DATOUBOSS DT-3U-4862S-A-EU

Contents

DATOUBOSS 48V 6.2kW 3U Rack-Mounted Hybrid Inverter User Manual

Model: DT-3U-4862S-A-EU

1. Introduction

1.1 Purpose

This manual describes the assembly, installation, operation, and troubleshooting of the DATOUBOSS 48V 6.2kW 3U Rack-Mounted Hybrid Inverter. Please read this manual carefully before installations and operations, and keep it for future reference.

1.2 Scope

This manual provides safety and installation guidelines as well as information on tools and wiring.

1.3 Product Overview

The DT4862S is a high-performance, rack-mounted hybrid inverter that integrates an inverter, MPPT solar charger, and utility charger into one compact 3U unit. Designed explicitly for residential and small commercial applications, it delivers a robust 6200W continuous output, making it the cornerstone of a reliable and efficient photovoltaic energy storage system.

Its comprehensive LCD display offers user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

DATOUBOSS 48V 6.2kW Hybrid Inverter front view with key features
Figure 1: DATOUBOSS 48V 6.2kW Hybrid Inverter front view, highlighting 8500W Max PV Input, 120A Max PV Charging Current, 500V Max PV Voltage, and Pure Sine Wave output.
DATOUBOSS 6200W Hybrid Solar Inverter side view with specifications
Figure 2: DATOUBOSS 6200W Hybrid Solar Inverter side view, detailing Rated Output Power (6200W), Max PV Input Power (8500W), Battery Voltage (48V), Max PV Input Current (27A), MPPT Voltage Range (60-500VDC), Max PV Input Voltage (500V), Operating Temperature (-10°C~50°C), Max Charging Current (120A), and Max AC Charging Current (100A).

1.4 Features

  • Pure sine wave inverter
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible with mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/Over temperature/short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function

1.5 Basic System Architecture

The following illustration shows a typical application for this inverter/charger. It can be integrated with a generator or utility grid and PV modules to form a complete running system.

Solar Power Generation System diagram
Figure 3: Diagram of a solar power generation system, showing energy flow from solar panels to the inverter stack, providing residential electricity and connecting to the power grid.

This inverter can power all kinds of appliances in home or environment, including motor-type appliances such as tube light, fan, refrigerator, and air conditioner.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION: To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION: Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for the details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

3. Installation

3.1 Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:

  • The unit x 1
  • User manual x 1

3.2 Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
  • The ambient temperature should be within the range of 20~35°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

3.2.1. Bracket Installation

  • Before installing the stacking brackets, first remove the four fixing screws on the back of the device.
  • Align both sides of the device accurately with the bracket slot positions.
  • Ensure the device is fully snapped into the brackets and properly installed in place.
  • Using the provided screws, securely fasten the brackets on both sides (using a Phillips screwdriver is recommended).

3.2.2. Equipment Stacking

  • Ensure the bottom-layer device is securely installed on the bracket.
  • Align the upper-layer device vertically with the stacking interface of the lower-layer device.
  • Gently lower the upper-layer device, ensuring a complete fit without any wobbling.

3.2.3. Safety Inspection

  • Check that all connection points are secure.
  • Ensure there is no tilting or loosening of the equipment after stacking.

3.3 Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.

Rated Capacity Typical Amperage Battery capacity Wire Size Ring Terminal Dimensions Torque value
Cable(mm²) D(mm) L(mm)
6.2KVA 128A 200AH 1*2AWG (38) 8.4 39.2 5Nm
2*4AWG (25) 8.4 33.2

Please follow below steps to implement battery connection:

  1. Assemble battery ring terminal based on recommended battery cable and terminal size.
  2. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

3.4 AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the Inverter can be disconnected during maintenance and fully protected from over current of AC input. The recommended spec of breaker is 32A for 24V system and 63A for 48V system.

CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for AC wires:

Rated Capacity Gauge Torque Value
6.2KVA 10AWG 1.4-1.6Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N3 mm.
  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (Ground) first.
  • Ground (yellow-green)
  • L-LINE (brown or black)
  • N-Neutral (blue)

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

  1. Make sure the wires are securely connected.

CAUTION: Appliances such as air conditioner are required at least 2-3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trigger overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.

3.5 PV Connection

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for PV wires:

Typical Amperage Gauge Torque Value
30A 12AWG 1.4-1.6Nm

PV module selection:

When choosing the right PV module, be sure to first consider the following requirements:

The open circuit voltage (Voc) of the PV modules does not exceed the maximum PV array open circuit voltage of the inverter. The maximum supply voltage of the PV modules should be close to the optimal PV access voltage range of the inverter for best performance. If one PV module cannot meet this requirement, it is necessary to connect multiple PV modules in series.

PV Module Wire Connection:

Please follow below steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Fix wire cover to the inverter with supplied screws as shown in below chart.
  4. Check correct polarity of wire from PV modules and PV input connectors. Then, connect positive pole(+) of connection wire to positive pole(+) of PV input connector. Connect negative pole (-)of connection wire to negative pole(-) of PV input connector. Screw two wires tightly in clockwise direction. Recommended tool: 4mm blade screwdriver.
Detailed Specifications and Connection Diagram
Figure 4: Detailed specifications and connection diagram for Solar, Electricity Grid, Battery, and AC output, showing MAX.PV Input Power (8500W), MAX.PV Input Current (27A), MAX. AC charging current (120A), MAX. charging current (120A), MPPT Tracking Range (60-500 V DC), Best voltage (360-430 V DC), MAX.PV Input Voltage (500 V DC), Output voltage (220/230/240VAC ±5%), Feed into the grid voltage range (100-280VAC), Feed into the grid frequency range (47-53±1Hz/57-62±1Hz), Nominal output current (26.9 A), Maximum conversion efficiency (DC/AC): 98%, Battery voltage (48V DC), Constant charging voltage (56.4V DC), Floate charging voltage (54V DC), Rated Power (6200W), Output Voltage (220/230/240 VAC ±5%), Output Frequency (50/60 Hz ±0.1%), Peak Power (12,400 VA), Waveform (Pure Sine Wave).

The CT Operation Guide

With CT connected, the hybrid inverter can be easily integrated into the existing household system. It's to arrange self-consumption via CT to control power generation and battery charging of the Inverter.

1. Single commissioning
  1. Step 1. Power off the inverter and connect the external CT by using the tool accessory to install on the spring terminal block. Be noted the mark of current flow direction on the CT should point to the Inverter and the polarity on connecting CT wires on the terminal block should be followed as "L+" VS red wire and "L-" VS black wire.
  2. Step 2. Power on the inverter.
  3. Step 3. Enter LCD setting on the inverter with CT sensor connected and set CT function to "PEC".

4. Operation

4.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the button of the case) to turn on the unit.

4.1.1 Steps to start up

Connect the battery that meets the requirements (battery voltage needs to be beyond 23V) or AC (AC needs to confirm the suitable input range depending on the output mode), then you can start up the inverter.

Mains power on

Connect to normal AC power, press the switch, the system will automatically turn on. If you set AC output power priority, after waiting for a period of time, the panel will display AC mode that represents turn on the machine successfully, then will enter the AC mode.

When the normal mains power is connected and press the power-on button then the system will automatically power on. If it is set as AC output priority, after a period of time, the panel will display the AC mode to indicate that the power-on is complete and enter the AC mode.

Battery boot

Connect to battery, press the power-on button to establish a working power source.

The system will automatically turn on, after waiting for a period of time, the panel will display battery mode that represents turn on the machine successfully, then will enter the battery mode.

4.1.2 Shutdown steps

When the system is in battery mode or AC mode output, press the switch again, then the system will be turned off.

4.2 Operation and Display Panel

The operation and display panel, shown in the chart below, is on the front panel of the inverter. It includes three indicators, four function keys and an LCD display, indicating the operating status and input/output power information.

Smart Display Screen diagram
Figure 5: Smart Display Screen, showing LCD display, Status indicator (AC/INV), Charging indicator (CHG), Fault indicator (FAULT), and control buttons (ESC, UP, DOWN, ENTER).

LED Indicator

LED Indicator Messages
AC/INV Green Solid On Output is powered by utility in Line mode.
Green Flashing Output is powered by battery or PV in battery mode.
CHG Yellow Solid On Battery is fully charged.
Yellow Flashing Battery is charging.
FAULT Red Solid On Fault occurs in the inverter.
Red Flashing Warning condition occurs in the inverter.

Function Keys

Function Key Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode

4.3 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button exit.

Setting Programs:

Program Description Selectable option
00 Exit setting mode Escape (ESC 00)
01 Output source priority selection Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, Utility energy will supply power to the loads at the same time. (SUL 01)
Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. (SBU 01)
Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12 or solar and battery is not sufficient. (UTI 01)
If solar energy is sufficient to all connected loads and charge battery, the solar energy could feedback to the grid (sell power to grid). If solar energy is not sufficient to power all connected loads, Utility energy will supply power to the loads at the same time. (SUF 01)
The units will not only provide power to the connected load but also give power to connected home load. If PV power and battery power is insufficient, it will take grid energy as supplement. The units will not sell power to grid. In this mode, a CT can be used. The installation method of the CT please refer to chapter about CT connection. The external CT will detect power flowing back to the grid and will reduce the power of the inverter only to supply the local load, charge battery and home load. (PEC 01)
05 Battery type User-Defined 2 (suitable when lithium battery without BMS communication) (US2 05). If selected, battery charge voltage and low DC cut-off voltage can be set up in program 26 and 29. Program 26 and 27 will be set to the same voltage automatically (full charging voltage point of lithium battery).
06 Auto restart when overload occurs Restart disable (LHD 06) / Restart enable (LHE 06)
07 Auto restart when over temperature occurs Restart disable (LHD 07) / Restart enable (LHE 07)
08 ECO function: System will temporarily stop when the load is low in battery mode. disable (ECO SDS 08) / enable (ECO SEN 08)
09 Output frequency 50Hz (50 09) / 60Hz (60 09)
10 Output voltage 220V (220 10) / 230V (default) (230 10) / 240V (240 10)
11 Maximum utility charging current. Note: If setting value in program 02 is smaller than that in program in 11, the inverter will apply charging current from program 02 for utility charger. 30A (default) (30A 11). Setting range is 2A, then from 10A to max.AC charging current. Increment of each click is 10A.
12 Setting voltage point back to utility source when selecting "SBU priority" in program 01. 23.0V (default) (230 12). Setting range is from 22V to 25.5V. Increment of each click is 0.5V. (Available options in 24 system model).
13 Setting voltage point back to battery mode when selecting "SBU priority" in program 01. 27V (default) (FUL 13). Setting range is from 24V to 29V. Increment of each click is 0.5V. (Available options in 24 system model).
16 Charger source priority: To configure charger source priority. Solar first (CSO 16) / Solar and Utility (default) (SNU 16) / Only Solar (OSO 16) / Solar residual (SAT 16)
17 Battery reboot voltage default (FUL 53.5 17)
18 Alarm control Alarm on (default) (AON 18) / Alarm off (AOF 18)
19 Auto return to default display screen Return to default display screen (default) (ESP 19) / Stay at latest screen (HEP 19)
20 Backlight control Backlight on (default) (LON 20) / Backlight off (LOF 20)
22 Beeps while primary source is interrupted Alarm on (default) (AON 22) / Alarm off (AOF 22)
23 Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. Bypass disable (default) (BYP 23) / Bypass enable (BYE 23)
24 Battery low voltage. If battery power is only power source available, inverter will alarm. Battery low voltage 44.0V (LOV 440 24). Setting range is from 20.0V-27.0V for 24V system and 40.0V-54.0V for 48V system.
25 Record fault code Record enable (default) (FEN 25) / Record disable (FGS 25)
26 Bulk charging voltage (C.V voltage) 24V system default setting: 28.2V (CUV 28.2 26) / 48V system default setting: 56.4V (CUV 56.4 26). If self-defined is selected in program 5, this program can be set up. Setting range is from 24.0V to 30.0V for 24V system and 48.0V to 60.0V for 48V system. Increment of each click is 0.1V.
27 Floating charging voltage 24V system default setting: 27.0V (FLU 27.0 27) / 48V system default setting: 54.0V (FLU 54.0 27)
28 Reset factory setting default: Std OFF 28 / Std ON 28
29 Low DC cut-off voltage: If battery power is only power source available, inverter will shut down. If PV energy and battery power are available, inverter will charge battery without AC output. 24V system default setting: 21.0V (COV 21.0 29) / 48V system default setting: 42.0V (COV 42.0 29). If self-defined is selected in program 5, this program can be set up. Setting range is from 20.0V to 26.0V for 24V system and 40.0V to 52.0V for 48V system. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected.
30 Battery equalization Battery equalization disable (default) (EDS 30) / Battery equalization enable (EEN 30). If "Flooded" or "User Defined" is selected in program 05, this program can be setup.
31 Battery equalization voltage 24V system default setting: 29.2V (EUV 29.2 31) / 48V system default setting: 58.4V (EUV 58.4 31). Setting range is from 24.0V to 30.0V for 24V system and 48.0V to 60.0V for 48V system. Increment of each click is 0.1V.
33 Battery equalized time 60min (default) (60 33). Setting range is from 5min to 900min. Increment of each click is 5min.
34 Battery equalized timeout 120min (default) (120 34). Setting range is from 5min to 900min. Increment of each click is 5min.
35 Equalization interval 30days (default) (30d 35). Setting range is from 0 to 90 days. Increment of each click is 1 day.
36 Equalization activated immediately Enable (EEN 36) / Disable (default) (ADS 36). If "Enable" is selected, it will activate battery equalization immediately. If "Disable" is selected, it will cancel equalization function until next activated equalization time arrives.
37 BMS Function Switch off (default) (BMS OFF 37) / on (BMS ON 37). Whether to enable the BMS communication function.
38 Bat Soc Under Lock If any type of lithium battery is selected in program 5. BMS low voltage SOC value, if the BMS SOC value is lower than the set value, the inverter will shut down to protect the battery. (BSL 10 38)
39 Bat Soc Turn To Ac If any type of lithium battery is selected in program 5. When the working mode of the inverter is set to the battery priority mode, the inverter will be forced to enter the mains charging when the SOC of the BMS is lower than the set value. (BST 20 39)
40 Bat Soc Turn To Dc If any type of lithium battery is selected in program 5. When the working mode of the inverter is set to the battery priority mode, the inverter resumes the DC working mode when the SOC of the BMS is higher than the set value. (BSD 95 40)
41 Bat Restart Soc If any type of lithium battery is selected in program 5. When the inverter is turned on, the SOC must be higher than the set value to work normally. (BSR 50 41)
45 Reset PV energy storage Not set (default) (NRS 45) / Reset (RST 45)
46 Start charging time for AC charger 00:00 (default) (SCT 00.0 46). The setting range of start charging time for AC charger is from 00:00 to 23:00, increment of each click is 1 hour.
47 Stop charging time for AC charger 00:00 (default) (SCT 00.0 47). The setting range of scheduled Time for AC output on is from 00:00 to 23:00, increment of each click is 1 hour.
48 Scheduled time for AC output on 00:00 (Default) (ON 00.0 48). The setting range of scheduled Time for AC output off is from 00:00 to 23:00, increment of each click is 1 hour.
49 Scheduled time for AC output off 00:00 (Default) (OFF 00.0 49). The setting range of scheduled Time for AC output off is from 00:00 to 23:00, increment of each click is 1 hour.
50 Set country customized regulations Mode 1 (IND 50): If selected, acceptable feed-in grid voltage range will be 195.5-253VAC. Acceptable feed-in grid frequency range will be 49-51Hz.
Mode 2 (GEN 50): If selected, acceptable feed-in grid voltage range will be 184-264.5VAC. Acceptable feed-in grid frequency range will be 47.5-51.5Hz.
Mode 3 (SAD 50): If selected, acceptable feed-in grid voltage range will be 184-264.5VAC. Acceptable feed-in grid frequency range will be 57-62Hz.
Mode 4 (PAH 50): If selected, acceptable feed-in grid voltage range will be 170-264.5VAC. Acceptable feed-in grid frequency range will be 47.5-53.5Hz.
Mode 5 (Default) (026 50): If selected, acceptable feed-in grid voltage range will be 100-280VAC. Acceptable feed-in grid frequency range will be 47.5-53.5Hz.
51 Time setting-Minute For minute setting, the range is from 00 to 59. (MIN 00 51)
52 Time setting-Hour For hour setting, the range is from 00 to 23. (HOU 00 52)
53 Time setting-Day For day setting, the range is from 00 to 31. (DAY 01 53)
54 Time setting-Month For month setting, the range is from 1 to 12. (MON 01 54)
55 Time setting-Year For year setting, the range is from 16 to 99. (YER 16 55)
56 GRID-tie power 6.2KW (6.2KW 56). Increment of each click is 200W.
58 Set the input power of the mains power 0.15KW (default) (2EP 0.15 58). Setting range is from 0.01KW to 0.5KW. Increment of each click is 0.01KW.
59 Max battery discharge current setting 200 (default) (DIC 200 59). When the battery discharge current is more than the setting value, the unit will alarm. The setting range is from 20 to 200.
67 Output Open Time 00.0 (DER 00.0 67). The value ranges from 0 to 23.
68 Output Stop Time 00.0 (DEO 00.0 68). The value ranges from 0 to 23.
71 Start time setting for power grid peak shaving 00:00 (Default) (LSA 00.0 71). The setting range of start time for power grid peak shaving is from 00:00 to 23:00, increment of each click is 1 hour. In PEC mode, set the start time and stop time for the battery to sell electricity according to requirements.
72 Stop time setting for power grid peak shaving 00:00 (Default) (LSO 00.0 72). The setting range of stop time for power grid peak shaving is from 00:00 to 23:00, increment of each click is 1 hour.

5. Maintenance

5.1 Battery Equalization Description

Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.

How to Apply Equalization Function

You must enable the battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in the device by either one of the following methods:

  1. Setting equalization interval in program 35.
  2. Active equalization immediately in program 36.

When to Equalize

In this stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter the Equalize stage.

Equalize charging time and timeout

In the Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage raises to the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the setting battery equalized time is arrived.

However, in the Equalize stage, when the battery equalized time is expired and the battery voltage doesn't rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the battery equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.

6. Troubleshooting

6.1 Faults Descriptions

Fault: The inverter enters the fault mode, the red LED light is always on and the LCD displays the fault code.

Fault Reference Code:

Fault Code Fault Event Icon on
F01Fan is locked when inverter is off.F01
F02Over temperature or NTC is not connected well.F02
F03Battery voltage is too high.F03
F04Battery voltage is too low.F04
F05Output short circuited or over temperature is detected by internal converter components.F05
F06Output voltage is too high.F06
F07Over load time out.F07
F08Bus voltage is too highF08
F09Bus soft start failedF09
F51Over currents or surgeF51
F52Bus voltage is too lowF52
F53Inverter soft start failedF53
F55Over DC voltage in AC outputF55
F57Current sensor failedF57
F58Output voltage is too lowF58
F59PV voltage is over limitationF59

6.2 Alarm Descriptions

Alarm: The red LED flashes, and the LCD displays an alarm code, the inverter does not enter the failure mode.

Alarm Indicator:

Alarm Code Alarm Event Audible Alarm Icon flashing
A01Fan is locked when inverter is on.Beep three times every secondA01
A02Over temperatureNoneA02
A03Battery is over-chargedBeep once every secondA03
A04Low batteryBeep once every secondA04
A07OverloadBeep once every 0.5 secondA07
A10Output power deratingBeep twice every 3 secondsA10
A15PV energy is low.Beep twice every 3 secondsA15
A16High AC input (>280VAC) during BUS soft startNoneA16
A27Max battery discharge current settingNoneA27
E9Battery equalizationNoneE9
bPBattery is not connectedNonebP

6.3 Trouble Removal

Problem LCD/LED/Buzzer Explanation/Possible cause What to do
Unit shuts down automatically during startup process. LCD/LEDs and buzzer will be active for 3 seconds and then complete off. The battery voltage is too low (<1.91V/Cell) 1. Re-charge battery.
2. Replace battery.
No response after power on. No indication. 1. The battery voltage is far too low. (<1.4V/Cell)
2. Internal fuse tripped.
1. Contact repair center for replacing the fuse.
2. Re-charge battery.
Input voltage is displayed as 0 on the LCD and green LED is flashing. Input protector is tripped 3. Replace battery.
Check if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode. Green LED is flashing Insufficient quality of AC power. (Shore or Generator) 1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UP-->appliance)
Green LED is flashing. Set "Solar First" as the priority of output source. Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly. LCD display and LEDs are flashing Battery is disconnected. Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on. Fault code 07 Overload error. The inverter is overload 105% and time is up. Reduce the connected load by switching off some equipment.
If PV input voltage is higher than specification, the output power will be derated. At this time, if connected loads is higher than derated output power, it will cause overload. Reduce the number of PV modules in series or the connected load.
Fault code 05 Output short circuited. Check if wiring is connected well and remove abnormal load.
Fault code 02 Temperature internal converter component is over 120°C. Internal temperature of inverter component is over 100°C. Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 03 Battery is over-charged. The battery voltage is too high. Return to repair center. Check if spec and quantity of batteries are meet requirements.
Fault code 01 Fan fault Replace the fan.
Fault code 06/58 Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) 1. Reduce the connected load.
2. Return to repair center.
Fault code 08/09/53/57 Internal components failed. Return to repair center.
Fault code 51 Over current or surge. Restart the unit, if the error happens again, please return to repair center.
Fault code 52 Bus voltage is too low.
Fault code 55 Output voltage is unbalanced.
Fault code 59 PV input voltage is beyond the specification. Reduce the number of PV modules in series.

7. Technical Specifications

Model MF-3U-4862S
Input Input Sources L+N+PE
Rated Input Voltage 220/230/240VAC
Voltage Range 90-280VAC±3V(APL Mode) / 170-280VAC±3V(UPS Mode)
Frequency 50Hz/60Hz (Auto Adaptive)
Rated Power The battery inverts 6200W
Photovoltaic inverter 6200W
Output Output Voltage 220/230/240VAC±5%
Output Frequency 50/60Hz±0.1%
Waveform Pure Sine Wave
Transfer Time (adjustable) Computers (UPS Mode) 10ms, Appliance (APL Mode) 20ms
Peak Power 12400VA
Overload capacity Battery mode: 11s@105%~150% Load; 2s@150%-200% Load, 400ms@>200% Load
Grid-connected operation Output Voltage 220/230/240VAC±5%
Feed into the grid voltage range 100-280VAC
Feed into the grid frequency range 47-53±1Hz/57-62±1Hz
Nominal output current 26.9A
Power Factor Range >0.99
Maximum conversion efficiency (DC/AC) 98%
Battery Battery Voltage 48Vdc
Constant Charging Voltage (Adjustable) 56.4Vdc
Float Charging Voltage (Adjustable) 54Vdc
Chargers PV Charging Mode MPPT
MAX.PV Input Power 8500W
MPPT Tracking Range 60-500Vdc
Best voltage 360-430V
MAX.PV Input Voltage 500Vdc
PV Max Input Current 27A
MAX.PV Charging Current 120A
MAX.AC Charging Current 100A
MAX. Charging Current 120A
Display LCD interface CAN display running mode/load/input/output, etc.
Interface RS232 Baud Rate 2400
Extend the socket communication interface Lithium Battery BMS Communication Card WifiCard
Operating Temperature -10-50℃
Environments Humidity 20%-95% (Non-condensing)
Storage Temperature -15-60°C
Altitude Altitude Not Over 1000m, Derating over 1000m, Max 4000m, Refer to IEC62040
Noise ≤50db
Standards and certification EN-IEC 60335-1, EN IEC 60335-2-29, IEC 62109-1

For a downloadable PDF version of the user manual, please refer to the official document: User Manual (PDF).

8. User Tips

  • Consider placement away from living areas due to fan noise, as the inverter's fan can be loud.
  • Familiarize yourself with the RS485 and RS232 communication ports for advanced monitoring and control.

9. Frequently Asked Questions (FAQ)

Q1: Can it work with Lithium batteries? How does BMS communication work?

A1: Absolutely. Select your lithium battery type in program 05 and connect it via the BMS/RS485 communication port on the rear panel. This enables real-time data exchange (voltage, current, SOC) for intelligent management.

Q2: How can I quickly diagnose issues if a fault occurs?

A2: The unit features a comprehensive fault (F01-F59) and alarm (A01-A27) code system. When the red fault LED illuminates, the LCD will display the specific code. Simply refer to the manual to quickly identify the issue (e.g., fan failure, over-temperature, overload) for efficient maintenance.

10. Warranty and Support

For any issues not resolved by following the troubleshooting guide, please contact your local dealer or service center for maintenance and support. Only qualified service personnel should attempt repairs.