1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the Daxtromn GGH-6.5KVA-PRO Hybrid Solar Inverter. This multi-function inverter/charger combines the functions of an inverter, MPPT solar charger, and battery charger to provide uninterruptible power support. It features a comprehensive LCD display for user-configurable settings such as battery charging current, AC/solar charger priority, and acceptable input voltage ranges.
Please read this manual carefully before installation and operation, and keep it for future reference. This manual also provides safety and installation guidelines, as well as information on tools and wiring.
Key Features:
- Pure sine wave inverter
- Inverter running without battery
- Built-in MPPT solar controller (Max 80A, Max 500VDC PV input)
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible with mains voltage or generator power
- Auto restart while AC is recovering
- Overload/Over temperature/Short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
- With BMS (Battery Management System) support for communication and automatic parameter adjustment
- Supports RS232 communication
- Lithium battery activation function
- Dry contact for generator start
- Mainboard with waterproof coating for moisture corrosion resistance
- MOSFET pin protection against insects and short circuits
- Large internal wire diameter to reduce heat generation
- Built-in dustproof kit for harsh environments
- Intelligent fan for power saving and noise reduction at low/no load
- Mix power support (grid and solar energy)
- Can work without batteries
- Supports 50Hz or 60Hz (programmable)
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with a battery.
- NEVER charge a frozen battery.
- For optimum operation, follow required specifications to select appropriate cable sizes.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool, causing sparks or short circuits, which could lead to an explosion.
- Strictly follow the installation procedure when disconnecting AC or DC terminals. Refer to the INSTALLATION section for details.
- A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
- NEVER cause AC output and DC input short-circuited. Do NOT connect to the mains when DC input short circuits.
- Warning: Only qualified service persons are able to service this device. If errors persist after following the troubleshooting table, send this inverter/charger back to your local dealer or service center for maintenance.
3. Product Overview
The Daxtromn GGH-6.5KVA-PRO Hybrid Solar Inverter is designed for various applications, including powering home and office appliances. Below is an overview of its components and basic system architecture.
Component Identification:
- AC Indicator
- Invert Indicator
- Charging Indicator
- Fault Indicator
- LCD Display
- Up Button
- Down Button
- Enter Button
- Power ON/OFF Switch
- AC Input
- AC Output 1
- AC Output 2
- PV Input
- Battery Input
- BMS Port
- COM Port
- PE (Protective Earth)
The basic system architecture involves connecting solar power (PV modules), a generator or utility grid, and external battery packs to the inverter, which then supplies power to home appliances.
4. Installation
4.1 Unpacking and Inspection
Before installation, inspect the unit for any damage. The package should contain:
- The inverter unit (x1)
- User manual (x1)
4.2 Preparation
Before connecting any wirings, remove the bottom cover by unscrewing the two screws.
4.3 Mounting the Unit
Consider the following points when selecting an installation location:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install the inverter at eye level for easy LCD display readability.
- The ambient temperature should be between 0°C and 55°C for optimal operation.
- The recommended installation position is vertically on the wall.
- Ensure sufficient clearance for heat dissipation and wire removal.
CAUTION: Suitable for mounting on concrete or other non-combustible surface only.
Install the unit by screwing three M4 or M5 screws.
4.4 Battery Connection
CAUTION: For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter.
WARNING: Use appropriate cable for battery connection to reduce risk of injury.
Follow these steps for battery connection:
- Remove 18 mm of insulation sleeve for positive and negative cables based on recommended stripping length.
- Connect all battery packs as required.
- Insert battery cable flatly into the inverter's battery connector and tighten bolts with a torque of 2-3 Nm. Ensure correct polarity.
Recommended Battery Cable Specifications:
| Model | Maximum Amperage | Battery Capacity | Wire Size | Cable mm² | L1 (mm) | L2 (mm) | Torque Value |
|---|---|---|---|---|---|---|---|
| 3.5KVA | 137A | 100AH | 2AWG | 38 | 3 | 18 | 2-3 Nm |
| 5.5KVA | 137A | 200AH | 2AWG | 38 | 3 | 18 | 2-3 Nm |
4.5 AC Input/Output Connection
CAUTION: Install a separate AC breaker (recommended 50A) between the inverter and AC input power source.
CAUTION: Do NOT mis-connect input and output connectors. There are two terminal blocks with "IN" and "OUT" markings.
WARNING: All wiring must be performed by qualified personnel.
WARNING: Ensure AC power source is disconnected before hardwiring.
Follow these steps for AC input/output connection:
- Before making AC input/output connections, open the DC protector or disconnector.
- Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the screws. Connect PE protective conductor (yellow-green) first, then L (brown or black), and N (blue).
- Insert AC output wires according to polarities and tighten screws. Connect PE protective conductor first, then L, and N.
- Make sure all wires are securely connected.
Suggested Cable Requirement for AC Wires:
| Model | Gauge | Torque Value |
|---|---|---|
| 3.5KVA | 10AWG | 1.4-1.6Nm |
| 5.5KVA | 8AWG | 1.4-1.6Nm |
4.6 PV Connection
CAUTION: Install a separate DC circuit breaker between the inverter and PV modules.
WARNING: All wiring must be performed by qualified personnel.
WARNING: Use appropriate cable for PV module connection to reduce risk of injury.
Follow these steps for PV module connection:
- Remove 10mm of insulation sleeve for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) to positive pole (+) and negative pole (-) to negative pole (-).
- Make sure all wires are securely connected.
PV Module Selection Parameters:
- Open circuit Voltage (Voc) of PV modules should not exceed the max. PV array open circuit voltage of the inverter (500VDC).
- Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
Solar Charging Mode Specifications:
| Inverter Model | Max. PV Array Open Circuit Voltage | PV Array MPPT Voltage Range |
|---|---|---|
| 3.5KVA/5.5KVA | 500VDC | 120VDC-450VDC |
Suggested Cable Requirement for PV Wires:
| Model | Typical Amperage | Cable Size | Torque |
|---|---|---|---|
| 3.5KVA | 15A | 12 AWG | 1.4-1.6 Nm |
| 5.5KVA | 18A | 12 AWG | 1.4-1.6 Nm |
Note on PV Input Voltage:
This is a wide voltage Hybrid Solar inverter. If the inverter is used without an external battery, the voltage that starts to connect to the solar panel must be above 150V for the inverter to work normally. If used with an external battery, 120V PV input is sufficient for operation.
4.7 Final Assembly
After connecting all wirings, replace the bottom cover and secure it with the two screws.
4.8 Dry Contact Signal
A dry contact (3A/250VAC) is available on the rear panel. This can be used to deliver a signal to an external device when the battery voltage reaches a warning level.
| Unit Status | Condition | Dry Contact Port (NC & C) | Dry Contact Port (NO & C) |
|---|---|---|---|
| Power Off | Unit is off and no output is powered. | Close | Open |
| Output is powered from Utility. | Close | Open | |
| Power On | Battery voltage < Low DC warning voltage | Open | Close |
| Battery voltage > Setting value in Program 13 or battery charging reaches floating stage | Close | Open |
5. Operation
5.1 Power ON/OFF
Once the unit is properly installed and batteries are connected, press the On/Off switch (located on the button of the case) to turn on the unit.
5.2 Operation and Display Panel
The front panel of the inverter features an operation and display panel, including three indicators, four function keys, and an LCD display for operating status and input/output power information.
LED Indicators:
| LED Indicator | Color | State | Message |
|---|---|---|---|
| AC/INV | Green | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by battery or PV in battery mode. | ||
| CHG | Green | Solid On | Battery is fully charged. |
| Flashing | Battery is charging. | ||
| FAULT | Red | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
5.3 LCD Display Icons
The LCD displays various icons to indicate input source, output information, battery status, load level, and operating mode. Refer to the manual for a detailed explanation of each icon.
5.4 LCD Setting
To enter setting mode, press and hold the ENTER button for 3 seconds. Use the UP or DOWN buttons to select programs, and ENTER to confirm or ESC to exit. Key settings include:
- Program 00: Exit setting mode.
- Program 01: Output source priority (Utility first, Solar first, SBU priority).
- Program 02: Maximum charging current (10A to 60A).
- Program 03: AC input voltage range (Appliances: 90-280VAC, UPS: 170-280VAC).
- Program 05: Battery type (AGM, Flooded, User-Defined).
- Program 06: Auto restart when overload occurs (Enable/Disable).
- Program 07: Auto restart when over temperature occurs (Enable/Disable).
- Program 09: Output frequency (50Hz/60Hz).
- Program 10: Output voltage (220V, 230V, 240V).
- Program 11: Maximum utility charging current.
- Program 12: Setting voltage point back to utility source.
- Program 13: Setting voltage point back to battery mode.
- Program 16: Charger source priority.
- Program 18: Alarm control (On/Off).
- Program 19: Auto return to default display screen (Enable/Disable).
- Program 20: Backlight control (On/Off).
- Program 22: Beeps while primary source is interrupted (On/Off).
- Program 23: Overload bypass (Enable/Disable).
- Program 25: Record Fault code (Enable/Disable).
- Program 26: Bulk charging voltage (C.V voltage).
- Program 27: Floating charging voltage.
- Program 28: AC output mode (Single phase).
- Program 29: Low DC cut-off voltage.
- Program 30: Battery equalization (Enable/Disable).
- Program 31: Battery equalization voltage.
- Program 33: Battery equalized time.
- Program 34: Battery equalized timeout.
- Program 35: Equalization interval.
- Program 36: Equalization activated immediately.
- Program 37: Communication protocol (Pylon, Ritar, Jabaida).
- Program 38: BMS alarm enable (Enable/Disable).
- Program 39: Discharge cut off Soc.
- Program 40: Charge stop Soc.
- Program 41: Restart Soc.
- Program 42: Grid-parallel operation (Not supported for this model).
5.5 Display Setting
Pressing the "UP" or "DOWN" key cycles through various display information on the LCD, including input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, DC discharging current, and main CPU Version.
5.6 Operating Mode Description
The inverter operates in different modes:
- Standby Mode: Inverter is off, but can charge batteries from PV or utility.
- Fault Mode: Errors detected (e.g., over temperature, short circuit). PV energy and utility can still charge batteries.
- Line Mode: Unit provides output power from mains and charges battery.
- Battery Mode: Unit provides output power from battery and PV power.
6. Setting for Lithium Battery
If using a compatible lithium battery, ensure the BMS communication cable is connected between the battery and the inverter. This cable facilitates communication for automatic adjustment of charging voltage, current, and discharge cut-off voltage based on battery parameters, and allows the inverter to start/stop charging according to battery status.
6.1 Lithium Battery Connection
- Assemble battery terminals based on recommended cable and terminal size (similar to lead-acid batteries).
- Connect the RJ45 port of the battery to the BMS (RS485) communication port of the inverter.
6.2 Battery Communication Cable Port Definition
Connect the RS485 end of the battery to the RS485 communication port of the inverter. Ensure the lithium battery port connects to the inverter is Pin to Pin. The communication cable is included in the package.
| Pin Number | Port Function |
|---|---|
| PIN1, PIN8 | RS485-B |
| PIN2, PIN7 | RS485-A |
| PIN3 | GND |
| PIN4 | CAN-H |
| PIN5 | CAN-L |
| PIN6 | GND |
6.3 LCD Setting for Lithium Battery
After connecting, confirm settings in Program 05 (Battery type) to "User-Defined" and Program 37 (Comm protocol) to the appropriate protocol (e.g., Pylon, Ritar, Jabaida) for your lithium battery.
6.4 LCD Display for Lithium Battery
If communication between the inverter and battery is successful, the "Li" icon will be solid on the LCD. If communication is unsuccessful, it will flash.
7. Maintenance
7.1 Clearance and Maintenance for Anti-Dust Kit
The inverter comes with a pre-installed anti-dust kit. This kit helps protect the inverter from dust and improves reliability. The inverter automatically detects this kit and adjusts internal thermal sensors.
- Loosen the screw on the top of the inverter in a counterclockwise direction.
- Remove the dustproof case and take out the air filter foam.
- Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back into the inverter.
NOTICE: The anti-dust kit should be cleaned every one month.
7.2 Battery Equalization Description
The equalization function helps reverse the buildup of negative chemical effects like stratification and removes sulfate crystals from battery plates, which can reduce battery capacity. It is recommended to equalize batteries periodically.
How to Apply Equalization Function:
Enable the battery equalization function in LCD setting program 30. Then, you can apply this function by:
- Setting the equalization interval in program 35.
- Activating equalization immediately in program 36.
When to Equalize:
In the float stage, when the set equalization interval is reached or equalization is actively initiated, the controller will enter the Equalize stage.
Equalize Charging Time and Timeout:
During the Equalize stage, the controller charges the battery until it reaches the battery equalization voltage. Constant-voltage regulation then maintains this voltage. The battery remains in this stage until the set equalized time is over. If the battery voltage does not reach the equalization voltage within the set time, the charge controller will extend the time. If the voltage is still low after the extended timeout, equalization will stop, and the charger will return to the float stage.
8. Troubleshooting
This section provides guidance on common issues, fault codes, and warning indicators.
8.1 Fault Reference Code
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | 01 |
| 02 | Over temperature or NTC is not connected well. | 02 |
| 03 | Battery voltage is too high | 03 |
| 04 | Battery voltage is too low | 04 |
| 05 | Output short circuit or over temperature is detected by internal converter components. | 05 |
| 06 | Output voltage is too high. | 06 |
| 07 | Overload time out | 07 |
| 08 | Bus voltage is too high | 08 |
| 09 | Bus soft start failed | 09 |
| 51 | Over current or surge | 51 |
| 52 | Bus voltage is too low | 52 |
| 53 | Inverter soft start fails | 53 |
| 55 | Over DC voltage in AC output | 55 |
| 57 | Current sensor fails | 57 |
| 58 | Output voltage is too low | 58 |
| 59 | PV voltage is over limitation | 59 |
| 71 | Firmware version inconsistent | 71 |
| 72 | Current sharing fault | 72 |
| 73 | Output voltage different | 73 |
| 80 | CAN fault | 80 |
| 81 | Host lost | 81 |
| 82 | Synchronization lost | 82 |
| 83 | Battery voltage detected different | 83 |
| 84 | AC input voltage and frequency detected different | 84 |
| 86 | AC output mode setting different | 85 |
8.2 Warning Indicator
| Warning Code | Warning Event | Audible Alarm | Icon Flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beeps three times every second | 01 |
| 02 | Over temperature | None | 02 |
| 03 | Battery is over-charged | Beeps once every second | 03 |
| 04 | Low battery | Beeps once every second | 04 |
| 07 | Overload | Beeps once every 0.5 second | OVERLOAD |
| 10 | Output power derating | Beeps twice every 3 seconds | 10 |
| 13 | BMS alarm or comm lost | Beeps twice every 3 seconds | 13 |
| 15 | PV energy is low. | Beeps twice every 3 seconds | 15 |
| 16 | High AC input (>280VAC) during BUS soft start | None | 16 |
| E9 | Battery equalization | None | E9 |
| bP | Battery is not connected | None | EQ |
8.3 General Troubleshooting Table
| Problem | LCD/LED/Buzzer | Explanation / Possible Cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer active for 3 seconds, then off. | The battery voltage is too low. | 1. Re-charge battery. 2. Replace battery. |
| No restart after power on. | No indication. | 1. Battery voltage is too low. 2. Battery polarity is connected reversed. | 1. Check if batteries and wiring are connected well. 2. Re-charge battery. 3. Replace battery. |
| Mains exist but unit works in battery mode. | Input voltage displayed as 0 on LCD, green LED flashing. | Input protector is tripped. | Check if AC breaker is tripped and AC wiring is connected well. |
| Green LED is flashing. | Insufficient quality of AC power (Shore or Generator). | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct (UPS Appliance). | |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When unit is turned on, internal relay switches on and off repeatedly. | LCD display and LEDs are flashing. | Battery is disconnected. | Check if battery wires are connected well. |
| Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. Inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 03 | The battery voltage is too high. | Check if spec and quantity of batteries are met requirements. | |
| Fault code 01 | Fan fault. | Check whether the fan is locked, or replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below 190Vac or higher than 260Vac). | Reduce the connected load. | |
| Fault code 08 | Bus voltage is too high. | Restart the device. If the fault repeats frequently, contact service. | |
| Fault code 09/53/57 | Internal components failed. | Contact service or return for repair. | |
| Fault code 51, 52, 55 | Over current or surge, Bus voltage too low, Inverter voltage DC component is over. | Restart the device. If fault repeats frequently, contact service. | |
| Fault code 80 | Communication abnormal. | Check the connection of parallel comm cable, then restart. If fault happens again, contact service. |
9. Specifications
9.1 Line Mode Specifications
| Parameter | 3.5KVA Model | 5.5KVA Model |
|---|---|---|
| Rated Output Power | 3.5KVA/3.5KW | 5.5KVA/5.5KW |
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 230Vac | |
| Low Loss Voltage (UPS) | 170Vac±7V | |
| Low Loss Voltage (Appliances) | 90Vac±7V | |
| Low Loss Return Voltage (UPS) | 180Vac±7V | |
| Low Loss Return Voltage (Appliances) | 100Vac±7V | |
| High Loss Voltage | 280Vac±7V | |
| High Loss Return Voltage | 270Vac±7V | |
| Max AC Input Voltage | 300Vac | |
| Nominal Input Frequency | 50Hz/60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Line mode: Circuit Breaker; Battery mode: Electronic Circuits | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
9.2 Inverter Mode Specifications
| Parameter | 3.5KVA Model | 5.5KVA Model |
|---|---|---|
| Rated Output Power | 3.5KVA/3.5KW | 5.5KVA/5.5KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 230Vac±5% | |
| Output Frequency | 50Hz or 60Hz | |
| Peak Efficiency | >93.5% | |
| Overload Protection | 5s@>140% load; 10s@100%~140% load | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 24.0Vdc | 48.0Vdc |
| Cold Start Voltage | 23.0Vdc | 46.0Vdc |
| Low DC Warning Voltage (@load < 20%) | 22.0Vdc | 44.0Vdc |
| Low DC Warning Voltage (@20% < load < 50%) | 21.4Vdc | 42.8Vdc |
| Low DC Warning Voltage (@load > 50%) | 20.2Vdc | 40.4Vdc |
| Low DC Warning Return Voltage (@load < 20%) | 23.0Vdc | 46.0Vdc |
| Low DC Warning Return Voltage (@20% < load < 50%) | 22.4Vdc | 44.8Vdc |
| Low DC Warning Return Voltage (@load > 50%) | 21.2Vdc | 42.4Vdc |
| Low DC Cut-off Voltage (@load < 20%) | 21.0Vdc | 42.0Vdc |
| Low DC Cut-off Voltage (@20% < load < 50%) | 20.4Vdc | 40.8Vdc |
| Low DC Cut-off Voltage (@load > 50%) | 19.2Vdc | 38.4Vdc |
9.3 Charge Mode Specifications
| Parameter | 3.5KVA Model | 5.5KVA Model |
|---|---|---|
| Max Charging Current (PV+AC) | 100Amp (@VI/P=230Vac) | |
| AC Charging Current (Max) | 60Amp (@VI/P=230Vac) | |
| Bulk Charging Voltage (Flooded Battery) | 29.2 Vdc | 58.4Vdc |
| Bulk Charging Voltage (AGM/Gel Battery) | 28.2Vdc | 56.4Vdc |
| Floating Charging Voltage | 27.0Vdc | 54.0Vdc |
| Overcharge Protection | 33.0Vdc | 63.0Vdc |
| Charging Algorithm | 3-Step | |
| Max. PV Array Power | 5000W | 6000W |
| Nominal PV Voltage | 240Vdc | |
| Start-up Voltage | 160Vdc +/-10Vdc | |
| PV Array MPPT Voltage Range | 120-450Vdc | |
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| Max. Input Current | 15 | 18 |
| Max Solar Charging Current | 100A | |
| Max AC Charging Current | 60A | |
| Solar Charger Type | MPPT | |
9.4 General Specifications
| Parameter | 3.5KVA Model | 5.5KVA Model |
|---|---|---|
| Safety Certification | CE | |
| Operating Temperature Range | -10°C to 55°C | |
| Storage temperature | -15°C - 60°C | |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
| Dimension (D*W*H), mm | 448x295x105(122) | |
| Net Weight, kg | 8.2(8.5) | 9.9(10.2) |
| Communication Interface | RS232/RS485CAN/Drycontact | |
| Battery type | Lead acid + Lithium battery | |
| Battery voltage range | 21-30V | 42-60V |
| Wave form | Pure Sine Wave | |
| Surge Power | 7000VA | 11000VA |
| Peak efficiency | 93.5% | |
| Switching time | 10ms(For Personal Computers); 20ms (For Home Appliances) | |
Note: Product specifications are subject to change without further notice.
10. User Tips
- PV Input Voltage: If operating without an external battery, ensure your solar panel array provides at least 150V DC to start the inverter. With an external battery, 120V DC is sufficient.
- BMS Communication: For optimal battery management and longevity, ensure your lithium battery has a compatible BMS and connect it to the inverter's BMS port. This allows for automatic adjustment of charging parameters.
- Parallel Operation: This specific GGH-6.5KVA-PRO (No WiFi) model does NOT support parallel operation. If you require parallel functionality, please ensure you purchase a model specifically designed for it.
- Maintenance Schedule: Regularly clean the anti-dust kit (monthly) to ensure efficient cooling and prolong the inverter's lifespan, especially in dusty environments.
- Generator Integration: Utilize the dry contact feature to automatically start your generator when grid power is unavailable or battery levels are low, ensuring continuous power supply.
11. Warranty and Support
The Daxtromn GGH-6.5KVA-PRO Hybrid Solar Inverter comes with a 1-year warranty.
For technical support, service, or repair, please contact your local dealer or authorized service center. Do not attempt to disassemble or repair the unit yourself, as this may void the warranty and pose safety risks.
A detailed user manual in PDF format is available for download: Download User Manual (PDF)