1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the DATOUBOSS 11kW Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference. This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support in a portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
1.1 Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible with mains voltage or generator power
- Auto restart while AC is recovering
- Overload/Over temperature/short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
- Support parallel connection of inverters, up to 9 inverters can be parallelized
- Supports grid connection (user must complete relevant procedures)
- Support three-phase power input and output (at least three inverters required)
- Support BMS battery communication
- Support battery-less operation
- Support WiFi connection monitoring
- Built-in dual MPPT, support dual PV inputs
- Support timer switch on/off and timer charging of battery
- Support power generation statistics function
- With lithium battery activation function
- With diesel generator dry node
1.2 Basic System Architecture
The following illustration shows a basic application for this inverter/charger, including photovoltaic modules, generators, batteries, and various home appliances.

Diagram: A typical home solar power system showing solar panels, a generator, batteries, the inverter, and various household appliances connected.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable size. It is very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short-circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to the local dealer or service center for maintenance.
3. Product Overview
3.1 LCD Screen and Control Panel
The inverter features an LCD screen and control buttons for monitoring and configuration. The control panel includes ESC, UP, DOWN, and ENTER buttons for navigation and selection.

Image: Front view of the inverter showing the LCD display and control buttons.
3.2 Back Panel Connections
The back panel provides all necessary connection ports for the inverter system.

Image: Rear view of the inverter showing various input and output ports.
Back Panel Port Descriptions:
- LCD display
- Status display
- Charging indicator
- Error display
- Function keys (ESC, UP, DOWN, ENTER)
- AC Input
- Main Output
- Second Output
- BMS/RS485 Communication Port
- RS232 Communication Port
- Solar Panel input (PV1, PV2)
- Parallel connection ports
- Dry Contact
- Battery input (POS+, NEG-)
- Power ON/OFF Switch
4. Setup and Installation
4.1 Unpacking and Inspection
Before installation, inspect the unit. Ensure that nothing inside the package is damaged. You should have received the following items:
- The inverter unit x 1
- User manual x 1
4.2 Preparation
Before connecting any cables, remove the bottom cover of the inverter by unscrewing two screws.
4.3 Mounting the Unit
Consider the following points when selecting where to install the inverter:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the sides and approximately 50 cm above and below the unit.
- The ambient temperature should be between and to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces clear as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing three screws:
- Use M6*80mm expansion bolts for points 1 and 2.
- Use M4 or M5 for point 3.

Diagram: Recommended clearances for inverter mounting (20cm side, 50cm top/bottom).
4.4 Battery Connection
CAUTION:
- For safety and regulation compliance, it is requested to install a separate DC over-current protector or disconnect device between the battery and inverter.
- Only qualified personnel must perform all wiring.
- It is very important for system safety and efficient operation to use appropriate cable for battery connection.
Assemble battery ring terminals based on the recommended battery cable and terminal size. Ensure correct polarity (positive to positive, negative to negative) and tighten bolts with a torque of 2 Nm.
Recommended Battery Cable and Terminal Size:
| Rated Capacity | Typical Amperage | Battery Capacity | Wire Size | Cable (mm²) | Ring Terminal D (mm) | Ring Terminal L (mm) | Torque Value |
|---|---|---|---|---|---|---|---|
| 2KVA | 88A | 100AH | 1*6AWG | 14 | 6.4 | 33.2 | 2-3 Nm |
| 2*10AWG | 6 | 6.4 | 23.8 | ||||
| 3KVA | 132A | 100AH | 1*4AWG | 22 | 6.4 | 33.2 | 2-3 Nm |
| 200AH | 2*8AWG | 9 | 6.4 | 29.2 | |||
| 3.6KVA | 165A | 200AH | 2*4AWG | 25 | 8.4 | 33.2 | 5Nm |
| 5KVA | 109A | 200AH | 1*2AWG | 38 | 6.4 | 39.2 | 2-3 Nm |
| 2*6AWG | 28 | 6.4 | 33.2 | ||||
| 5.5KVA | 121A | 200AH | 1*2AWG | 34 | 6.4 | 39.2 | 2-3 Nm |
| 2*6AWG | 14 | 6.4 | 33.2 | ||||
| 6.2KVA | 124A | 200AH | 1*2AWG | 38 | 8.4 | 39.2 | 5Nm |
| 2*4AWG | 25 | 8.4 | 33.2 | ||||
| 8KVA | 183.2A | 250AH | 1*2/0AWG | 67.4 | 8.4 | 51 | 5Nm |
| 11KVA | 228A | 250AH | 1*3/0AWG | 85 | 8.4 | 54 | 5Nm |
WARNING: Be sure the length of all battery cables is the same. Otherwise, there will be voltage difference between the inverter and battery, causing parallel inverters to not work.
4.5 AC Input/Output Connection
CAUTION:
- Before connecting to an AC input power source, install a separate AC breaker between the inverter and the AC input source. This ensures the inverter can be disconnected during maintenance and is fully protected from overcurrent.
- The recommended breaker specification is 63A for a 48V system.
- There are two terminal blocks with "IN" and "OUT" markings. Do NOT mis-connect input and output connectors.
WARNING: All wiring must be performed by qualified personnel. It is very important for system safety and efficient operation to use appropriate cable for AC input connection.
Suggested Cable Requirement for AC Wires:
| Rated Capacity | Gauge | Torque Value |
|---|---|---|
| 2KVA | 14AWG | 0.8-1.0Nm |
| 3KVA | 12AWG | 1.2-1.6Nm |
| 3.6KVA | 12AWG | 1.2-1.6Nm |
| 5KVA | 10AWG | 1.4-1.6Nm |
| 5.5KVA | 10AWG | 1.4-1.6Nm |
| 6.2KVA | 10AWG | 1.4-1.6Nm |
| 8KVA | 8AWG | 1.4-1.6Nm |
| 11KVA | 8AWG | 1.4-1.6Nm |
Follow these steps to implement AC input/output connection:
- Before making AC input/output connections, ensure the DC protector or disconnector is open.
- Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N3 mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (ground) first.
Recommended AC Input and Output Cable Size for Each Inverter:
| Rated Capacity | AWG no. | Torque |
|---|---|---|
| 3KW | 12AWG | 1.2~1.6Nm |
| 3.6KW | 12AWG | 1.2~1.6Nm |
| 5KW | 10AWG | 1.2~1.6Nm |
| 5.5KW | 10AWG | 1.2~1.6Nm |
| 6.2KW | 10AWG | 1.2~1.6Nm |
| 8KW | 8AWG | 1.4-1.6Nm |
| 11KW | 8AWG | 1.4-1.6Nm |
WARNING: Make sure all output N wires of each inverter are connected at all times. Otherwise, it will cause inverter fault in error code #72.
CAUTION: Install the breaker at the battery and AC input side. This will ensure the inverter can be securely disconnected during maintenance and fully protected from overcurrent of battery or AC input.
4.6 PV Connection (Only for models with solar charger)
CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.
WARNING: All wiring must be performed by qualified personnel. It is very important for system safety and efficient operation to use appropriate cable for PV module connection.
Suggested Cable Requirement for PV Wires:
| Typical Amperage | Gauge | Torque Value |
|---|---|---|
| 30A | 12AWG | 1.4-1.6Nm |
Follow these steps to implement PV module connection:
- Remove 10mm of insulation sleeve for positive and negative conductors.
- It is suggested to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Fix the wire cover to the inverter with supplied screws.
- Check correct polarity of wire from PV modules and PV input connectors. Connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Screw two wires tightly in a clockwise direction. Recommended tool: 4mm blade screwdriver.

Diagram: Dual MPPT input showing two separate PV arrays connected to the inverter.
4.7 Parallel Connection
NOTICE: It is requested to connect to the battery for parallel operation.
The inverter supports parallel operation for increased power output or three-phase output. Up to 9 units can be parallelized.
Parallel in Single Phase:
For single-phase parallel operation, connect the communication cables between units as shown in the diagram. Ensure all breakers in the line wires of the load side are open and each neutral wire of each unit is connected together.

Diagram: Example of parallel wiring for multiple inverters, showing communication and power connections.
WARNING: Do not connect the current sharing cable between inverters which are in different phases. Otherwise, it may damage the inverters.
Three-Phase Output:
For three-phase output, a minimum of three inverters are required. Connect the inverters and communication cables as per the diagram. Each phase (L1, L2, L3) requires at least one inverter.

Diagram: Detailed wiring diagram for a three-phase system with multiple inverters, showing connections to mains power, generator, PV, batteries, and loads.
Parallel Connection Setup Video:
Video: This video demonstrates the process of connecting multiple DATOUBOSS 11kW Hybrid Solar Inverters in parallel for three-phase output, including wiring communication cables, AC input/output, and verifying output voltage.
4.8 Final Assembly
After connecting all wirings, please put the bottom cover back by screwing the two screws.
5. Operation
5.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the button of the case) to turn on the unit.
Steps to Start Up:
- Connect the battery that meets the requirements (battery voltage needs to be beyond 23V) or AC (AC needs to confirm the suitable input range depending on the output mode). Then you can start up the inverter.
- Mains Power On: Connect to normal AC power, press the switch. The system will automatically turn on. If AC output power priority is set, after a period of time, the panel will display AC mode, indicating successful power-on and entry into AC mode.
- Battery Boot: Connect to battery, press the power-on button to establish a working power source. The system will automatically turn on. After a period of time, the panel will display battery mode, indicating successful power-on and entry into battery mode.
Shutdown Steps:
When the system is in battery mode or AC mode output, press the switch again, then the system will be turned off.
5.2 Operation and Display Panel
The operation and display panel, located on the front of the inverter, includes three indicators, four function keys, and an LCD display. These elements provide information on operating status and input/output power.
LED Indicators:
| LED Indicator | Color | State | Messages |
|---|---|---|---|
| AC/INV | Green | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by battery or PV in battery mode. | ||
| CHG | Green | Solid On | Battery is fully charged. |
| Flashing | Battery is charging. | ||
| FAULT | Red | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
5.3 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the UP or DOWN buttons to select setting programs, then press ENTER to confirm the selection or ESC to exit.
Key Settings:
- Program 04 (AC Output Mode): Select "PAL" for parallel operation in single phase. For three-phase output, select "3P1", "3P2", or "3P3" depending on the phase the inverter is connected to.
- Program 05 (Battery Type): Select AGM, Flooded, or User-Defined. If User-Defined, battery charge voltage, low DC cut-off voltage, and dual cut-off voltage can be set in programs 26, 27, 29, and 61.
- Program 09 (Output Frequency): Set to 50Hz or 60Hz.
- Program 26 (Bulk Charging Voltage): Set the bulk charging voltage for the battery.
- Program 27 (Floating Charging Voltage): Set the floating charging voltage for the battery.
- Program 30 (Battery Equalization): Enable or disable battery equalization.
- Program 35 (Equalization Interval): Set the interval for battery equalization (0 to 90 days).
- Program 37 (BMS Function Switch): Enable or disable BMS communication.
- Program 43 (Solar Supply Priority): Choose whether solar energy prioritizes charging the battery or supplying loads.
Operating Mode Description:
The LCD display shows various operating modes and statuses:
- Standby Mode: Inverter is off, but can charge battery from PV or utility.
- Line Mode: Output power from utility, charger available. Can also show PV energy, battery power, and utility providing power to load, or PV energy charging battery and feeding remaining energy to the grid.
- Battery Mode: Output power from battery or PV.
- Only PV Mode: PV provides power to the load.
Battery Equalization:
The equalization function helps reverse the buildup of negative chemical effects in batteries, such as stratification and sulfation, which can reduce battery capacity. It is recommended to equalize batteries periodically.
To apply equalization, enable it in LCD setting program 30. Then, you can set the equalization interval in program 35 or activate it immediately in program 36.

Diagram: Illustrates four charging modes (Mains priority, Solar priority, Mixed loading, Solar only) and three charge output working modes (Net, Solar, SBU).

Image: Shows support for battery-free operation, allowing the inverter to power loads directly from PV and the utility grid without batteries. Also highlights compatibility with various battery types (AGM, GEL, FLD, LI, SLD, USER) and BMS monitoring.
6. Maintenance
Regular maintenance ensures the longevity and optimal performance of your DATOUBOSS Hybrid Solar Inverter. While specific maintenance schedules are not detailed in this manual, general best practices include:
- Keep the inverter clean and free from dust and debris. Ensure ventilation openings are not blocked.
- Periodically check all wiring connections for tightness and signs of corrosion.
- Monitor the LCD display for any warning or fault codes and address them promptly.
- Ensure proper air circulation around the unit to prevent overheating.
- If using batteries, perform regular battery equalization as recommended in the operation section.
- For any complex issues or internal repairs, always contact qualified service personnel.
7. Troubleshooting
The inverter is equipped with a fault detection system that displays specific codes on the LCD screen when an issue occurs. The red LED light will be solid on, and the LCD will display the fault code.
Fault Reference Codes:
| Fault Code | Fault Event | What to do |
|---|---|---|
| 01 | Fan is locked when inverter is off. | Replace the fan. |
| 02 | Over temperature or NTC is not connected well. | Check if the air flow of the unit is blocked or if the ambient temperature is too high. |
| 03 | Battery voltage is too high. | Check if specifications and quantity of batteries meet requirements. |
| 04 | Battery voltage is too low. | Re-charge battery. Replace battery. |
| 05 | Output short circuited or over temperature is detected by internal converter components. | Check if wiring is connected well and remove abnormal load. |
| 06 | Output voltage is too high. | Reduce the connected load. |
| 07 | Over load time out. | Reduce the connected load by switching off some equipment. |
| 08 | Bus voltage is too high. | Return to repair center. |
| 09 | Bus soft start failed. | Return to repair center. |
| 51 | Over currents or surge. | Return to repair center. |
| 52 | Bus voltage is too low. | Return to repair center. |
| 53 | Inverter soft start failed. | Return to repair center. |
| 55 | Over DC voltage in AC output. | Return to repair center. |
| 57 | Current sensor failed. | Return to repair center. |
| 58 | Output voltage is too low. | Return to repair center. |
| 59 | PV voltage is over limitation. | Reduce the number of PV modules in series. |
Warning Indicators:
The red LED flashes, and the LCD displays an alarm code, but the inverter does not enter failure mode.
| Warning Code | Warning Event | Audible Alarm |
|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second |
| 02 | Over temperature | None |
| 03 | Battery is over-charged | Beep once every second |
| 04 | Low battery | Beep once every second |
| 07 | Overload | Beep once every 0.5 second |
| 10 | Output power derating | Beep twice every 3 seconds |
| 15 | PV energy is low. | Beep twice every 3 seconds |
| 16 | High AC input (>280VAC) during BUS soft start | None |
| E9 | Battery equalization | None |
| 6P | Battery is not connected | None |
8. Specifications
General Specifications:
| Attribute | Value |
|---|---|
| Brand Name | DATOUBOSS |
| Model Number | DT4811B |
| Type | Solar Inverter |
| Rated Capacity | 11KW |
| Certification | CE, FCC, pse |
| Output Frequency | 50/60Hz |
| Nominal Input Frequency | 50Hz/60Hz (Auto Adaptive) |
| Output Voltage | 220/230/240VAC±5% |
| Waveform | Pure Sine Wave |
| Transfer Time (adjustable) | Computers (UPS Mode) 10ms, Appliance (APL Mode) 20ms |
| Peak Power | 22KW |
| Peak Efficiency (battery Mode) | >98% |
| Battery Voltage | 48Vdc |
| PV Charging Model | MPPT Dual MPPT |
| MAX.PV Input Power | 2*5500W |
| MPPT Tracking Range | 90-500 Vdc |
| MAX.PV Input Voltage | 500Vdc |
| MAX.PV Charging Current | 150A |
| RS232 | Baud Rate 2400 |
| Noise | ≤50db |
Detailed Technical Datasheet:
| Model | 2024P | 3024M | 3524M | 3024MH | 3624MH | 5048MH | 5548MH | 6248MH | 8048MH | 11048MH |
|---|---|---|---|---|---|---|---|---|---|---|
| Input Sources | L+N+PE | |||||||||
| Rated Input Voltage | 220/230/240VAC | |||||||||
| Voltage Range | 90-280VAC±3V (APL Mode) / 170-280VAC±3V (UPS Mode) | |||||||||
| Frequency | 50Hz/60Hz (Auto Adaptive) | |||||||||
| Rated Capacity | 2000W | 3000W | 3500W | 3000W | 3600W | 5000W | 5500W | 6200W | 8000W | 11000W |
| Output Voltage | 220/230/240VAC±5% | |||||||||
| Output Frequency | 50/60Hz±0.1% | |||||||||
| Waveform | Pure Sine Wave | |||||||||
| Transfer Time (adjustable) | Computers (UPS Mode) 10ms, Appliance (APL Mode) 20ms | |||||||||
| Peak Power | 4000VA | 6000VA | 7000VA | 6000VA | 7200VA | 10000VA | 11000VA | 12400VA | 16000VA | 22000VA |
| Peak Efficiency (battery Mode) | >93% | >94% | >94% | >94% | >98% | >98% | >98% | >98% | >98% | >98% |
| Battery Voltage | 24Vdc | 24Vdc | 24Vdc | 48Vdc | 48Vdc | 48Vdc | 48Vdc | 48Vdc | 48Vdc | 48Vdc |
| Constant Charging Voltage (Adjustable) | 28.2Vdc | 28.2Vdc | 28.2Vdc | 56.4Vdc | 56.4Vdc | 56.4Vdc | 56.4Vdc | 56.4Vdc | 56.4Vdc | 56.4Vdc |
| Float Charging Voltage (Adjustable) | 27Vdc | 27Vdc | 27Vdc | 54Vdc | 54Vdc | 54Vdc | 54Vdc | 54Vdc | 54Vdc | 54Vdc |
| PV Charging Mode | PWM | MPPT | MPPT | MPPT | MPPT | MPPT | MPPT | MPPT | Dual MPPT | Dual MPPT |
| MAX PV Input Power | 1200W | 1500W | 1500W | 5000W | 5000W | 6200W | 6200W | 6200W | 2*5500W | 2*5500W |
| MPPT Tracking Range | N/A | 30-145 Vdc | 30-145 Vdc | 60-500 Vdc | 60-500 Vdc | 60-500 Vdc | 60-500 Vdc | 60-500 Vdc | 90-500 Vdc | 90-500 Vdc |
| Best voltage | 30-32V | 30-115V | 30-115V | 300-400V | 300-400V | 300-400V | 300-400V | 300-400V | 300-400V | 300-400V |
| MAX PV Input Voltage | 80Vdc | 150Vdc | 145Vdc | 500Vdc | 500Vdc | 500Vdc | 500Vdc | 500Vdc | 500Vdc | 500Vdc |
| MAX PV Charging Current | 50A | 60A | 60A | 100A | 120A | 100A | 100A | 120A | 150A | 150A |
| MAX AC Charging Current | 50A | 60A | 60A | 60A | 100A | 60A | 60A | 100A | 120A | 150A |
| MAX. Charging Current | 100A | 120A | 120A | 100A | 120A | 100A | 100A | 120A | 150A | 150A |
| Operating Temperature | -10-50°C | |||||||||
| Humidity | 20%~95% (Non-condensing) | |||||||||
| Storage Temperature | -15-60°C | |||||||||
| Altitude | Altitude Not Over 1000m, Derating over 1000m, Max 4000m. Refer to IEC62040 | |||||||||
| Noise | <50db | |||||||||
9. User Tips
- For optimal performance, ensure all parallel inverters share the same battery bank. This prevents voltage differences that could lead to fault modes.
- When setting up three-phase parallel systems, remember that a minimum of three inverters is required.
- Always double-check wiring polarity and connections before powering on to avoid damage.
- If using appliances like air conditioners, be aware that they may require a 2-3 minute restart delay. Ensure your inverter settings or appliance features account for this to prevent damage during power fluctuations.
- Regularly monitor the LCD display for any fault or warning codes and consult the troubleshooting section for solutions.
10. Warranty and Support
For warranty information, technical support, or service requests, please contact your local DATOUBOSS dealer or authorized service center. Ensure you have your product model number (DT4811B) and serial number ready when contacting support.
If errors persist after following the troubleshooting guide, it is recommended to seek professional assistance.
For the complete user manual in PDF format, please refer to the official document: DATOUBOSS 11kW Hybrid Solar Inverter User Manual (PDF).