1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the PowMr FU65-248P 6.5KW 48V Split Phase Solar Inverter. This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support. It features a comprehensive LCD display and user-configurable button operation for settings like battery charging current, AC/solar charger priority, and acceptable input voltage.
1.1 Features
- Capable of operating without a battery.
- 120Vac single phase and 240Vac split phase output.
- Wide PV input voltage range: 100V~500Vdc.
- Excellent solar MPPT performance with efficiency up to 99%.
- Displays PV generated energy (total and daily information).
- Battery wake-up function.
- Capable of communicating with battery BMS via RS-485 interface.
- Pure sine wave inverter output.
- Configurable battery charging or discharging current via LCD settings.
- Configurable AC/Solar Charger priority via LCD settings.
- Overload, over temperature, and short circuit protection.
1.2 Basic System Architecture
The inverter/charger is designed to work with a generator or utility grid, and PV modules. It can power various home and office appliances, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners.

1.3 Product Overview
The inverter features an LCD display, status indicators, function buttons, and various input/output ports.

Key Components:
- LCD display
- Status indicator
- Bypass indicator
- Fault indicator
- Function buttons (ESC, UP, DOWN, ENTER)
- Power on/off switch
- AC input
- AC split phase output
- PV input
- Battery input
- Ground Screw
- BMS RS485 communication port
- USB communication port
- Dust proof components
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION – To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION – Only qualified personnel can install this device with a battery.
- NEVER charge a frozen battery.
- For optimum operation, follow required specifications for appropriate cable size.
- Be very cautious when working with metal tools on or around batteries to avoid sparks or short circuits.
- Strictly follow installation procedures when disconnecting AC or DC terminals.
- A 150A fuse is provided for over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS – This inverter/charger should be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
- NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
- Warning! Only qualified service persons are able to service this device. If errors persist after following troubleshooting, send the inverter/charger back to a local dealer or service center.
3. Setup
3.1 Unpacking and Inspection
Before installation, inspect the unit and ensure no damage occurred during transit. The package should contain:
- The unit x 1
- User manual x 1 (PDF version available at PowMr FU65-248P User Manual PDF)
- Screws x 2
3.2 Preparation
Before connecting any wiring, remove the bottom cover of the inverter as shown in the diagram below.

3.3 Mounting the Unit
Consider the following points when selecting a mounting location:
- Do not mount on flammable construction materials.
- Mount on a solid surface.
- Install at eye level for easy LCD display reading.
- Allow approximately 20 cm clearance to the sides and 50 cm above and below for proper air circulation and heat dissipation.
- Ambient temperature should be between 0°C and 55°C.
- Mount vertically on a wall.
- Ensure sufficient space for wiring and heat dissipation.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

3.4 Battery Connection
CAUTION: For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. A 150A fuse is provided for over-current protection.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable size for battery connection to reduce risk of injury.
Recommended Battery Cable Size:
| Model | Wire Size | Cable (mm²) | Torque Value (max) |
|---|---|---|---|
| FU65-248P | 1×3 AWG | 25 | 6 N-m |
Steps for Battery Connection:
- Remove 18 mm of insulation sleeve from positive and negative conductors.
- Suggest using bootlace ferrules on the ends of positive and negative wires with a proper crimping tool.
- Connect all battery packs as shown in the diagram.
- Insert the battery wires flatly into the inverter's battery connectors. Ensure bolts are tightened with a torque of 6 N·m in a clockwise direction. Verify correct polarity at both the battery and inverter/charger, and ensure conductors are tightly screwed into the battery terminals.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.
CAUTION: Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) is connected to negative (-).
3.5 AC Input/Output Connection
CAUTION: Before connecting to the AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures secure disconnection during maintenance and protection from overcurrent. Recommended AC breaker spec is 50A for 6.5KW.
CAUTION: There are two terminal blocks labeled "IN" and "OUT". Do NOT mis-connect input and output connectors.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection to reduce risk of injury.
Suggested Cable Requirement for AC Wires:
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| FU65-248P | 10 AWG | 6 | 2 N-m |
Steps for AC Input/Output Connection:
- Before making AC input/output connections, open the DC protector or disconnector.
- Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Connect the PE protective conductor (yellow-green) first. L1, L2 to LINE (brown or red), N to Neutral (black).

WARNING: Ensure the AC power source is disconnected before attempting to hardwire it to the unit.
- Insert AC output wires according to polarities indicated on the terminal block and tighten terminal screws. Connect the PE protective conductor first. L1, L2 to LINE (brown or red), N to Neutral (black).
- Ensure all wires are securely connected.

3.6 PV Connection
CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.
WARNING: Use appropriate cable size for PV module connection for system safety and efficient operation.
Suggested Cable Requirement for PV Wires:
| Model | Wire Size | Cable (mm²) | Torque Value (max) |
|---|---|---|---|
| FU65-248P | 1x 12AWG | 4 | 1.2 N·m |
PV Module Selection:
When selecting PV modules, consider the following:
- Open circuit voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter (500Vdc).
- Open circuit voltage (Voc) of PV modules should be higher than the minimum battery voltage.
Inverter Model Specifications:
- Max. PV Array Open Circuit Voltage: 500Vdc
- PV Array MPPT Voltage Range: 120Vdc~450Vdc
PV Module Wire Connection Steps:
- Remove 10 mm of insulation sleeve for positive and negative conductors.
- Suggest using bootlace ferrules on the ends of positive and negative wires with a proper crimping tool.
- Check correct polarity of wire connection from PV modules and PV input connectors. Connect positive pole (+) of the connection wire to the positive pole (+) of the PV input connector. Connect negative pole (-) of the connection wire to the negative pole (-) of the PV input connector. Screw two wires tightly in a clockwise direction.

3.7 Final Assembly
After connecting all wiring, re-attach the bottom cover by screwing in four screws as shown below.

3.8 Communication Connection
The inverter supports BMS RS-485, RS-232, and optional Wi-Fi cloud communication.
BMS RS-485 Communication: Use the supplied communication cable to connect to the inverter and the Lithium battery pack's BMS RS-485. Select the PYLON communication protocol. Once communication is established (battery icon "Li" blinks), re-configure charging voltage, charging current, battery discharge cut-off voltage, and SOC according to the lithium battery BMS parameters. If using lead-acid battery packs, BMS RS-485 communication is not used, and the screen icon displays "SLA".
RS-485 Port (to BMS) Signal Definition:
| PIN | Definition |
|---|---|
| Pin 8 | RS485-B |
| Pin 7 | RS485-A |
| Pin 6 | GND |
RS-232 Communication: Use a communication cable to connect the inverter to a PC. Use the upper computer software to view inverter information.
Wi-Fi Cloud Communication (Option): Use a communication cable to connect the inverter and a Wi-Fi module (or direct connect to inverter and WiFi PLUG). Download and install the APP from the APP store. Refer to the "WiFi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown on the mobile phone APP or computer webpage.

4. Operation
4.1 Power ON/OFF
Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the side of the unit) to turn on the unit.
4.2 Operation and Display Panel
The front panel of the inverter includes an LCD display, three indicators, and four function keys, providing operating status and input/output power information.

LED Indicator Messages:
| LED Indicator | Status | Messages |
|---|---|---|
| INV (Green) | Solid On | Output is powered by PV (main) or Bat in Inverter mode. |
| Flashing | Output is powered by bat (main) or PV in Inverter mode. | |
| HYBRID BYPASS (Yellow) | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by utility and PV/Bat in Hybrid mode. | |
| FAULT (Red) | Solid On | Fault condition occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or display in-turns |
4.3 LCD Display Icons
The LCD display uses various icons to convey information about input sources, configuration, faults, output, and battery status.
| Icon | Function Description |
|---|---|
| AC | Indicates the AC input or displays AC parameters. |
| PV | Indicates the PV input or displays PV parameters. |
| INV | Indicates the INV Output or displays INV parameters. |
| INPUTBATT | Indicates input voltage, input frequency, PV voltage, charger current, charger power, battery voltage, PV power generation, etc. |
| SET | Indicates the setting programs. |
| ERROR | Indicates warning and fault codes. Flashing for warning, solid for fault. |
| OUTPUTBATTLOAD | Indicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current. |
| CHARGING | Indicates battery SOC level (0-24%, 25-49%, 50-74%, 75-100%) in battery mode and charging status in line mode. |
| OVERLOAD | Indicates overload and load level (0-24%, 25-49%, 50-74%, 75-100%). |
| Grid Connection Icon | Indicates unit connects to the mains. |
| PV Panel Icon | Indicates unit connects to the PV panel, weak to strong power. |
| BYPASS | Indicates load is supplied by utility power. |
| Utility Charger Icon | Indicates the utility charger or PV supply circuit is working. |
| Inverter Circuit Icon | Indicates the DC/AC inverter circuit is working. |
| Mute Icon | Indicates unit alarm is disabled. |
4.4 LCD Setting
To enter setting mode, press and hold "ESC" and "ENTER" buttons together for more than 10 seconds. Use "UP" or "DOWN" to select programs, then "ENTER" to confirm or "ESC" to exit.
Example Settings:
| Program | Description | Selectable Option |
|---|---|---|
| 01 | Output voltage | 220V, 230V, 240V (default) |
| 02 | Output frequency | 50Hz, 60Hz (default) |
| 03 | Output source priority | Solar first (default), SBU priority, Utility first |
| 04 | Battery type | Li Battery (default), Lead-acid Battery, User-defined |
| 05 | Maximum Battery Charging Voltage | 58.4V (max.), 57.6V (default), 56.0V, 54.0V (min.) |
| 06 | Minimum Battery Discharging Voltage | 48.0V (max.), 46.2V, 45.0V (default), 42.0V (min.) |
| 07 | Battery SOC Reserved for backup | Lower SOC Reserved (default), Higher SOC Reserved |
| 08 | Maximum battery charging current | 100A (max.), 60A (default), 50A, 30A (min.) |
| 09 | Maximum battery discharging current | 120A (max.), 100A (default), 70A, 50A (min.) |
| 10 | Under voltage SOC value setting | 0% (default) |
| 11 | Enable the second output and set the SOC value | 48% (default) |
| 12 | Enabling or disabling the grid connection function | Default Off (SOF) |
| 13 | Alarm control | Alarm on (default), Alarm off |
| 14 | Restore factory setting | SET 14 DFE |
| 15 | Calendar Clock setting – Year | 2023year, 2024year, 2025year |
| 16 | Calendar Clock setting – Month | September, August, July |
| 17 | Calendar Clock setting – Day | The 12th day, The 11th day, The 10th day |
| 18 | Calendar Clock setting – Hour | The 14th hour, The 15th hour, The 16th hour |
| 19 | Calendar Clock setting – Minute | The 11th minute, The 12th minute, The 13th minute |
4.5 Display Information
The LCD display information can be switched by pressing "UP" or "DOWN" keys, or by pressing "ENTER" to cycle through information. Selectable information includes: Output voltage / Load power, Output frequency / Load current, PV voltage / PV current, PV generated energy (Today / PV power), Battery voltage / Battery SOC, Battery Charging current / Battery power, Unit temperature / Battery Discharging current, Input AC voltage / Input AC frequency, Unit firmware Version, and calendar clock.
4.6 PV Generated Energy Information Display
To display PV generated energy information, press and hold "ESC" and "UP" buttons together for more than 10 seconds. Use "UP" or "DOWN" to view PV generated energy Total or Daily for up to 10 days. Press "ENTER" to exit.
4.7 Operating Mode Description
The inverter supports various operating modes, each with specific behaviors for power flow and charging.
| Operation Mode | Description | LCD Display (Example) |
|---|---|---|
| Standby mode | The inverter is turned off, and no AC output. The battery can still be charged by solar energy or utility. | "OF" displayed, No charging icon, or Charging by solar/utility icons. |
| Fault mode | Errors caused by internal circuit issues or external reasons (e.g., over temperature, output short circuit). PV energy and utility can charge batteries. | No charging icon, or Charging by solar/utility icons. |
| Bypass Mode | Load power is provided only by the mains. The battery can be charged by mains or solar energy. | BYPASS icon, with or without CHARGING icon. |
| Hybrid Mode | Load power is provided by mains and solar energy or battery together. Battery can be charged by superfluous solar energy. | Various combinations of utility, solar, and battery icons with CHARGING. |
| Inverter Mode | Load power is provided by solar energy and battery together. Battery can be charged by superfluous solar energy. | Battery icon, solar panel icon, with or without CHARGING. |
5. Maintenance
Regular maintenance ensures the longevity and optimal performance of your PowMr inverter. Always disconnect all power sources (AC, DC, PV) before performing any maintenance.
- Cleaning: Periodically clean the exterior of the inverter with a dry, soft cloth. Ensure ventilation openings are free from dust and debris to maintain proper cooling.
- Connections: Annually check all electrical connections (battery, AC input/output, PV input) for tightness and signs of corrosion. Re-tighten if necessary.
- Battery Inspection: If using lead-acid batteries, check electrolyte levels and terminal conditions as per battery manufacturer guidelines. For lithium batteries, monitor BMS data for any anomalies.
- Environment: Ensure the operating environment remains within specified temperature and humidity ranges.
- Firmware Updates: Check the manufacturer's website or contact support for any available firmware updates that may improve performance or add features.
6. Troubleshooting
This section provides solutions for common issues. If problems persist, contact technical support.
6.1 Fault Reference Code
When a fault occurs, the red FAULT LED will be on, and the LCD will display a fault code. The buzzer may beep continuously.
| Fault Code | Fault / Event | What to do |
|---|---|---|
| 01 | Overload time out | Reduce the connected load by switching off some equipment. |
| 02 | Over temperature fault: The temperature of the radiator inside the inverter exceeds 80°C. | Check whether the inlet and outlet of the inverter are blocked or the ambient temperature is too high. |
| 03 | INV Over current | Restart the inverter. If it does not work properly, return to the repair center. |
| 04 | Output short circuit | Check if wiring is connected well and remove abnormal load. |
| 05 | High output voltage | Restart the inverter. If it does not work properly, return to the repair center. |
| 06 | Low output voltage | Restart the inverter. If it does not work properly, return to the repair center. |
| 07 | The bus voltage is abnormal | Restart the inverter. If it does not work properly, return to the repair center. |
| 08 | The bus voltage is too high | Restart the inverter. If it does not work properly, return to the repair center. |
| 09 | The bus voltage is too low | Restart the inverter. If it does not work properly, return to the repair center. |
| 10 | PV over current | Check if wiring is connected well or replace the fan. |
| 11 | Fan error | Check if wiring is connected well or replace the fan. |
| 12 | The battery voltage is too high. | 1. Check if wiring is connected well; 2. Check if spec and quality of batteries are meet requirements. |
| 13 | The battery voltage is too low. | 1. Check if wiring is connected well; 2. Check if spec and quality of batteries are meet requirements. |
| 14 | Battery not connected | 1. Check if wiring is connected well; 2. Check if spec and quality of batteries are meet requirements. |
6.2 Common Issues and Solutions
| Problem | LCD/LED/Buzzer | Explanation / Possible Cause | What to do |
|---|---|---|---|
| Mains power often outages, battery backup time is insufficient | The inverter works properly. | Poor battery performance or small capacity; Battery SOC is low during power outage. | Increase battery capacity; Select "SBU" priority and set "Battery SOC Reserved" to "High (SoH)", or select "UTL" mains priority to keep battery SOC high in case of mains outage. |
| The electricity supply is stable, but the electricity bill has not decreased significantly | The inverter works properly. | Insufficient use of solar energy or batteries. | If mains is stable, select SBU and set Battery SOC Reserved to "Low (SoL)" to reduce mains power supply by making full use of solar power and battery energy storage. |
| There is no reaction after the battery is connected | No display | Battery voltage is too low; The battery polarity is reversed; The battery input is insured damaged. | 1. Check whether the battery connection is normal; 2. Charge or replace the battery; 3. Replace insurance. |
| After the battery is connected, it automatically shuts down during startup | The LCD/LEDs and buzzer work for 3S and then turn off | Battery voltage is too low | 1. Re-charge battery. 2. Replace battery. |
| When the mains is connected, the LCD voltage of the inverter is 0 | Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. |
| Green LED is flashing. | Insufficient quality of AC power. | 1. Check if AC wires are too thin and/or too long; 2. Check whether the mains voltage is normal or the input voltage range is set correctly. | |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
7. Specifications
Detailed technical specifications for the PowMr FU65-248P inverter.

8. User Tips
- For optimal battery life and system efficiency, regularly monitor your battery's State of Charge (SOC) and adjust charging/discharging parameters via the LCD settings if needed.
- When setting up PV connections, double-check all polarities to prevent damage to the inverter and ensure safe operation.
- Consider using the Wi-Fi monitoring feature for real-time data and remote management, which can help in optimizing energy usage and detecting issues early.
- Ensure adequate ventilation around the inverter to prevent overheating, especially in warmer climates, as this can impact performance and lifespan.