PowMr FU65-248P

Contents

PowMr FU65-248P 6.5KW 48V Split Phase Solar Inverter

User Manual

1. Introduction

This manual describes the assembly, installation, operation, and troubleshooting of the PowMr FU65-248P 6.5KW 48V Split Phase Solar Inverter. This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support. It features a comprehensive LCD display and user-configurable button operation for settings like battery charging current, AC/solar charger priority, and acceptable input voltage.

1.1 Features

  • Capable of operating without a battery.
  • 120Vac single phase and 240Vac split phase output.
  • Wide PV input voltage range: 100V~500Vdc.
  • Excellent solar MPPT performance with efficiency up to 99%.
  • Displays PV generated energy (total and daily information).
  • Battery wake-up function.
  • Capable of communicating with battery BMS via RS-485 interface.
  • Pure sine wave inverter output.
  • Configurable battery charging or discharging current via LCD settings.
  • Configurable AC/Solar Charger priority via LCD settings.
  • Overload, over temperature, and short circuit protection.

1.2 Basic System Architecture

The inverter/charger is designed to work with a generator or utility grid, and PV modules. It can power various home and office appliances, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners.

Solar PV Inverter system diagram showing connections to PV input, utility grid, generator, battery bank, and home loads.
Figure: Basic System Architecture for the PowMr FU65-248P Inverter. This diagram illustrates how the inverter connects to solar panels (PV Input), a battery bank, the utility grid or a generator (AC Input), and various home loads (AC Output).

1.3 Product Overview

The inverter features an LCD display, status indicators, function buttons, and various input/output ports.

Various views of the FU65-248P inverter (front, back, side) with labels for components.
Figure: FU65-248P Inverter Views. This image shows the front, back, and side views of the inverter, highlighting the LCD display, indicators, function buttons, AC input/output, PV input, battery input, ground screw, and communication ports.

Key Components:

  1. LCD display
  2. Status indicator
  3. Bypass indicator
  4. Fault indicator
  5. Function buttons (ESC, UP, DOWN, ENTER)
  6. Power on/off switch
  7. AC input
  8. AC split phase output
  9. PV input
  10. Battery input
  11. Ground Screw
  12. BMS RS485 communication port
  13. USB communication port
  14. Dust proof components

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  • Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  • CAUTION – To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  • Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  • To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  • CAUTION – Only qualified personnel can install this device with a battery.
  • NEVER charge a frozen battery.
  • For optimum operation, follow required specifications for appropriate cable size.
  • Be very cautious when working with metal tools on or around batteries to avoid sparks or short circuits.
  • Strictly follow installation procedures when disconnecting AC or DC terminals.
  • A 150A fuse is provided for over-current protection for the battery supply.
  • GROUNDING INSTRUCTIONS – This inverter/charger should be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
  • NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  • Warning! Only qualified service persons are able to service this device. If errors persist after following troubleshooting, send the inverter/charger back to a local dealer or service center.

3. Setup

3.1 Unpacking and Inspection

Before installation, inspect the unit and ensure no damage occurred during transit. The package should contain:

3.2 Preparation

Before connecting any wiring, remove the bottom cover of the inverter as shown in the diagram below.

Diagram showing the inverter with its bottom cover removed for wiring access.
Figure: Inverter with Bottom Cover Removed. This diagram illustrates the process of removing the bottom cover to access wiring terminals.

3.3 Mounting the Unit

Consider the following points when selecting a mounting location:

  • Do not mount on flammable construction materials.
  • Mount on a solid surface.
  • Install at eye level for easy LCD display reading.
  • Allow approximately 20 cm clearance to the sides and 50 cm above and below for proper air circulation and heat dissipation.
  • Ambient temperature should be between 0°C and 55°C.
  • Mount vertically on a wall.
  • Ensure sufficient space for wiring and heat dissipation.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Diagram showing recommended clearances for mounting the inverter on a wall.
Figure: Mounting Clearances. This diagram shows the recommended minimum clearances (20cm sides, 50cm top/bottom) for proper air circulation when mounting the inverter.

3.4 Battery Connection

CAUTION: For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. A 150A fuse is provided for over-current protection.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable size for battery connection to reduce risk of injury.

Recommended Battery Cable Size:

ModelWire SizeCable (mm²)Torque Value (max)
FU65-248P1×3 AWG256 N-m

Steps for Battery Connection:

  1. Remove 18 mm of insulation sleeve from positive and negative conductors.
  2. Suggest using bootlace ferrules on the ends of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as shown in the diagram.
  4. Insert the battery wires flatly into the inverter's battery connectors. Ensure bolts are tightened with a torque of 6 N·m in a clockwise direction. Verify correct polarity at both the battery and inverter/charger, and ensure conductors are tightly screwed into the battery terminals.
Diagram showing battery wiring to the inverter terminals, emphasizing correct polarity.
Figure: Battery Terminal Connection. This diagram illustrates the correct way to connect battery wires to the inverter's terminals, ensuring proper polarity.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.

CAUTION: Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) is connected to negative (-).

3.5 AC Input/Output Connection

CAUTION: Before connecting to the AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures secure disconnection during maintenance and protection from overcurrent. Recommended AC breaker spec is 50A for 6.5KW.

CAUTION: There are two terminal blocks labeled "IN" and "OUT". Do NOT mis-connect input and output connectors.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection to reduce risk of injury.

Suggested Cable Requirement for AC Wires:

ModelGaugeCable (mm²)Torque Value
FU65-248P10 AWG62 N-m

Steps for AC Input/Output Connection:

  1. Before making AC input/output connections, open the DC protector or disconnector.
  2. Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Connect the PE protective conductor (yellow-green) first. L1, L2 to LINE (brown or red), N to Neutral (black).
Diagram showing AC input wiring to the inverter terminal block.
Figure: AC Input Wiring. This diagram illustrates the correct connection of AC input wires to the inverter's terminal block, including PE, L1, L2, and N.

WARNING: Ensure the AC power source is disconnected before attempting to hardwire it to the unit.

  1. Insert AC output wires according to polarities indicated on the terminal block and tighten terminal screws. Connect the PE protective conductor first. L1, L2 to LINE (brown or red), N to Neutral (black).
  2. Ensure all wires are securely connected.
Diagram showing AC output wiring from the inverter terminal block.
Figure: AC Output Wiring. This diagram illustrates the correct connection of AC output wires from the inverter's terminal block.

3.6 PV Connection

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING: Use appropriate cable size for PV module connection for system safety and efficient operation.

Suggested Cable Requirement for PV Wires:

ModelWire SizeCable (mm²)Torque Value (max)
FU65-248P1x 12AWG41.2 N·m

PV Module Selection:

When selecting PV modules, consider the following:

  • Open circuit voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter (500Vdc).
  • Open circuit voltage (Voc) of PV modules should be higher than the minimum battery voltage.

Inverter Model Specifications:

  • Max. PV Array Open Circuit Voltage: 500Vdc
  • PV Array MPPT Voltage Range: 120Vdc~450Vdc

PV Module Wire Connection Steps:

  1. Remove 10 mm of insulation sleeve for positive and negative conductors.
  2. Suggest using bootlace ferrules on the ends of positive and negative wires with a proper crimping tool.
  3. Check correct polarity of wire connection from PV modules and PV input connectors. Connect positive pole (+) of the connection wire to the positive pole (+) of the PV input connector. Connect negative pole (-) of the connection wire to the negative pole (-) of the PV input connector. Screw two wires tightly in a clockwise direction.
Diagram showing PV input wiring to the inverter terminal block.
Figure: PV Input Wiring. This diagram illustrates the correct connection of PV input wires to the inverter's terminal block.

3.7 Final Assembly

After connecting all wiring, re-attach the bottom cover by screwing in four screws as shown below.

Diagram showing the re-attachment of the inverter's bottom cover.
Figure: Final Assembly. This diagram shows the inverter with its bottom cover being re-attached after all wiring is complete.

3.8 Communication Connection

The inverter supports BMS RS-485, RS-232, and optional Wi-Fi cloud communication.

BMS RS-485 Communication: Use the supplied communication cable to connect to the inverter and the Lithium battery pack's BMS RS-485. Select the PYLON communication protocol. Once communication is established (battery icon "Li" blinks), re-configure charging voltage, charging current, battery discharge cut-off voltage, and SOC according to the lithium battery BMS parameters. If using lead-acid battery packs, BMS RS-485 communication is not used, and the screen icon displays "SLA".

RS-485 Port (to BMS) Signal Definition:

PINDefinition
Pin 8RS485-B
Pin 7RS485-A
Pin 6GND

RS-232 Communication: Use a communication cable to connect the inverter to a PC. Use the upper computer software to view inverter information.

Wi-Fi Cloud Communication (Option): Use a communication cable to connect the inverter and a Wi-Fi module (or direct connect to inverter and WiFi PLUG). Download and install the APP from the APP store. Refer to the "WiFi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown on the mobile phone APP or computer webpage.

Diagrams showing the WiFi plug, USB port, and BMS RS-485 communication ports on the inverter.
Figure: Communication Ports. This image illustrates the locations of the WiFi plug, USB port, and BMS RS-485 port on the inverter for various communication methods.

4. Operation

4.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the side of the unit) to turn on the unit.

4.2 Operation and Display Panel

The front panel of the inverter includes an LCD display, three indicators, and four function keys, providing operating status and input/output power information.

Close-up of the inverter's front panel with LCD display, LED indicators, and function keys.
Figure: Operation and Display Panel. This image highlights the LCD display, LED indicators (INV, HYBRID BYPASS, FAULT), and function keys (ESC, UP, DOWN, ENTER) on the inverter's front panel.

LED Indicator Messages:

LED IndicatorStatusMessages
INV (Green)Solid OnOutput is powered by PV (main) or Bat in Inverter mode.
FlashingOutput is powered by bat (main) or PV in Inverter mode.
HYBRID BYPASS (Yellow)Solid OnOutput is powered by utility in Line mode.
FlashingOutput is powered by utility and PV/Bat in Hybrid mode.
FAULT (Red)Solid OnFault condition occurs in the inverter.
FlashingWarning condition occurs in the inverter.

Function Keys:

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or display in-turns

4.3 LCD Display Icons

The LCD display uses various icons to convey information about input sources, configuration, faults, output, and battery status.

IconFunction Description
ACIndicates the AC input or displays AC parameters.
PVIndicates the PV input or displays PV parameters.
INVIndicates the INV Output or displays INV parameters.
INPUTBATTIndicates input voltage, input frequency, PV voltage, charger current, charger power, battery voltage, PV power generation, etc.
SETIndicates the setting programs.
ERRORIndicates warning and fault codes. Flashing for warning, solid for fault.
OUTPUTBATTLOADIndicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current.
CHARGINGIndicates battery SOC level (0-24%, 25-49%, 50-74%, 75-100%) in battery mode and charging status in line mode.
OVERLOADIndicates overload and load level (0-24%, 25-49%, 50-74%, 75-100%).
Grid Connection IconIndicates unit connects to the mains.
PV Panel IconIndicates unit connects to the PV panel, weak to strong power.
BYPASSIndicates load is supplied by utility power.
Utility Charger IconIndicates the utility charger or PV supply circuit is working.
Inverter Circuit IconIndicates the DC/AC inverter circuit is working.
Mute IconIndicates unit alarm is disabled.

4.4 LCD Setting

To enter setting mode, press and hold "ESC" and "ENTER" buttons together for more than 10 seconds. Use "UP" or "DOWN" to select programs, then "ENTER" to confirm or "ESC" to exit.

Example Settings:

ProgramDescriptionSelectable Option
01Output voltage220V, 230V, 240V (default)
02Output frequency50Hz, 60Hz (default)
03Output source prioritySolar first (default), SBU priority, Utility first
04Battery typeLi Battery (default), Lead-acid Battery, User-defined
05Maximum Battery Charging Voltage58.4V (max.), 57.6V (default), 56.0V, 54.0V (min.)
06Minimum Battery Discharging Voltage48.0V (max.), 46.2V, 45.0V (default), 42.0V (min.)
07Battery SOC Reserved for backupLower SOC Reserved (default), Higher SOC Reserved
08Maximum battery charging current100A (max.), 60A (default), 50A, 30A (min.)
09Maximum battery discharging current120A (max.), 100A (default), 70A, 50A (min.)
10Under voltage SOC value setting0% (default)
11Enable the second output and set the SOC value48% (default)
12Enabling or disabling the grid connection functionDefault Off (SOF)
13Alarm controlAlarm on (default), Alarm off
14Restore factory settingSET 14 DFE
15Calendar Clock setting – Year2023year, 2024year, 2025year
16Calendar Clock setting – MonthSeptember, August, July
17Calendar Clock setting – DayThe 12th day, The 11th day, The 10th day
18Calendar Clock setting – HourThe 14th hour, The 15th hour, The 16th hour
19Calendar Clock setting – MinuteThe 11th minute, The 12th minute, The 13th minute

4.5 Display Information

The LCD display information can be switched by pressing "UP" or "DOWN" keys, or by pressing "ENTER" to cycle through information. Selectable information includes: Output voltage / Load power, Output frequency / Load current, PV voltage / PV current, PV generated energy (Today / PV power), Battery voltage / Battery SOC, Battery Charging current / Battery power, Unit temperature / Battery Discharging current, Input AC voltage / Input AC frequency, Unit firmware Version, and calendar clock.

4.6 PV Generated Energy Information Display

To display PV generated energy information, press and hold "ESC" and "UP" buttons together for more than 10 seconds. Use "UP" or "DOWN" to view PV generated energy Total or Daily for up to 10 days. Press "ENTER" to exit.

4.7 Operating Mode Description

The inverter supports various operating modes, each with specific behaviors for power flow and charging.

Operation ModeDescriptionLCD Display (Example)
Standby modeThe inverter is turned off, and no AC output. The battery can still be charged by solar energy or utility."OF" displayed, No charging icon, or Charging by solar/utility icons.
Fault modeErrors caused by internal circuit issues or external reasons (e.g., over temperature, output short circuit). PV energy and utility can charge batteries.No charging icon, or Charging by solar/utility icons.
Bypass ModeLoad power is provided only by the mains. The battery can be charged by mains or solar energy.BYPASS icon, with or without CHARGING icon.
Hybrid ModeLoad power is provided by mains and solar energy or battery together. Battery can be charged by superfluous solar energy.Various combinations of utility, solar, and battery icons with CHARGING.
Inverter ModeLoad power is provided by solar energy and battery together. Battery can be charged by superfluous solar energy.Battery icon, solar panel icon, with or without CHARGING.

5. Maintenance

Regular maintenance ensures the longevity and optimal performance of your PowMr inverter. Always disconnect all power sources (AC, DC, PV) before performing any maintenance.

  • Cleaning: Periodically clean the exterior of the inverter with a dry, soft cloth. Ensure ventilation openings are free from dust and debris to maintain proper cooling.
  • Connections: Annually check all electrical connections (battery, AC input/output, PV input) for tightness and signs of corrosion. Re-tighten if necessary.
  • Battery Inspection: If using lead-acid batteries, check electrolyte levels and terminal conditions as per battery manufacturer guidelines. For lithium batteries, monitor BMS data for any anomalies.
  • Environment: Ensure the operating environment remains within specified temperature and humidity ranges.
  • Firmware Updates: Check the manufacturer's website or contact support for any available firmware updates that may improve performance or add features.

6. Troubleshooting

This section provides solutions for common issues. If problems persist, contact technical support.

6.1 Fault Reference Code

When a fault occurs, the red FAULT LED will be on, and the LCD will display a fault code. The buzzer may beep continuously.

Fault CodeFault / EventWhat to do
01Overload time outReduce the connected load by switching off some equipment.
02Over temperature fault: The temperature of the radiator inside the inverter exceeds 80°C.Check whether the inlet and outlet of the inverter are blocked or the ambient temperature is too high.
03INV Over currentRestart the inverter. If it does not work properly, return to the repair center.
04Output short circuitCheck if wiring is connected well and remove abnormal load.
05High output voltageRestart the inverter. If it does not work properly, return to the repair center.
06Low output voltageRestart the inverter. If it does not work properly, return to the repair center.
07The bus voltage is abnormalRestart the inverter. If it does not work properly, return to the repair center.
08The bus voltage is too highRestart the inverter. If it does not work properly, return to the repair center.
09The bus voltage is too lowRestart the inverter. If it does not work properly, return to the repair center.
10PV over currentCheck if wiring is connected well or replace the fan.
11Fan errorCheck if wiring is connected well or replace the fan.
12The battery voltage is too high.1. Check if wiring is connected well; 2. Check if spec and quality of batteries are meet requirements.
13The battery voltage is too low.1. Check if wiring is connected well; 2. Check if spec and quality of batteries are meet requirements.
14Battery not connected1. Check if wiring is connected well; 2. Check if spec and quality of batteries are meet requirements.

6.2 Common Issues and Solutions

ProblemLCD/LED/BuzzerExplanation / Possible CauseWhat to do
Mains power often outages, battery backup time is insufficientThe inverter works properly.Poor battery performance or small capacity; Battery SOC is low during power outage.Increase battery capacity; Select "SBU" priority and set "Battery SOC Reserved" to "High (SoH)", or select "UTL" mains priority to keep battery SOC high in case of mains outage.
The electricity supply is stable, but the electricity bill has not decreased significantlyThe inverter works properly.Insufficient use of solar energy or batteries.If mains is stable, select SBU and set Battery SOC Reserved to "Low (SoL)" to reduce mains power supply by making full use of solar power and battery energy storage.
There is no reaction after the battery is connectedNo displayBattery voltage is too low; The battery polarity is reversed; The battery input is insured damaged.1. Check whether the battery connection is normal; 2. Charge or replace the battery; 3. Replace insurance.
After the battery is connected, it automatically shuts down during startupThe LCD/LEDs and buzzer work for 3S and then turn offBattery voltage is too low1. Re-charge battery. 2. Replace battery.
When the mains is connected, the LCD voltage of the inverter is 0Input voltage is displayed as 0 on the LCD and green LED is flashing.Input protector is trippedCheck if AC breaker is tripped and AC wiring is connected well.
Green LED is flashing.Insufficient quality of AC power.1. Check if AC wires are too thin and/or too long; 2. Check whether the mains voltage is normal or the input voltage range is set correctly.
Green LED is flashing.Set "Solar First" as the priority of output source.Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.LCD display and LEDs are flashingBattery is disconnected.Check if battery wires are connected well.

7. Specifications

Detailed technical specifications for the PowMr FU65-248P inverter.

Table of detailed technical specifications for the PowMr FU65-248P inverter, including PV array, battery, AC input, AC output, protection, and general data.
Figure: Technical Specifications. This table provides comprehensive details on PV array, battery, AC input, AC output, protection features, and general operating data for the FU65-248P inverter.

8. User Tips

  • For optimal battery life and system efficiency, regularly monitor your battery's State of Charge (SOC) and adjust charging/discharging parameters via the LCD settings if needed.
  • When setting up PV connections, double-check all polarities to prevent damage to the inverter and ensure safe operation.
  • Consider using the Wi-Fi monitoring feature for real-time data and remote management, which can help in optimizing energy usage and detecting issues early.
  • Ensure adequate ventilation around the inverter to prevent overheating, especially in warmer climates, as this can impact performance and lifespan.

9. Warranty and Support

For technical support, service, or warranty inquiries, please contact PowMr directly using the information below. Keep your purchase receipt as proof of purchase.