram

Figure 3.1: Split-phase mode wiring diagram. Shows solar panels, batteries, inverter, AC load, and utility grid connections. Labels include CAN, L wire, PE wire, N wire, DC breaker, AC breaker.

3.2 Unpacking and Inspection

Before installation, inspect the unit for any damage. Ensure all items are present:

  • Inverter unit (x1)
  • User manual (x1)
  • Ring terminals (x2)
  • Parallel cable (x1)
  • Spare screws (x4)
  • Warranty card (x1)
  • Plastic expansion screws (x1)
  • Stainless steel expansion screws (x2)

3.3 Selecting the Mounting Location

This inverter is for indoor use only (IP20 protection). Consider the following:

  • Mount on a solid wall.
  • Install at eye level for easy viewing.
  • Ensure sufficient heat-dissipation space around the inverter.
  • Ambient temperature: -10°C to 55°C (14°F to 131°F).

DANGER:

  • Do not install near flammable substances or in explosive areas.
  • Do not install the inverter and lead-acid batteries in an enclosed space.

WARNING:

  • Do not install in direct sunlight or humid environments.

3.4 Inverter Overview and Ports

Inverter front and bottom view with labeled ports

Figure 3.2: Inverter front and bottom view with labeled ports.

Table 3.1: Inverter Port Identification
No.DescriptionNo.Description
1Capacitive touch screen8Dry contact
2LED indicator9Battery port (positive)
3Terminal protection cover10Battery port (negative)
4ON/OFF rocker switch11Photovoltaic port
5Parallel communication port12AC output (L1+N+L2)
6RS485-1 port13AC input (L1+N+L2+PE)
7CAN/RS485-2 port

3.5 Wiring Instructions

DANGER: Before connecting any wiring, ensure the corresponding circuit breaker is disconnected to avoid electric shock. Do not operate under live conditions.

3.5.1 Cable and Circuit Breaker Selection

Table 3.2: Cable and Circuit Breaker Specifications
Input/OutputModeMax CurrentWire DiameterBreaker Spec
PhotovoltaicN/A27A4mm²/8 AWG2P-32A
AC Input/OutputSplit-phase45A (L1/L2/N)10mm²/4 AWG3P-50A
AC Input/OutputSingle-phase45A (L1/N)10mm²/4 AWG2P-50A
BatteryN/A120A50mm²/2/0 AWG2P-125A

3.5.2 AC Input and Output Wiring

Connect live, neutral, and ground wires as shown in the diagram. Ensure cables meet specifications; undersized or poor-quality cables pose safety hazards.

AC Output Wiring Diagram for Split-phase and Single-phase

Figure 3.3: AC Output Wiring Diagram for Split-phase and Single-phase modes. Shows L1, L2, N connections and voltage waveforms.

3.5.3 Battery Wiring

Connect positive and negative battery cables. Ensure correct polarity to prevent inverter damage. Verify cable specifications.

3.5.4 Photovoltaic Wiring

Connect positive and negative PV input wires. Ensure the open-circuit voltage of PV modules in series does not exceed 500VDC.

3.5.5 Dry Contact Wiring

Insert communication cable (0.2~1.5mm²) into the dry contact port using a small screwdriver.

3.6 Final Installation and Start-up

  1. After wiring is complete and verified, restore the terminal protection cover.
  2. Start-up Sequence:
    1. Close the battery circuit breaker.
    2. Press the ON/OFF rocker switch at the bottom of the inverter. Screen and indicators will illuminate.
    3. Close the circuit breakers for photovoltaic, AC input, and AC output in turn.
    4. Start loads one by one in ascending order of power.

4. Operating Instructions

4.1 LED Indications

Table 4.1: LED Indicator Status
Indicator LightColorsDescription
AC/INVGreenSteady on: Mains bypass output
Flashing: Inverter output
CHARGEGreenSteady on: Charging completed
Flashing: Charging is underway
FAULTRedFlashing: A fault has occurred

4.2 LCD Display and Operation

The inverter features a capacitive intelligent touch screen for menu-based operation and parameter setting. The home page displays real-time system status, including PV data, grid data, battery data, and load data. Navigation is intuitive, allowing users to access detailed information and settings.

4.2.1 Data Interface

The data interface provides access to real-time data, statistical data, historical data, event records, and control functions.

4.2.2 Control Functions

Users can access various control functions, including immediate equalization charge, time setting, clearing events/status/historical records, restoring factory settings, and resetting the inverter.

4.2.3 Setting Interface

The setting interface allows configuration of communication settings, time-slot charging/discharging, battery parameters, and system parameters.

  • Communication Settings: Device address, Bluetooth/Wi-Fi enable, LCD backlight time.
  • Time-Slot Charging/Discharging: Configure start/end times for charging and discharging periods.
  • Battery Settings: Battery type (USE, SLD, FLD, GEL, LiFePO4, NCM), system voltage, nominal capacity, temperature compensation, SOC limits, inverter switching voltages, charge current limits, and BMS protocol.
  • System Settings: AC output mode (Mains priority, Inverter priority, PV priority), AC output voltage, frequency, parallel mode, parallel phase, battery charging mode, charge current limit, and various system functions (NPE ground wire shorting, energy saving, auto restart, buzzer, mode shift alert, overload bypass).

4.3 Charging and Output Modes

Four Charging Modes and Two Load Output Working Modes

Figure 4.1: Four Charging Modes (Solar First, Utility First, Solar and Utility, Only Solar) and Two Load Output Working Modes (Solar First, Utility First).

5. Maintenance

To ensure optimal long-term performance, perform the following checks twice a year:

  • Ensure clear airflow around the inverter and clean the radiator.
  • Inspect all exposed wiring for damage (sun, friction, rot, pests); repair/replace as needed.
  • Verify display consistency with actual operation; address any faults.
  • Check terminals for corrosion, damage, overheating; tighten screws.
  • Clean insect netting regularly.
  • Replace failed lightning arresters promptly.

DANGER: Before any inspection or operation, disconnect all power sources and ensure internal capacitors are fully discharged to prevent electric shock.

5.1 Warranty Exclusions

The standard warranty does not cover issues caused by:

  • Product beyond warranty period.
  • Failure to follow instructions, improper installation/maintenance, or unsuitable environment.
  • Unauthorized disassembly, repair, or modification.
  • Products obtained through unauthorized channels.
  • Unforeseeable circumstances, human factors, or force majeure (storms, floods, lightning, overvoltage, infestation, fire).
  • Unauthorized design changes or part replacements.
  • Intentional damage, defacement, theft.
  • Normal wear and tear.
  • Failure to comply with applicable safety standards.
  • Other non-product quality issues.
  • Damage during transportation (scratches).
  • Rust or corrosion due to harsh environmental conditions.

6. Troubleshooting

This section provides common trouble codes, their meanings, reasons, and solutions.

Table 6.1: Common Trouble Codes and Solutions
CodeMeaningReasonSolution
N/AScreen not displayingNo power input, switch offCheck battery/PV breakers, ensure switch is ON
01Battery voltage lowBelow warning voltageCharge battery until voltage is above set value
03Battery no connectNot connected, or BMS in protectionCheck connections, battery breaker, BMS communication
04Battery undervoltage stops dischargingBelow over discharge voltageManual reset (power off/on) or automatic reset (charge battery)
06Battery charge overvoltageBattery is overvoltageManually power off/on, discharge battery below limit
13Bypass overload protectionBypass output overloadedReduce load, restart device
14Inverter overload protectionInverter output overloadedReduce load, restart device
21Fan faultHardware detected fan failureShut down, start fan manually, check for obstructions. If persists, contact service.
26Inverter AC output is fed back to bypass AC outputAC output relay is stuckContact after-sales service for repair
27Mains input phase errorPhase mismatch between AC input and outputEnsure AC input phase matches AC output phase configuration

For a complete list of fault codes and detailed troubleshooting steps, please refer to the full user manual PDF.

7. Specifications

Detailed specifications table for ECGSOLAX 8KW Hybrid Solar Inverter

Figure 7.1: Detailed specifications for ECGSOLAX 8KW Hybrid Solar Inverter (Model ECG-LVM8K-SP).

Table 7.1: ECGSOLAX 8KW Hybrid Solar Inverter Specifications (ECG-LVM8K-SP)
CategoryParameterValue
Inverter OutputRated Output Power8000 W
Max. Peak Power16000 W
Rated Output Voltage100/110/120/127V; 200/220/240V; 208V; 220V
Rated Frequency50/60Hz
Output WaveformPure sine wave
BatteryBattery TypeLithium-ion battery/lead-acid battery
Rated Battery Voltage48Vdc
Battery Voltage Range40~60Vdc
Max. PV Charging Current120A
Max. Hybrid Charging Current120A
PV InputMax. Input Power10500 W
Max. Input Current27A
Max. Open Circuit Voltage500Vdc
MPPT Operating Voltage Range125~425Vdc
Mains/Generator InputInput Voltage Range90~275Vac
Input Frequency Range60/55~65Hz
Bypass Overload Current45A
EfficiencyMPPT Tracking Efficiency99%
Max. Efficiency of Battery Inverter93%
UniversalDimensions (H*W*D)472*412*130mm
Net Weight16kg
Level of ProtectionIP20
Ambient Temperature-10 ~ 55°C
Cooling MethodIntelligent Air Cooling
CommunicationBuilt-in InterfaceWIFI/Bluetooth/RS485/CAN/4G (Optional)
Communication MethodWIFI/Bluetooth/RS485/CAN/4G (Optional)

8. Warranty and Support

8.1 Warranty Information

The ECGSOLAX 8KW Hybrid Solar Inverter comes with a 2-year warranty from the date of purchase. Please retain your proof of purchase for warranty claims.

8.2 Warranty Exclusions

The warranty does not cover damages or malfunctions resulting from:

  • Improper installation, operation, or maintenance not in accordance with this manual.
  • Unauthorized modifications, repairs, or disassembly.
  • External factors such as natural disasters (lightning, floods), power surges, or extreme environmental conditions.
  • Normal wear and tear.
  • Damage during transportation.
  • Use of non-approved accessories or parts.

For detailed warranty terms and conditions, please refer to the official ECGSOLAX warranty document or contact customer support.

8.3 Customer Support

For technical assistance, troubleshooting beyond this manual, or warranty claims, please contact your local dealer or ECGSOLAX customer service. Provide your product model (ECG-LVM8K-SP) and serial number for faster service.

9. User Tips

Based on common user inquiries and feedback:

  • Battery Compatibility: Ensure your battery system (lithium-ion or lead-acid) is correctly selected in the inverter settings for optimal performance and safety.
  • Parallel Operation: If operating multiple inverters in parallel, ensure all communication cables are securely connected and wiring lengths/gauges are consistent to prevent operational issues. Refer to the full PDF manual for detailed parallel wiring diagrams.
  • Firmware Updates: Keep an eye on official announcements for firmware updates, which can improve performance and add features. Follow the provided instructions carefully for any update process.
  • Monitoring: Utilize the built-in Bluetooth and Wi-Fi connectivity to monitor your system's performance via the dedicated app. This allows for real-time data viewing and historical record analysis.

For more detailed information, please refer to the official ECGSOLAX 8KW Hybrid Solar Inverter User Manual (PDF) available from the manufacturer.

Ask a question about this manual