1. Introduction
The LILYTECH ZL-7802D is a versatile temperature and humidity controller designed for various applications, including incubators, climate rooms, and warehouses. It offers both PID and on/off temperature control, with an internal control resolution of 0.01°C for precise management. The unit features an integrated SSR with a 5A power driving ability, and supports optional external SSR-DA for heavier loads. With its auxiliary outputs, the controller can manage multiple environmental factors effectively.
2. Package Contents
Please check the package for the following items:
- 1 x ZL-7802D Temperature and Humidity Controller
- 1 x Combined Temperature and Humidity Sensor
- 1 x USB Communication Cable
- 1 x Fuse
- 1 x Fuse Holder/Connectors
3. Specifications
| Feature | Specification |
|---|---|
| Model Number | ZL-7802D |
| Display Type | LCD Display |
| Temperature Sensor | NTC, R25°C = 10K, B25/50°C = 3470K |
| Setting Range | -40.0 ~ 99.9°C (Temperature), 10.0 ~ 90.0%RH (Humidity) |
| Temperature Resolution | 0.1°C (0.18°F) |
| Power Supply | 100-240Vac, 50/60Hz |
| Temperature Output (R5) | Integrated SSR, 5A, 250Vac (resistance load) |
| External SSR Output (Y+, Y-) | 4-20mA, 12Vdc |
| Humidity Output (R2) | 10A, 250Vac (resistance load) |
| Output R1 | 7A, 250Vac (resistance load) |
| Output R3/R4 | 3A, 250Vac (resistance load) |
| Working Environment | -10 ~ 45°C, 5 ~ 85%RH (without dew) |
| Protection Level | IP65 (Front panel only) |
| Case Dimension | L78 x W34.5 x D71 (mm) |
| Drilling Size | L 71 x W29 (mm) |
| Communication Interface | Serial Port |
| Weight | 0.25 kg |
4. Installation
Follow these steps to install the ZL-7802D controller:
- Insert the controller into the prepared mounting hole.
- Slide the provided bracket to fix the device securely in place.
5. Wiring Diagram
WARNING: Electrical wiring must be performed by a certified electrician. Ensure power is disconnected before wiring to prevent damage or injury. Incorrect wiring will damage the device.
Connect the controller according to the following diagram. Do not route the sensor bundle together with power supply bundles to avoid interference.
Key Connections:
- Power Supply (7, 8, 9, 10): Connect 100~240Vac to terminals L (Live) and N (Neutral). Terminal 10 is for the R5 Heater output fuse.
- Outputs (1-6):
- R1 (Fan): Terminals 1 (COM) and 2 (7A 250V).
- R2 (Humidity): Terminals 3 (COM) and 4 (10A 250V).
- R3 (Left-turning): Terminal 5 (3A 250V).
- R4 (Right-turning): Terminal 6 (3A 250V).
- Humidity Sensor: Connect to the dedicated 3-pin connector.
- Temperature Sensor (t1, DI): Terminals 13, 14, 15.
- EX-SSR (External SSR): Terminals 11 (Y+) and 12 (Y-).
6. Display Icons
The ZL-7802D uses various icons on its LCD display to indicate status and functions:
| Icon | Function | On | Blink | Off |
|---|---|---|---|---|
| Heating | Heating | SSRs on (PID controlling if U73=0) | SSRs off | |
| Humidifying | Humidifying | R2 on | Delay protection, R2 on | R2 off |
| Day | Incubation days | Has incubated for set days | ||
| A | Alarming | Alarming | Alarming | |
| AT | PID Auto Tune | Will start AT | Auto tuning | |
| ✔ | Set parameter | Parameter setting | ||
| R1 on/off | R1 on/off | R1 timer on | R1 over limit on | R1 off |
| Left turning R3 | Left turning R3 | R3 on | Start left turning, R3 on, icon blinks for 30 sec. | R3 off |
| Right turning R4 | Right turning R4 | R4 on | Start right turning, R4 on, icon blinks for 30 sec. | R4 off |
Note: Both 'Heating' and 'Humidifying' icons blink when egg turning times have reached the set times.
7. Operation
7.1. Setting Setpoints (Temperature & Humidity)
- Press and hold the S button for 3 seconds. The display will show the current temperature setpoint ('t' + setpoint) or humidity setpoint ('H' + setpoint).
- Press S to switch between temperature and humidity setpoint status.
- Use the ▲ or ▼ buttons to adjust the setpoint value. Holding the button will fast-set the value.
- Press and hold the S button for 3 seconds again to save the settings and exit.
If there is no key operation for 30 seconds, the settings will not be saved, and the unit will exit the setting status.
7.2. Parameter Code Table (Excerpt)
The controller has various configurable parameters. Here are some key ones:
| Code | Function | Range | Factory Set |
|---|---|---|---|
| U10 | Temperature setpoint up limit | U11 ~ 99.9°C | 99.9 |
| U11 | Temperature setpoint low limit | -40.0°C ~ U10 | -40.0 |
| U16 | Temperature hysteresis | 0.0 ~ 20.0°C | 0.2 |
| U30 | Temperature calibration | -20.0 ~ 20.0°C | 0.0 |
| U46 | Output R1 working mode | 0-3 | 2 |
| U50 | Humidity hysteresis | 0.1 ~ 20%RH | 2.0 |
| U52 | Humidity calibration | -20.0 ~ 20.0%RH | 0.0 |
| U60 | Egg turn times set | 0 ~ 999 | 0 |
| U69 | Max incubation days set | 0 ~ 999 day | 30 |
| U73 | Temperature control mode | 0-1 | 0 |
| P | Proportion parameter: Kp | 0.1 ~ 9999 | 2.6 |
| I | Integration parameter: Ti | 0 ~ 9999 | 500 |
| d | Differential parameter: Td | 0 ~ 9999 | 50 |
For a complete list of parameters and their detailed descriptions, please refer to the full PDF manual.
7.3. Temperature Control (R5 & EX-SSR)
The ZL-7802D supports two temperature control modes, configured by parameter U73:
- PID Control (U73 = 0): Provides precise temperature regulation.
- ON/OFF Control (U73 = 1): Uses hysteresis for simpler control.
- If Room temp. ≥ Temp. setpoint, R5 and external SSR de-energize.
- If Room temp. ≤ Temp. setpoint - [Temperature hysteresis U16], R5 and external SSR fully energize.
7.4. Humidity Control (R2)
- If Room humidity ≥ Humidity setpoint, R2 de-energizes.
- If Room humidity ≤ Humidity setpoint - [Humidity hysteresis U50], and R2 has stopped for [R2 delay protection time U51], R2 energizes.
7.5. Egg Turning Control (R3/R4)
Outputs R3 and R4 are universal timer outputs, primarily designed for incubator egg turning.
- Timer Function:
- During [Left turn R3 time U62], R3 energizes, R4 de-energizes.
- During [Right turn R4 time U64], R4 energizes, R3 de-energizes.
- One full egg turn = one left turn + one right turn. The egg turn counter tracks the number of full egg turns.
- Manual Egg Turning:
- Hold ▲ for 3 seconds to start right egg turning (R4 energized, R3 de-energized).
- Hold ▼ for 3 seconds to start left egg turning (R3 energized, R4 de-energized).
- Reset Egg Turn Counter: Hold S and ▼ simultaneously for 5 seconds. Display shows "cnt" + "Clr", then resets.
7.6. Incubation Days
- Check Incubation Days: Press S and ▲ simultaneously to display "day" + "value" for 2 seconds.
- Reset Incubation Days Counter: Hold S and ▲ simultaneously for 5 seconds. Display shows "day" + "Clr", then resets.
7.7. PID Auto Tuning (AT)
Auto-tuning helps optimize PID parameters for the best temperature control. Refer to the full PDF manual for detailed steps.
8. Error Codes and Alarms
The controller displays specific codes to indicate issues:
| Display | Remark |
|---|---|
| E1 | NTC sensor failure |
| E2 | Humidity sensor failure |
| tHi | High temperature warning |
| tLo | Low temperature warning |
| HHi | High humidity warning |
| HLo | Low humidity warning |
| A | External digital input alarming |
| At1-At4 | PID auto tuning fails (various reasons) |
| SUc* | PID auto tuning success |
| UnL | Restore to factory settings |
When an alarm occurs, the buzzer will sound (if U71=1), and relevant outputs may de-energize. Press P to stop beeping.
9. Maintenance
- Sensor Calibration: The temperature and humidity sensors can be calibrated using parameters U30 and U52 respectively.
- Cleaning: Keep the controller and sensors clean and free from dust or debris.
- Environment: Avoid operating the device in corrosive, wet, or strong electrical-magnetic field environments.
- Restore to Factory Settings: Hold P and ▲ simultaneously for 3 seconds until "UnL" displays. Then press S 3 times to restore all parameters to factory defaults, including the password.
10. Troubleshooting
If you encounter issues, refer to the error codes section (Section 8) and the following common troubleshooting tips:
- Display shows E1 or E2: Indicates a sensor failure. Check the sensor connection or replace the sensor.
- Temperature/Humidity readings are inaccurate: Consider calibrating the sensors (U30 for temperature, U52 for humidity).
- Outputs not switching: Check wiring according to the diagram. Verify setpoints and hysteresis settings. Ensure the working mode (U46) is correctly configured.
- Controller not responding: Ensure the power supply is stable (100-240Vac). Check for any overload conditions.
- PID Auto Tuning fails (At1-At4): This can be due to temperature interference, abnormal oscillation, or timeout. Ensure the heater power rate (U74) is appropriate and there are no external disturbances during tuning.
11. User Tips
No specific user tips from reviews or Q&A were provided for this product. However, general advice for similar controllers includes:
- Always double-check wiring before applying power.
- For critical applications, consider using an external SSR-DA for heating elements with higher current draw or inductive loads.
- Regularly clean the sensor to maintain accuracy, especially in dusty or humid environments.
12. Safety Warnings
- Electrical Safety: All wiring must be performed by a qualified electrician. Disconnect power before any installation or maintenance.
- Overload Protection: If the temperature heater power rate is high, or if there are inductive loads (e.g., coil wired heaters), use an external SSR-DA instead of the integrated SSR. For other large loads or capacitive/inductive loads (e.g., many humidifiers), consider using an intermediate relay, SSR-AA, or magnetic contactor.
- Environmental Conditions: Avoid working in corrosive, wet, and strong electrical-magnetic field environments.
- Warranty: Overload damage or damage due to wrong usage/connection is not covered under warranty.
13. Warranty and Support
This device has been thoroughly checked before shipment. A warranty period of one year is provided from the date of purchase. The warranty does not cover damage caused by incorrect usage, improper wiring, or other user-induced faults.
For detailed warranty terms, technical support, or further inquiries, please refer to the official product manual PDF:
Official PDF Manual: https://www.suzhoulily.com/pdf/ZL-7802D_V1.0b_en.pdf