1. Introduction
1.1. About This Manual
This manual introduces the assembly, installation, operation, and troubleshooting of the PowMr 2500W Hybrid Solar Inverter. Please read this manual carefully before installation and operation to ensure proper use and safety.
1.2. Product Overview
The PowMr 2500W Hybrid Solar Inverter (POW-HVM2.5KW-12V) is an all-in-one unit integrating an MPPT solar charge controller, a high-frequency pure sine wave inverter, and a UPS (Uninterruptible Power Supply) function module. Its high-frequency transformer design allows for compact size and efficient power conversion. It supports dual inputs from photovoltaic panels and AC/generator power, capable of charging batteries while simultaneously supplying AC loads. It is compatible with both lead-acid and lithium batteries (with BMS communication). Optional accessory modules enable remote monitoring. This inverter is ideal for off-grid power supply in areas without grid access, as a home backup power source, and for self-consumption photovoltaic systems.
1.3. Features
- Pure sine wave output inverter.
- Selectable input voltage range for utility grid based on load requirements (household appliances/personal computers).
- Adjustable charging current via LCD based on battery requirements.
- Simultaneous power supply to loads from solar energy and utility grid.
- AC input compatible with mains and generator.
- Automatic restart function upon restoration of mains power.
- Overload, over-temperature, and short circuit protection.
- Intelligent charging design for optimal battery utilization.
- RS485 port for BMS communication.
- Cold start function.
- Intelligent fan speed adjustment based on temperature, load, and charging current.
- Built-in MPPT with an operating voltage range of 55V~430V and open circuit voltage of 450Voc.
- WIFI remote monitoring (optional).
1.4. Basic System Architecture
The inverter/charger forms the core of a hybrid power system. A complete running system typically includes:
- Solar Power (PV array)
- Generator or Mains Electricity (Utility Grid)
- External Battery Packs (12V Lithium or Lead-Acid Battery)
- Home Appliances (Loads)
The inverter can power various appliances in home or office environments, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners.
2. Safety Regulations
WARNING: This article contains important safety and operation instructions. Please read and save this manual for future reference.
- Choose the corresponding setting for lead-acid or lithium batteries. Incorrect settings may lead to system malfunction.
- Before using the unit, read all instructions and cautionary notes on the unit and understand all battery models and relevant chapters in this manual.
- Never short-circuit AC output and DC input. Never connect the mains when the DC input is short-circuited.
- Never charge a non-rechargeable battery.
- Do not disassemble the unit. For maintenance or repair, send it to a professional technical service center. Incorrect reassembly may lead to electric shock or fire.
- To reduce the risk of electric shock, disconnect all wiring before attempting any maintenance or cleaning. Turning off the device alone will not eliminate this risk.
- Exercise extreme caution when using metal tools on or around the battery. Sparks from falling tools can cause short circuits, potentially leading to explosions.
- For optimal operation, select appropriate cable sizes for battery connection as per instructions.
- When disconnecting AC or DC terminals, strictly follow the installation procedure detailed in the "Installation" section.
- This off-grid solar inverter must be connected to a permanent grounding wiring system. Comply with local requirements and regulations.
- Provide a fuse that meets specific battery power supply requirements for overcurrent protection.
- WARNING: Only professional service personnel can repair this equipment. If errors persist after troubleshooting, return the inverter to the local dealer or service center.
3. Installation
3.1. Unpacking and Inspection
Unpack the inverter and inspect for any damaged objects. The package should contain:
- Inverter Unit x 1
- User Manual x 1
3.2. Preparation Before Installation
Before connecting any wiring, remove the bottom port cover by unscrewing the two screws as shown in the wiring guide video.
3.3. Installation Location
Consider the following points when selecting an installation location:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install the inverter at eye level for easy reading of the LCD display.
- Allow approximately 20 cm clearance on both sides and above the equipment, and 50 cm below, for proper air circulation and heat dissipation.
- The ambient temperature should be between 0°C and 55°C for optimal operation.
- The recommended installation position is vertically adhered to the wall.
- Ensure sufficient space around the machine for adequate heat dissipation and wire removal.
CAUTION: Suitable for installation on concrete or other non-combustible surfaces only.
Tighten the screws to fix the installation. M4 or M5 screws are recommended for machine fixing.
3.4. Wiring Connections
Ensure all wiring is performed by qualified personnel and adheres to safety regulations.
3.4.1. Grounding
Ground the inverter via the bottom grounding terminal. This off-grid solar inverter must be connected to a permanent grounding wiring system. Comply with local requirements and regulations.
3.4.2. Battery Connection
WARNING: Install an independent DC overcurrent protector or disconnect device between the battery and the inverter. All wiring must be performed by qualified personnel. Use appropriate cable for battery connection to reduce risk of injury.
Recommended battery cable specifications:
| Model | Wire Specification | Torque Value |
|---|---|---|
| 2.5KVA-12V | 1 * 4 AWG (22mm²) | 2-3 Nm |
Note: The recommended charging current for lead-acid batteries is 0.2C (C is battery capacity).
Steps for battery connection:
- Connect the battery according to the recommended cable specifications.
- Connect all battery packs as needed.
- Insert the ring terminal of the battery cable into the inverter's battery connector. Ensure bolts are tightened with a torque of 2-3 Nm. Verify correct polarity and tighten the ring terminal with the battery terminal.
WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION: Do not place anything between the flat part of the inverter terminal and the ring terminal, as this may cause short circuit or overheating.
CAUTION: Do not apply antioxidant to the terminal before it is tightly connected.
CAUTION: Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).
Connect battery packs as shown in the diagram:
3.4.3. Lithium Battery Communication
If using a lithium battery, only those matched with BMS communication protocol are allowed. Connect the RJ45 communication cable between the inverter and battery. Confirm the lithium battery BMS port's PIN corresponds with the inverter BMS communication port.
Inverter BMS port PIN definition:
| Pin Number | Port Definitions |
|---|---|
| 1 | RS485B |
| 2 | RS485A |
| 3 | NG |
| 4 | NG |
| 5 | NG |
| 6 | NG |
| 7 | RS485A |
| 8 | RS485B |
NOTE: If you choose a lithium battery, connect the battery and inverter with a BMS communication cable and select the battery type as "LIB-485" mode in Program 05.
3.4.4. AC Input/Output Connection
CAUTION: Install a separate AC breaker between the inverter and AC input power source for secure disconnection and overcurrent protection. Do NOT mis-connect input and output connectors. All wiring must be performed by qualified personnel. Use appropriate cable sizes.
Suitable cable specifications for AC wires:
| Model | Wire Gauge | Torque Value |
|---|---|---|
| 2.5KVA-12V | 1 * 12 AWG | 1.2-1.6 Nm |
Steps for AC input/output connection:
- Before making AC input/output connections, open the DC protector or disconnector first.
- Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. (L→ LINE (brown or black), N→ Neutral (blue))
- Insert the AC output conductor according to the polarity identification at the terminal and tighten the screw.
- Ensure the wires are firmly connected.
WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
CAUTION: Ensure all AC cables are connected correctly according to the corresponding polarity. Appliances like air conditioners require 2-3 minutes to restart. If a power shortage occurs, it may damage connected appliances. Check the air conditioner manufacturer for time-delay functions. Otherwise, the inverter may trigger an overload fault to protect the appliance, but internal damage may still occur.
3.4.5. PV Connection
CAUTION: Before connecting the PV module, install a separate DC circuit breaker between the inverter and PV module. All wiring must be performed by qualified personnel. Use appropriate cable sizes.
Suitable cable specifications for PV module connection:
| Model | Wire Gauge | Torque Value |
|---|---|---|
| 2.5KVA-12V | 1 * 14 AWG | 1.2-1.6 Nm |
PV Module Selection considerations:
- Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter (500Vdc).
- Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
Recommended module configurations (example for 250Wp PV module):
| Solar Panel Parameters | Solar Input Range (Min in serial: 6 pcs, max in serial: 11 pcs) | Q'ty of Panels | Total Input |
|---|---|---|---|
| 250Wp, Vmp: 30.1Vdc, Imp: 8.3A, Voc: 37.7Vdc, Isc: 8.4A, Cells: 60 | 3 pcs in serial | 3 | 750W |
| 4 pcs in serial | 4 | 1000W | |
| 5 pcs in serial | 5 | 1250W | |
| 6 pcs in serial | 6 | 1500W | |
| 8 pcs in serial | 8 | 2000W | |
| 11 pcs in serial | 11 | 2750W |
Steps for PV module connection:
- Remove 10mm of insulation sleeve for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
- Make sure the wires are securely connected.
3.5. Final Assembly
After connecting all the wires, replace the bottom port cover and secure it with the screws.
4. Operation
4.1. Power On/Off
After correctly installing the machine and connecting the battery, simply press the On/Off switch to turn on the machine.
4.2. Operation and Display
The operation and display panel is located on the front of the inverter. It includes four function keys and an LCD screen for indicating operation status and input/output power information.
4.2.1. Function Keys
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
4.2.2. LED Indicators
| Indicator | LED Status | Messages |
|---|---|---|
| AC/INV | Green, Solid On | Output is powered by utility in Line mode. |
| Green, Flashing | Output is powered by battery or PV in battery mode. | |
| CHG | Green, Solid On | Battery is fully charged. |
| Green, Flashing | Battery is charging. | |
| FAULT | Red, Solid On | Fault occurs in the inverter. |
| Red, Flashing | Warning condition occurs in the inverter. |
4.2.3. LCD Display Icons
The LCD display provides various information through icons. Here are some key icons and their descriptions:
| Icon | Function Description |
|---|---|
| AC | Indicates the AC input. |
| PV | Indicates the PV input. |
| INPUTBATT (e.g., 888 kW/VA/Hz/°C) | Indicates input voltage, input frequency, PV voltage, battery voltage, and charger current. |
| 88 | Indicates the setting programs. |
| 88 (flashing) | Flashing with warning code. |
| 88 (lit) | Lighting with fault code. |
| OUTPUTBATTLOAD (e.g., 8.88 kW/VA/Hz) | Indicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current. |
| Battery Information (bars) | Indicates battery level by 0-24%, 25-49%, 50-74%, and 75-100% in battery mode and charging status in line mode. |
| OVER LOAD | Indicates overload. |
4.2.4. Operating Mode Description
The inverter operates in various modes, each with specific power flow and charging behavior:
| Operation Mode | Description |
|---|---|
| Standby Mode / Power Saving Mode | No output is supplied by the unit, but it can still charge batteries. In power saving mode, output is off if load is very low. |
| Line Mode | The unit provides output power from the mains and can charge the battery. Solar and mains can supply power to loads simultaneously. |
| Battery Mode | The unit provides output power from battery and PV power. Battery and solar can supply power to loads simultaneously. |
5. LCD Settings
To enter setting mode, press and hold the "ENTER" button for 3 seconds. Use "UP" or "DOWN" to select programs, then "ENTER" to confirm or "ESC" to exit.
Key settings include:
- Program 00: Exit Setting Mode (Escape, One-button restore setting options)
- Program 01: Output Source Priority (SUB priority, SBU priority, MKS priority)
- Program 02: Maximum Charging Current (10A, 20A, 30A, 40A, 50A, 60A, 70A, 80A, 90A, 100A)
- Program 03: AC Input Voltage Range (Appliances (90-280VAC), UPS (170-280VAC))
- Program 04: Power Saving Mode Enable/Disable
- Program 05: Battery Type (AGM, Flooded, User-Defined, LIB-485)
- Program 06: Auto Restart When Overload Occurs
- Program 07: Auto Restart When Over Temperature Occurs
- Program 09: Output Frequency (50Hz, 60Hz)
- Program 10: Output Voltage (220V, 230V, 240V)
- Program 11: Maximum Utility Charging Current (10A to 100A)
- Program 12: Setting Voltage Point Back to Utility Source (for SBU priority, various voltage options)
- Program 13: Setting Voltage Point Back to Battery Mode (for SBU priority, various voltage options)
- Program 16: Charger Source Priority (Solar first, Solar and Utility, Only Solar)
- Program 18: Alarm Control (Alarm on/off)
- Program 19: Auto Return to Default Display Screen (Enable/Disable)
- Program 20: Backlight Control (On/Off)
- Program 22: Beeps While Primary Source Is Interrupted (On/Off)
- Program 23: Overload Bypass (Enable/Disable)
- Program 25: Record Fault Code (Enable/Disable)
- Program 26: Bulk Charging Voltage (C.V voltage)
- Program 27: Floating Charging Voltage
- Program 29: Low DC Cut-off Voltage
- Program 30: Battery Equalization (Enable/Disable)
- Program 31: Battery Equalization Voltage
- Program 33: Battery Equalized Time
- Program 34: Battery Equalized Timeout
- Program 35: Equalization Interval
- Program 36: Equalization Activated Immediately
- Program 37: GRID-tie Operation (Off grid, Hybrid)
- Program 38: GRID-tie Current
- Program 39: LED Pattern Light (On/Off)
- Program 43: Lithium Battery Protocol (PYLON, PACE)
6. Battery Management
6.1. Battery Equalization
The equalization function helps reverse the buildup of negative chemical effects like stratification and removes sulfate crystals from battery plates, extending battery life. It is recommended to equalize batteries periodically.
To apply equalization:
- Enable battery equalization in LCD setting program 30.
- Apply by either: setting the equalization interval in program 35, or activating equalization immediately in program 36.
When the setting equalization interval is reached, or equalization is active immediately, the controller will enter the Equalize stage. The controller will charge the battery until it reaches the equalization voltage, then maintain it until the set equalized time is reached. If the battery voltage doesn't rise to the equalization voltage within the set time, the charge controller will extend the time until it does. If it still doesn't reach the voltage after the extended time, the controller will stop equalization and return to the float stage.
6.2. Mains and Lithium Battery Activation Function
- After 90 seconds of mains power connection to the inverter, the machine connects to the mains and starts operation.
- If the inverter is in lithium battery mode (Program 05 is LIB or LIB-485) and the mains is connected but the battery is not, the mains activation function is automatically enabled.
7. Clearance and Maintenance for Anti-Dust Kit
7.1. Overview
Every inverter comes with an anti-dust kit installed from the factory. The inverter automatically detects this kit and activates an internal thermal sensor to adjust internal temperature. This kit prevents dust from entering the inverter, increasing product reliability in harsh environments.
7.2. Clearance and Maintenance Steps
- Remove the screws securing the bottom port cover.
- Carefully remove the dustproof case and take out the air filter foam.
- Clean the air filter foam and dustproof case.
- After cleaning, re-assemble the dust-kit back into the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
8. Troubleshooting
8.1. Fault Codes
The inverter displays fault codes to indicate specific issues:
| Fault Code | Fault Event |
|---|---|
| 01 | Fan is locked when the inverter is turned off. |
| 02 | Over temperature |
| 03 | Battery voltage is too high |
| 04 | Battery voltage is too low |
| 05 | Output short circuit or over temperature. |
| 06 | Output voltage is too high |
| 07 | Exceeding overload time |
| 08 | BUS voltage is too high |
| 09 | BUS soft start failed. |
| 13 | PV voltage is too high |
| 51 | Over current and surge |
| 52 | BUS voltage is too low |
| 53 | Inverter soft start failed. |
| 55 | Over DC voltage in AC output |
| 56 | Battery is disconnected |
| 57 | Current sensor failed. |
| 58 | Output voltage is too low |
| 61 | Communication Failure |
8.2. Warning Codes
The inverter displays warning codes to indicate potential issues:
| Warning Code | Warning Event | Automatic Alarm |
|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second |
| 03 | Battery overcharge | Beep once every second |
| 04 | Battery low voltage | Beep once every second |
| 07 | Overload | Beep once every 0.5 second |
| 10 | Output power is derating | Beep twice every 3 seconds |
| 15 | PV energy is weak | No Beep |
| EQ | Battery equalization | No Beep |
| bP | Battery is not connected. | No Beep |
8.3. Common Problems and Solutions
| Problem | Explanation / Possible Cause | What to Do |
|---|---|---|
| Unit shuts down automatically during startup process. | Battery voltage is too low | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | 1. The battery voltage is far too low. 2. Battery polarity is connected reversed. |
1. Check if batteries and the wiring are connected well. 2. Re-charge battery. 3. Replace battery. |
| Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. |
| Buzzer beeps continuously and the status indicator icon is always on. | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. |
| Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Internal temperature of inverter component are over heated. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. Return to repair center. | |
| Battery is over-charged. | Check if spec and quantity of batteries are meet requirements. | |
| Fan fault | Replace the fan. | |
| Output abnormal | 1. Reduce the connected load. 2. Return to repair center. |
|
| Internal components failed. | Return to repair center. | |
| Over current or surge. Bus voltage is too low. Output voltage is unbalanced. |
Restart the unit, if the error happens again, please return to repair center. |
9. Specifications
9.1. Line Mode Specification
| Parameter | Value (2.5KVA-12V) |
|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) |
| Nominal Input Voltage | 230Vac |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) |
| High Loss Voltage | 280Vac±7V |
| High Loss Return Voltage | 270Vac±7V |
| Max AC Input Voltage | 300Vac |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) |
| Low Loss Frequency | 40±1Hz |
| Low Loss Return Frequency | 42±1Hz |
| High Loss Frequency | 65±1Hz |
| High Loss Return Frequency | 63±1Hz |
| Output Short Circuit Protection | Battery mode: Electronic Circuits |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) |
Output power derating: When AC input voltage drops to 95V or 170V depending on models, the output power will be derated.
9.2. Inverter Mode Specification
| Parameter | Value (2.5KVA-12V) |
|---|---|
| Rated Output Power | 1600VA/1600W |
| PV + Battery Rated Output Power | 2500VA/2500W |
| Output Voltage Waveform | Pure Sine Wave |
| Output Voltage Regulation | 230Vac±5% |
| Output Frequency | 60Hz or 50Hz |
| Peak Efficiency | 92% |
| Overload Protection | 3s@≥150% load; 20s@110%~150% load |
| Surge Capacity | 2* rated power for 5 seconds |
| Nominal DC Input Voltage | 12Vdc |
| Cold Start Voltage | 11.3Vdc |
| Low DC Warning Voltage (<50% Load) | 11.0Vdc |
| Low DC Warning Voltage (≥50% Load) | 10.5Vdc |
| Low DC Warning Return Voltage (<50% Load) | 11.5Vdc |
| Low DC Warning Return Voltage (≥50% Load) | 11.0Vdc |
| Low DC Cut-off Voltage (<50% Load) | 10.2Vdc |
| Low DC Cut-off Voltage (≥50% Load) | 10Vdc |
| High DC Recovery Voltage | 16Vdc |
| High DC Cut-off Voltage | 15Vdc |
| No Load Power Consumption | <25W |
| Saving Mode Power Consumption | <20W |
9.3. Charging Mode Specification
| Parameter | Value (2.5KVA-12V) |
|---|---|
| Utility Charging Mode Current (UPS @Nominal Input Voltage) | 100A |
| Bulk Charging Voltage (Flooded Battery) | 14.6V |
| Bulk Charging Voltage (AGM / Gel Battery) | 14.1V |
| Floating Charging Voltage | 13.5Vdc |
| Charging Algorithm | 3-Step |
| Solar Charging Mode Rated Power | 3000W |
| Solar Charging Mode Rated Solar Voltage | 240V |
| Solar Charging Mode PV Array MPPT Voltage Range | 55V~450V |
| Solar Charging Mode Max. PV Array Open Circuit Voltage | 500V |
| Solar Charging Mode IMax.PV | 13A |
| Solar Charging Mode Max Charging Current | 100A |
9.4. General Specifications
| Parameter | Value |
|---|---|
| Dimensions (D*W*H) | 345 * 255 * 100 mm |
| Net Weight | 4.6 kg |
| Operating Temperature Range | 0°C to 55°C |
| Storage Temperature | -15°C to 60°C |
| Operating Altitude | ≤ 6000 m |
| Battery Overvoltage Protection | Yes |
| Overload Protection | Yes |
| Output Short-Circuit Protection | Yes |
| Over-Temperature Protection | Yes |
10. User Tips
- Always ensure proper ventilation around the inverter to prevent overheating, especially during high load operation.
- Regularly check all wiring connections for tightness and signs of wear to maintain optimal performance and safety.
- If using lithium batteries, ensure the BMS communication is correctly configured to prevent potential issues and maximize battery life.
- Monitor the LCD display for any fault or warning codes and refer to the troubleshooting section promptly to address issues.
- Consider the environmental conditions (temperature, dust) and perform routine maintenance on the anti-dust kit to prolong the inverter's lifespan.